Cruise Ship: Norwegian Majesty Cruise Line: Norwegian Cruise Lines Inspection Date: 08/16/2009 Inspection Score: 97
This cruise ship inspection report lists the deficiencies found during the inspection. Additional information corresponding to each item number is available in the lastest editions of the CDC VSP Operational Manual.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 08
Site: Potable Water-Port Evaporator High Saline Discharge
Violation: There was not a proper air gap at the end of the rubber tube attached to the vent on the reduced pressure assembly device. This was corrected.
Recommendation: Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
Item No.: 08
Site: Potable Water-Technical Water Fill
Violation: There was not a proper air gap at the fill line from the evaporator to the technical water tank. This was corrected.
Recommendation: Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
Item No.: 08
Site: Potable Water-Starboard Bunker Station
Violation: One of the caps on the potable water filling line was not fastened by a chain. The cap had been removed from the line and placed face down on other piping in the station.
Recommendation: Ensure that the potable water filling line has a screw cap or plug fastened by a non-corroding chain to an adjacent bulkhead or surface in such a manner that the cap or plug does not touch the deck when hanging free. The connections for the hose attachments shall be unique and fit only potable water hoses.
Item No.: 19
Site: Galley-Coffee Station
Violation: The individual milk cartons were stored on a wet tray inside the reach-in refrigerator. This was corrected.
Recommendation: Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
Item No.: 21
Site: Galley-Hot Galley
Violation: The drip pan housings underneath the hot range were deep and less than two inches high, restricting access and making cleaning difficult.
Recommendation: Ensure the drip pan housings are accessible for cleaning.
Item No.: 21
Site: Galley-
Violation: The plastic piece attached to the hot water faucet handle for the soup kettle was damaged.
Recommendation: Replace the plastic piece.
Item No.: 21
Site: Food Service General-
Violation: There were open gaps and seams along the edges of equipment throughout the food preparation areas.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 21
Site: Buffet-Cafe Royale
Violation: There was condensate dripping from inside refrigeration unit #M-8 into a plastic cup on the deck.
Recommendation: Ensure the refrigeration unit is repaired.
Item No.: 22
Site: Galley-Warewash
Violation: The rinse curtain on the dishwash machine was heavily soiled.
Recommendation: Ensure that warewashing machines; the compartments of sinks, basins, or other receptacles used for washing and rinsing equipment, utensils, or raw foods, or laundering wiping cloths; and drainboards are cleaned: (1) Before use; (2) Throughout the day at a frequency necessary to prevent recontamination of equipment and utensils and to ensure that the equipment performs its intended function; and (3) If used, at least every 24 hours.
Item No.: 27
Site: Galley-Hot Galley
Violation: The drip pan housings underneath the hot range were soiled with grease and food debris.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Galley-Pastry Service Area
Violation: There was a gap around the inverted recessed nipple on the doors for the walk-in refrigerators.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Buffet-Crew, Staff and Officer's Messes
Violation: There was no coving along the deck/bulkhead juncture at the buffet stations.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 33
Site: Food Service General-
Violation: The deck tiles were cracked and the grout was missing throughout the food preparation areas. There were open seams in the deckheads and bulkheads throughout the food preparation areas.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Galley-Potwash
Violation: The inverted recessed nipples on the doors at the potwash and clean pot storage room were missing creating a void space.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Buffet-All Beverage Stations
Violation: There was peeling paint on the decks below the beverage stations.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Other-Pizzeria
Violation: There was a hole in the bulkhead to the right of the oven.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Other-Pizzeria
Violation: The deck/counter juncture was not coved.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 33
Site: Buffet-Cafe Royale
Violation: There was no coving along the deck/bulkhead juncture under refrigeration unit M-8.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 33
Site: Bar-Pool Bar
Violation: The stainless steel panel at the threshold was loose.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 34
Site: Buffet-Portside Buffet
Violation: There was a leak at the supply line for the ice machine.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 34
Site: Preparation Room-
Violation: There was a leak at the drain line of the handwash sink next to the mixer.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 37
Site: Buffet-Crew Mess
Violation: There was an excessive amount of condensate collecting on the deckhead above the coffee machine.
Recommendation: Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.