Cruise Ship: Carnival Liberty Cruise line: Carnival Cruise Lines, Inc. Inspection Date: 10/03/2009 Score: 97
 
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.



 
    Cruise Ship's Corrective Action Statement

Item No.: 03
Site: Potable Water-Production
Violation: The records indicated that the start of production and the first reading was routinely one hour apart. Per staff, the start time recorded was when the evaporators were turned on. For the first 30 minutes, the high salinity went overboard. Then the three way valve was positioned for water to be produced for the potable water tanks. This would mean the first reading would be within 30 minutes of the water going to the tanks. However, on a few occasions in the past seven months, the time between the start and the first reading was greater than one hour.
Recommendation: Ensure that potable water is continuously halogenated to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter.
Item No.: 08
Site: Potable Water-Cross-Connection Control Program
Violation: The program listed the toilets and showers by deck. However, it did not include the number of connections for each entry.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 08
Site: Potable Water-Chemical Feed Tanks
Violation: The potable water lines supplying the chemical feed tanks for production, distribution and bunkering halogen in the engine room were not striped blue.
Recommendation: Ensure that potable water piping and fittings are painted or striped auxiliary blue, or in accordance with ISO 14726, at 5 m (15 feet) intervals on each side of partitions, decks, and bulkheads in all spaces, except where the decor would be marred by such markings.
Item No.: 10
Site: Swimming Pool-
Violation: It was not clear from the records when the swimming pools were operated in sea to sea mode where chlorination was not required.
Recommendation: When the swimming pools are operated in sea to sea mode, ensure this is recorded.
Item No.: 10
Site: Whirlpool/Spa-
Violation: Per staff, the whirlpool/spa sand filters were automatically backwashed each night. A visual inspection of the water to ensure it was running clear before the backwash ended was not done.
Recommendation: Ensure that granular filters are backwashed at least daily. Repeat backwashing, if necessary, until the water viewed through the sight glass or discharge point is clean flowing.
Item No.: 16
Site: Galley-Harry's
Violation: The time as a public health control plan for hot and cold foods stated "all food out for service" was on time control. Per staff, there is no self-service for passengers. In addition, staff stated the undercounter refrigerators were on time control. These units were not listed on the plan.
Recommendation: Ensure the time as a public health control plan reflects the food operation.
Item No.: 16
Site: Food Service General-Time As A Public Health Control Plan
Violation: The time as a public health control plan did not list all the cold and hot holding units that were on time control.
Recommendation: Ensure the time as a public health control plan reflects the food operation.
Item No.: 21
Site: Galley-Harry's
Violation: The coating on the bulb at the carving station was peeling.
Recommendation: Replace the bulb.
Item No.: 21
Site: Galley-Golden Service Line
Violation: There were open seams along the front edges of the drip pan housings for the grills.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 21
Site: Galley-Potwash
Violation: The insulation around the pipe under the sanitize compartment of the three compartment sink was soiled and damaged.
Recommendation: Replace the insulation.
Item No.: 22
Site: Galley-Potwash
Violation: The soiled area was too small for the potwash area. There were many pans and trays stacked up too high and overflowing outside the soiled area.
Recommendation: Ensure that drainboards, utensil racks, or tables large enough to accommodate all soiled and cleaned items that may accumulate during hours of operation are provided for necessary utensil holding before cleaning and after sanitizing.
Item No.: 26
Site: Galley-Room Service
Violation: The insides of a few coffee lids were soiled.
Recommendation: Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 26
Site: Galley-Warewash
Violation: The inside of a few coffee lids were soiled.
Recommendation: Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 26
Site: Buffet-Beverage Station
Violation: The small nozzle on the juice machine was soiled.
Recommendation: Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 33
Site: Other-Hamburger Grill
Violation: There was recessed deck grout under the toaster.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Buffet-Taste of the Nations
Violation: The corner of the bulkhead near the decoration storage room was damaged.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Buffet-Omelet Station
Violation: There was recessed deck grout under the technical compartments for the toppings.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Galley-
Violation: There was recessed grout and damaged deck tiles around the scuppers in front of the tilting kettles.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Pantry-Ice Pantries
Violation: In several of the ice pantries, dirty dishware and glassware were stored in gray bins and brown bus tubs directly on the deck.
Recommendation: Ensure items are stored at least six inches from the deck to allow for cleaning.
Item No.: 34
Site: Galley-Fish 'n Chips
Violation: There was a leak at the supply line for the handwash station.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 34
Site: Galley-Center Galley
Violation: There was a leak from the technical compartment of tilting kettle #E3-59.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 34
Site: Galley-Potwash
Violation: There was a leak from the detergent supply line under the potwash machine.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 34
Site: Galley-Warewash
Violation: There was a drip from the deckhead above the dirty and soiled landing areas.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 34
Site: Galley-Potwash
Violation: There was a leak at the valve under the potwash machine.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 37
Site: Galley-Hot Galley
Violation: There was an excessive amount of condensate on the deckhead above the pasta cooker.
Recommendation: Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 39
Site: Galley-Center Galley
Violation: There were about 10 live and dead small flies on the bulkhead near the condensate drain line inside the walk-in cooler.
Recommendation: Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Silver Service Line
Violation: There were many small dead flies inside the overhead light covers above the cooking stations.
Recommendation: Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Center Galley
Violation: There were a few small dead flies in the overhead light cover above the CTX machine.
Recommendation: Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.
Item No.: 39
Site: Buffet-Beverage Station
Violation: There were 6 small live fruit flies on the bulkhead behind the soft serve ice cream machine and on the soft serve ice cream machine.
Recommendation: Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.