Item No.:
06
|
|
Site:
Potable Water-Far Point Charts
|
|
Violation:
Most of the forward and aft far point halogen analyzer-chart recorder charts had a range of 0-10 ppm. Staff showed a work order which was placed on 12 January for charts with a 0-5 ppm range.
|
|
Recommendation:
Ensure the halogen analyzer-chart recorder charts have a range of 0.0 to 5.0 mg/L (ppm) and have a recording period of (and limited to) 24 hours.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Mineralizer Backwash Drain Line
|
|
Violation:
The air gaps for the mineralizer backwash drain lines were not included on the list of air gaps. This list was updated in January 2013. This was written on the last inspection report.
|
|
Recommendation:
Update the list of air gaps.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Distillate and Permeate Lines
|
|
Violation:
After the mineralizers, the distillate lines from the evaporators and the permeate lines from the reverse osmosis system were not striped to the production chlorine injection point in accordance with ISO 14726 standards (blue/gray/blue).
|
|
Recommendation:
Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Starboard Bunker Station
|
|
Violation:
The caps on the two lower potable water filling lines did not have their chains fastened to them.
|
|
Recommendation:
Ensure the potable water filling line has a screw cap fastened by a noncorroding cable or chain to an adjacent bulkhead or surface in such a manner that the cap cannot touch the deck when hanging free. Ensure the hose connections are unique and fit only the potable water hoses.
|
|
|
Item No.:
09
|
|
Site:
Recreational Water Facilities-Center Pool
|
|
Violation:
Manual tests of the center pool indicated 0.88 ppm and 0.72 ppm by the staff member and 0.12 ppm and 0.26 ppm by the inspector. The pool was open at the time of the inspection. The halogen analyzer indicated 2.22 - 2.26 ppm. Staff determined that chlorine was supplied to the analyzer, but an abundant amount of air was supplied to the pool.
|
|
Recommendation:
Maintain a free residual halogen in recirculated RWFs in the following ranges: (1) swimming pools, between 1.0 and 5.0 mg/L (ppm).
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Center Whirlpool
|
|
Violation:
Upon entrance to the center whirlpool machine room, the halogen analyzer and chlorine dosing pumps' visual alarms were flashing, indicating an error. The analyzer indicated a free chlorine residual of 0.10 ppm. Upon arriving at the whirlpool a short while later, the attendants were closing the whirlpool until this system error could be corrected.
|
|
Recommendation:
Maintain halogenation and pH control systems in good repair and operate them in accordance with the manufacturer's recommendations.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Whirlpool Safety Signs
|
|
Violation:
The safety signs did not include 'no children in diapers or who are not toilet trained' and did not caution elderly persons and children using the facilities.
|
|
Recommendation:
Provide safety signs for all RWFs, except for baby-only water facilities. Ensure the signs, at a minimum, include the following words: (2) no children in diapers or who are not toilet trained. In addition to the safety sign requirements in section 6.7.1.1.1, install a sign at each whirlpool spa and spa pool entrance listing precautions and risks associated with the use of these facilities. Include, at a minimum, cautions against use by the following: (3) pregnant women, elderly persons, and children.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Water Slide Safety Sign
|
|
Violation:
The safety sign for the water slide could not be located.
|
|
Recommendation:
Provide safety signs for all RWFs, except for baby-only water facilities. Ensure the signs, at a minimum, include the following words: (1) do not use these facilities if you are experiencing diarrhea, vomiting, or fever; (2) no children in diapers or who are not toilet trained; (3) shower before entering the facility; and (4) bather load #.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Beverage Stations
|
|
Violation:
The time control plans for the beverage stations did not identify the refrigeration units for the milk kept on time control. These refrigerators were not labeled 'time control'.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such).
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such).
|
|
|
Item No.:
16
|
|
Site:
Buffet-Crew Mess
|
|
Violation:
Approximately 30 individually packaged yogurt containers were holding at 45 - 55F in the worker side undercounter refrigerator next to the self-service cold well. Also, there were approximately 30 individually wrapped packages of butter which were holding at 47F. The refrigerator was on temperature control. Staff immediately discarded these products.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, maintain potentially hazardous foods at 57C (135F) or above, except that roasts may be held at a temperature of 54C (130F); or 5C (41F) or less.
|
|
|
Item No.:
19
|
|
Site:
Pantry-Medical Pantry
|
|
Violation:
A box of bottled water was stored on the soiled counter of the dishwash machine.
|
|
Recommendation:
Protect food from contamination by storing the food: (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
20
|
|
Site:
Galley-Room Service - Deck 6
|
|
Violation:
The counter-mounted espresso machine had slotted fasteners at the coffee/water juncture.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Bar-Club Restaurant
|
|
Violation:
The counter-mounted espresso machine had slotted fasteners at the coffee/water juncture.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
21
|
|
Site:
Bar-Club Restaurant Bar
|
|
Violation:
The electrical cords to the ice/water dispenser and espresso machine were draped on the counter, making cleaning difficult.
|
|
Recommendation:
Remove the electrical cords from the counter. Remove the electrical cords from the counter.
|
|
|
Item No.:
22
|
|
Site:
Galley-Room Service - Deck 6
|
|
Violation:
The speed for the rack-type dishwash machine was in racks per hour rather than a minimum transit time.
|
|
Recommendation:
Ensure a warewashing machine is provided with an easily accessible and readable data plate affixed to or posted adjacent to the machine that indicates the machine?s design and operating specifications including the: (3) conveyor speed in feet per minute or minimum transit time for belt conveyor machines, minimum transit time for rack conveyor machines, and wash and final sanitizing rinse times as specified by the manufacturer for stationary rack machines. Ensure a warewashing machine is provided with an easily accessible and readable data plate affixed to or posted adjacent to the machine that indicates the machine's design and operating specifications including the: (3) conveyor speed in feet per minute or minimum transit time for belt conveyor machines, minimum transit time for rack conveyor machines, and wash and final sanitizing rinse times as specified by the manufacturer for stationary rack machines.
|
|
|
Item No.:
24
|
|
Site:
Buffet-Port Midship Beverage Station
|
|
Violation:
A bucket of sanitizing solution was measured at 0 ppm chlorine.
|
|
Recommendation:
Ensure sanitizing solutions are used with the following concentrations: (1) A chlorine solution with a concentration between 50 mg/L (ppm) and 200 mg/L (ppm). Ensure sanitizing solutions are used with the following concentrations: (1) A chlorine solution with a concentration between 50 mg/L (ppm) and 200 mg/L (ppm).
|
|
|
Item No.:
26
|
|
Site:
Bar-Club Restaurant Bar
|
|
Violation:
There was mold growth in the food splash area on the back dispensing lip of the counter-mounted ice/water dispenser.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Galley-Ice Machines
|
|
Violation:
There was a fine black powder along the length of the white plastic water return trays immediately below both ice cubers of the starboard side ice machine. The same powder was observed in the left water return tray of the port side ice machine.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
33
|
|
Site:
Galley-Sauce Station
|
|
Violation:
There were broken deck tiles and missing deck tile grout inside the walk-in refrigerator and at the entrance to the walk-in freezer.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Galley-Entrance Corridors
|
|
Violation:
There was no bulkhead/deck coving at the entrance corridors to the port and starboard pantries which service the aft grills. Food items and soiled dishes were transported through these corridors.
|
|
Recommendation:
Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel). Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
|
|
|
Item No.:
33
|
|
Site:
Galley-Hot Galley
|
|
Violation:
There was missing and pitted deck tile grout throughout this location.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
34
|
|
Site:
Galley-Sauce Station
|
|
Violation:
Water was leaking from a deckhead seam and pooling on the deck between the combination ovens and tilting pans. According to staff, a pipe in the deckhead was leaking, The leak was corrected.
|
|
Recommendation:
Ensure the plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
43
|
|
Site:
Ventilation-AC Station 8.6
|
|
Violation:
There was a heavy accumulation of dust and dead insects, such as moths and beetles, on the bottom of the air filter compartment of unit #6.083. Also, the lowest filter was in standing water and was heavily soiled with the dust and dead insects.
|
|
Recommendation:
Keep air handling units clean. Keep air handling units clean.
|
|