Item No.:
02
|
Site:
Medical-Gastrointestinal Log
|
Violation:
The gastrointestinal log did not include the crew position or job on the vessel.
|
Recommendation:
The gastrointestinal illness surveillance log entry for each passenger or crew member shall contain the following information:
(1) The first date of clinic visit or report to staff of illness; (2) The person's name, age and gender; (3) A designation as passenger or crew member; (4) Crew member position or job on the vessel, if applicable; (5) Cabin number; (6) Meal seating information; (7) Date and time of illness onset; (8) Illness symptoms, including the presence of the following selected signs and symptoms: numbers of episodes each of diarrhea and vomiting per day, bloody stools, fever, recorded temperature, abdominal cramps, headaches and muscle aches; (9) Notation on whether or not a stool specimen was requested and received; (10) Use of antidiarrheal medication; and (11) The presence of underlying medical conditions which may affect interpretation of acute gastrointestinal illness for example diabetic diarrhea, inflammatory bowel disease, gastrectomy or others.
|
|
Item No.:
03
|
Site:
Potable Water-Bunkering
|
Violation:
The bunkered water was not continuously halogenated above 2 ppm free residual halogen. The ship's chlorine pump was damaged and a new one was ordered. Per staff, the shore water tests were around 2 ppm free residual halogen at the start of bunkering, but there was no way to verify the residual after bunkering started.
|
Recommendation:
Ensure that potable water is continuously halogenated to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter.
|
|
Item No.:
06
|
Site:
Potable Water-Far Point Halogen Analyzer
|
Violation:
The automatic far point halogen analyzer had not worked for 3 months. Manual records were recorded every two hours during this time. The free residual halogen was 2.71 ppm when measured with the inspector's instrument. The manual records indicated that the residual was between 0.2 ppm and 5.0 ppm.
|
Recommendation:
Ensure that repairs on malfunctioning halogen analyzer-chart recorders are completed within 10 days of equipment failure.
|
|
Item No.:
08
|
Site:
Potable Water-Bunkering Hoses
|
Violation:
The potable water bunkering hoses were not labeled "POTABLE WATER ONLY" at both connection ends.
|
Recommendation:
Ensure that potable water hoses are labeled for use with the words "POTABLE WATER ONLY" in letters at least 13mm (0.5 inch) at each connecting end.
|
|
Item No.:
08
|
Site:
Potable Water-Bunkering Hoses
|
Violation:
The potable water bunkering hoses were not stored in a locker. When the inspector arrived at the ship, they were stored with ends unconnected next to portable gasoline containers.
|
Recommendation:
Ensure that hoses, fittings, water filters, buckets, and appurtenances used for connection with the bunkering of potable water are handled and stored in a sanitary manner.
|
|
Item No.:
08
|
Site:
Potable Water-Cabin 5309
|
Violation:
The potable water line supplying the flexible shower hose was not protected by a backflow prevention device. The hose could reach below the flood rim level of the shower, the toilet and the sink.
|
Recommendation:
Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
|
|
Item No.:
08
|
Site:
Potable Water-EVAC Toilets
|
Violation:
There were no backflow prevention devices on the potable water lines supplying the EVAC toilets in the crew and passenger cabins.
|
Recommendation:
Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
|
|
Item No.:
08
|
Site:
Potable Water-Bunkering
|
Violation:
Due to the analyzer not working a sample point for the bunkering water was not located at least 3 meters after the halogen injection point.
|
Recommendation:
Ensure that water samples for halogen testing are obtained from a sample cock located on the bunker or production water line at least 3 m (10 feet) after the halogen injection point and before the storage tank.
|
|
Item No.:
08
|
Site:
Potable Water-
|
Violation:
There were many backflow prevention devices installed on potable water lines that had a plugged vent. Per staff, these devices were leaking so the plumber plugged the vent. New devices have been ordered.
|
Recommendation:
Unplug the vents and install new devices.
|
|
Item No.:
08
|
Site:
Potable Water-Cross-Connection Control Program
|
Violation:
The cross-connection control program only listed the device type, the number of devices and the area they were in. It did not list the connections they protected.
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
|
|
Item No.:
08
|
Site:
Potable Water-Cross-Connection Control Program
|
Violation:
The cross-connection control program did not record the results for the annual test on reduced pressure zone assembly protecting the international shore connection.
|
Recommendation:
Ensure that backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, are inspected and tested with a test kit at least annually and that the test results showing the pressure differences on both sides of the valves are maintained for each device.
|
|
Item No.:
21
|
Site:
Galley-Steam Kettles
|
Violation:
The plastic conduits for the electrical wiring was secured with excessive sealant.
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
Item No.:
21
|
Site:
Galley-Hot Galley
|
Violation:
There were gaps around the grease chutes for the hot plates.
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
Item No.:
22
|
Site:
Galley-Potwash
|
Violation:
The 3-compartment sink was not large enough to allow immersion of the largest piece of equipment on the soiled rack.
|
Recommendation:
Ensure that sink compartments are large enough to accommodate immersion of the largest equipment and utensils. If equipment or utensils are too large for the warewashing sink, a warewashing machine or alternative equipment, such as a 3-bucket system, shall be used.
|
|
Item No.:
22
|
Site:
Galley-Dishwash
|
Violation:
The data plate on the conveyor dishwash machine did not state the conveyor speed.
|
Recommendation:
Ensure that warewashing machines are provided with an easily accessible and readable data plate affixed to the machine by the manufacturer that indicates the machine's design and operating specifications including the: (1) Temperatures required for washing, rinsing, and sanitizing; (2) Pressure required for the fresh water sanitizing rinse; and (3) Conveyor speed for conveyor machines or cycle time for stationary rack machines.
|
|
Item No.:
27
|
Site:
Galley-Hot Galley
|
Violation:
The gaps around the grease chutes and the chutes were soiled.
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
Item No.:
27
|
Site:
Galley-Hot Galley
|
Violation:
The underside of the flat grill was extremely soiled with old grease.
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
Item No.:
33
|
Site:
Provisions-Meat Freezer
|
Violation:
The metal cove piece had lifted from the deck, creating a gap that was hard to clean.
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
Item No.:
33
|
Site:
Other-Dining Room
|
Violation:
The deck under both waiter stations was soiled with food debris.
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
Item No.:
33
|
Site:
Buffet-
|
Violation:
The deck/counter junctures were not coved along the buffet.
|
Recommendation:
Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
|
|
Item No.:
40
|
Site:
Integrated Pest Management-Active Monitoring
|
Violation:
The night inspections in some of the areas occurred at 1200, 1330 and 1500.
|
Recommendation:
Ensure that the Integrated Pest Management Plan sets a schedule for periodic monitoring inspections including some at night.
|
|