Item No.:
06
|
|
Site:
Potable Water-FAR POINT ANALYZER CHARTS
|
|
Violation:
SEVERAL OF THE FAR POINT POTABLE WATER ANALYZER CHARTS HAD RECORDINGS OF GREATER THAN 24 HOURS WITHOUT ANY COMMENTS EXPLAINING WHY. SEVERAL OF THE CHARTS RAN FOR APPROXIMATELY 28 HOURS BEFORE BEING CHANGED.
|
|
Recommendation:
Ensure that halogen analyzer-chart recorder charts are changed, initialed, and dated daily and contain notations of any unusual water events in the potable water system.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-BUNKERING
|
|
Violation:
THERE WAS NO RECENT DOCUMENTATION OF MICROBIOLOGICAL TESTING OF THE BUNKERED WATER.
|
|
Recommendation:
Where available, ensure that the vessel has a copy of the most recent microbiologic report from each port before bunkering potable water to verify that the water meets potable standards, or perform a microbiological test onboard.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-HYDROTHERAPY POOL MECHANICAL ROOM
|
|
Violation:
A DUAL CHECK ASSEMBLY WAS INSTALLED ON THE POTABLE WATER SUPPLY LINE TO THE COMPENSATION TANK.
|
|
Recommendation:
Install either an air-gap between the potable water supply line and the compensation tank or install an approved continuous pressure type backflow prevention device with an intermediate atmospheric vent.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-SPA AREA STEAM GENERATOR ROOM
|
|
Violation:
THE INTERMEDIATE ATMOSPHERIC VENT ON THE POTABLE WATER SUPPLY LINE WAS POINTING UP WHICH WOULD NOT ALLOW THE WATER TO DRAIN FROM THE VENT.
THIS WAS CORRECTED DURING THE INSPECTION.
|
|
Recommendation:
Reposition the backflow prevention device so it points down to allow any collected water to drain.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-BEAUTY SALON
|
|
Violation:
NON-CONTINUOUS PRESSURE TYPE BACKFLOW PREVENTERS WERE INSTALLED ON THE HAIR RINSE SINK NEAREST TO DOOR, AND ON BOTH FOOT BATHS THAT WERE INSTALLED DURING THE RECENT DRYDOCK.
|
|
Recommendation:
Install continuous pressure type backflow protection devices.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-HOSPITAL
|
|
Violation:
THE BACKFLOW PREVENTION DEVICE ON THE FLEXIBLE SHOWER HOSE IN WARDROOM #2 WAS MISSING.
|
|
Recommendation:
Reinstall the backflow prevention device.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-HOSPITAL
|
|
Violation:
THE BACKFLOW PREVENTER FOR THE DENTAL EQUIPMENT COULD NOT BE LOCATED.
|
|
Recommendation:
Ensure that the potable water supply to the dental equipment is equipped with an appropriate backflow prevention device.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-MAIN AND CREW GALLEY
|
|
Violation:
THE CONBRACO DCV BACKFLOW PREVENTION DEVICES UTILIZED ON THE POTABLE WATER SUPPLY LINES FOR THE AUTOMATIC HOOD CLEANING SYSTEMS WERE NOT VENTED.
|
|
Recommendation:
Install vented backflow prevention devices on the potable water supply lines to the automatic hood cleaning systems.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-MEDICAL X-RAY DEVELOPER
|
|
Violation:
THE BACKFLOW PREVENTION DEVICE COULD NOT BE LOCATED ON THE DETACHABLE HOSE ON THE UTILITY SINK LOCATED BESIDE THE CHEMICAL X-RAY DEVELOPER.
|
|
Recommendation:
Provide an appropriate backflow prevention device on the potable water supply line to the spray hose of the utility sink.
|
|
|
Item No.:
15
|
|
Site:
Galley-BREAKFAST PANTRY
|
|
Violation:
TWO DENTED CANS OF JUICE WERE NOTED ON THE STORAGE SHELF IN THE BREAKFAST PANTRY.
|
|
Recommendation:
Ensure that food packages are in good condition and protect the integrity of the contents so that the food is not exposed to adulteration or potential contaminants. Canned goods with dents on end or side seams may not be used.
|
|
|
Item No.:
19
|
|
Site:
Buffet-NEPTUNE LOUNGE
|
|
Violation:
THERE WAS NO SNEEZE GUARD OR OTHER FOOD PROTECTION PROVIDE FOR THE DANISHES IN THE LOUNGE.
|
|
Recommendation:
Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
21
|
|
Site:
Bar-OCEAN
|
|
Violation:
THE LAMINATE SIDE-PANEL OF THE WAITER STATION HAD BEEN CHIPPED AND WAS NO LONGER EASILY CLEANABLE.
|
|
Recommendation:
Repair the damaged waiter station.
|
|
|
Item No.:
22
|
|
Site:
Galley-MAIN GALLEY DISHWASH
|
|
Violation:
THE PRESSURE GAUGES ON BOTH MACHINES DID NOT APPEAR TO OPERATE CORRECTLY. MACHINE # 1 PRESSURE GAUGE READ 16 AND 17 PSI AND MACHINE # 2 PRESSURE READ LESS THAN 15 PSI.
|
|
Recommendation:
Ensure that warewashing machines and their auxiliary components: (1) Are operated in accordance with the machine's data plate and other manufacturer's instructions. (2) A warewashing machine's conveyor speed or automatic cycle times are maintained accurately timed in accordance with manufacturer's specifications.
|
|
|
Item No.:
22
|
|
Site:
Galley-MAIN GALLEY & PINNACLE GRILLE DISHWASH
|
|
Violation:
THE DATA PLATES DID NOT LIST THE CONVEYOR SPEED ON THE ELECTROLUX DISHWASH MACHINES # 1 AND 2.
THE DATA PLATE WAS MISSING ON THE DISHWASH MACHINE IN THE PINNACLE GRILLE GALLEY.
|
|
Recommendation:
Ensure that warewashing machines are provided with an easily accessible and readable data plate affixed to the machine by the manufacturer that indicates the machine's design and operating specifications including the: (1) Temperatures required for washing, rinsing, and sanitizing; (2) Pressure required for the fresh water sanitizing rinse; and (3) Conveyor speed for conveyor machines or cycle time for stationary rack machines.
|
|
|
Item No.:
24
|
|
Site:
Galley-MAIN GALLEY DISHWASH
|
|
Violation:
DURING ACTIVE USE DISHWASH MACHINE # 1 FINAL RINSE TEMPERATURE WERE RECORDED WITH A MAXIMUM REGISTERING THERMOMETER AT 145, 120, 140, 120 F. THE PRE-WASH TANK TEMPERATURE WAS RECORDED AT 120 F, WASH 160F AND RECIRCULATED RINSE 170F.
DURING ACTIVE USE, DISHWASH MACHINE # 2 FINAL RINSE TEMPERATURE READ 120, 140 F.
THE EQUIPMENT WAS PLACED OUT OF ORDER AND THE MACHINES WERE REPAIRED AND WAS OPERATING CORRECTLY AT THE END OF THE INSPECTION.
|
|
Recommendation:
Ensure the final rinse temperatures of the dishwashing machines are at least 160 degrees F at the dish surface.
|
|