Home | About CDC | Press Room | A-Z Index | Contact Us
CDC Centers for Disease Control and Prevention Home Page
CDC en Español
 

Inspection Detail Report

  Basic Search |  Advanced Search |  Ship Scored 100 |  Green Sheet
 
Cruise Ship: Oosterdam Cruise line: Holland America Line Inspection Date: 03/14/2009 Score: 99
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
    Cruise Ship's Corrective Action Statement

Item No.: 08
Site: Potable Water-
Violation: The hot potable water lines in some areas were striped blue and red. The air conditioning lines in the engine room were striped blue and red. The cold potable water lines were striped blue throughout the vessel. The low temperature engine cooling lines in the engine room were striped blue.
Recommendation: Do not stripe lines carrying liquids other than potable water with the same color designation used for potable water lines.
Item No.: 08
Site: Potable Water-
Violation: There were a number of entries in the cross-connection control program where the protection was listed as internal. This was for the chemical dispensers in the food areas and the soda carbonation units. The protection was air-gaps for the chemical dispensers and continuous pressure-type devices for the carbonators.
Recommendation: Ensure that the protection used for these cross-connections is listed in the cross-connection control program.
Item No.: 20
Site: Preparation Room-
Violation: Inside the new potato peeler, there were slotted fasteners around the chute.
Recommendation: Replace the slotted fasteners with smooth, low-profile, non-corroding fasteners.
Item No.: 21
Site: Bar-Lido Bar
Violation: In the technical compartment to the left of the speed rail, there was peeling sealant at the right wall/floor juncture.
Recommendation: Remove and replace the sealant.
Item No.: 22
Site: Preparation Room-Dishwash
Violation: The data plate indicating the temperatures for each cycle of the dishwash unit had very small lettering and was located on the bottom corner of the unit and under the landing.
Recommendation: Ensure that the data plate is accessible for viewing by the crew members using the dishwash machine.
Item No.: 27
Site: Preparation Room-Fish Preparation
Violation: The excess expandable foam and the area around the bulkhead penetrations were soiled.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Buffet-
Violation: In the technical compartment for the ice cream freezer, the support ledge for the compressor was soiled with food debris.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 30
Site: Other-Garbage Room
Violation: There was no waste receptacle at the handwash sink in the garbage room.
Recommendation: Ensure that a handwashing facility includes a sink, soap dispenser, single-use towels dispenser, and waste receptacle.
Item No.: 33
Site: Food Service General-Decks
Violation: The deck material was damaged around stainless steel gutterways and thresholds throughout the galley and preparation room areas.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Preparation Room-Fish Preparation
Violation: There was excess expandable foam around the two bulkhead penetrations in the technical compartment for undercounter refrigeration unit B.01.
Recommendation: Remove the excess expandable foam.
Item No.: 33
Site: Provisions-Refr. Provision #13
Violation: There was a vertical gap on the left side of the threshold.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Preparation Room-Refr. Provision #14
Violation: There were 3 bolts missing on the strip at the lower edge of the outside of the entrance door.
Recommendation: Replace the missing bolts.
Item No.: 34
Site: Galley-Italian Station
Violation: The water fountain was not working.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 36
Site: Buffet-Italian Station
Violation: The shatter-resistant coating was sliding off one of the bulbs on the taller HATCO station. This area was not in operation during the inspection.
Recommendation: Replace the shatter-resistant bulb.
Item No.: 41
Site: Children Area-
Violation: The Lego toys were not disassembled prior to cleaning and disinfection.
Recommendation: Disassemble toys prior to cleaning and disinfection.
*Inspections scores of 85 or lower are NOT satisfactory

Safer, Healthier People
Centers for Disease Control and Prevention, 1600 Clifton Rd, Atlanta, GA 30333, U.S.A
Tel: (404) 639-3311 / Public Inquiries: (404) 639-3534 / (800) 311-3435
FirstGov
DHHS
Department of Health
and Human Services