Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Carnival Sunshine Cruise Line: Carnival Cruise Lines, Inc. Inspection Date: 04/18/2024 Inspection Score: 94
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 05
Site: Potable Water-Distant Point
Violation: The halogen analyzer was not within 0.2ppm when compared with consecutive measurements by the crew and inspector's test kits. At the time of measurements, the analyzer read 1.61ppm and tests taken by the inspector and crew averaged (5 measurements) 1.97ppm. The analyzer was recalibrated.
Recommendation: Ensure the free residual halogen measured by the halogen analyzer is within 0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
Item No.: 08
Site: Potable Water-Tank Maintenance
Violation: There was no written documentation of approval from the certification organization (independent of the coating manufacturer) that the paint used for tank coatings was approved for this use. Staff stated they had it onboard but it was not readily accessible.
Recommendation: Ensure the interior coatings on potable water tanks are approved for potable water contact by a certification organization. Follow all manufacturers? recommendations for application, drying, and curing. For the tank coatings used, maintain the following onboard: (1) written documentation of approval from the certification organization (independent of the coating manufacturer); (2) manufacturers? recommendations for application, drying, and curing; and (3) written documentation that the manufacturers? recommendations have been followed for application, drying, and curing.
Item No.: 08
Site: Potable Water-Backflow Log
Violation: The testable backflow log indicated test results for newly installed backflow prevention devices did not occur when they were installed. Specifically, the shoreside fire and sprinkler backflow assemblies were replaced on 4 February, however, the test dates for these devices were not until 18 February. Additionally, a new backflow prevention device was installed on the overboard discharge line for Osmosis #1, however, the type of device was still showing the old make and model on the log.
Recommendation: Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections. Inspect and test backflow prevention devices requiring testing (e.g., reduced pressure backflow prevention devices and pressure vacuum breakers) with a test kit after installation and at least annually. Maintain test results showing the pressure differences on both sides of the valves.
Item No.: 08
Site: Potable Water-Striping
Violation: The overboard line for the port evaporator was striped blue/gray/blue indicating water going to the potable water system. Additionally, permeate water lines from Osmosis #1 were not clearly striped blue/gray/blue, and the produced water lines from the mineralizer were striped blue and not blue/gray/ blue. These were corrected.
Recommendation: Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers. Do not stripe or paint potable water lines after reduced pressure assemblies as potable water. Identify all refrigerant brine lines and nonpotable chilled water lines in all food areas, such as on ice machines, ice cream machines, etc., with either ISO 14726 (blue/white/blue) or by another uniquely identifiable method to prevent cross-connections.
Item No.: 08
Site: Potable Water-Aft Port and Stbd Bunker Stations
Violation: Technical water connections at the stations were striped blue/gray/blue.
Recommendation: Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations.
Item No.: 09
Site: Recreational Water Facilities-Halogen levels - Serenity Pool
Violation: Chlorine residual tests at the open Serenity pool (IRWF) were below the required 2.00ppm. Repeated tests by the crew and inspector's test kits measured 1.65, 1.91, and 1.43. Passengers were instructed to vacate the pool and the pool was immediately closed. Inspection in the pump room found the halogen injection pump was malfunctioning and the halogen level had dropped below 2ppm from ~1015 until we tested at ~1045.
Recommendation: Maintain a free residual halogen in recirculated RWFs in the following ranges: (1) swimming pools, between 1.0 and 5.0 mg/L (ppm); (2) children's pools, between1.0 and 5.0 mg/L (ppm); (3) wading pools, between 1.0 and 5.0 mg/L (ppm); (4) interactive RWFs (activity pools), between 2.0 and 5.0 mg/L (ppm); (5) baby-only water facilities, between 3.0 and 10.0 mg/L (ppm) free chlorine or between 4.0 and 10.0 mg/L (ppm) bromine; and (6) whirlpool spas and spa pools, between 3.0 and 10.0 mg/L (ppm) free chlorine or between 4.0 and 10.0 mg/L (ppm) bromine. If facilities meet the definition of more than one type of RWF, apply the more protective halogen residual. If a facility is modified, apply the most protective halogen residual.
Item No.: 10
Site: Recreational Water Facilities-Skimming Serenity Pool
Violation: Only approximately 30% of the surface of the pool was effectively skimming.
Recommendation: For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters.
Item No.: 10
Site: Recreational Water Facilities-Port Whirlpool Turnover Rate
Violation: Using the system's flow meter, the turnover rate was calculated at 40 minutes.
Recommendation: . Design recirculation systems and equipment, including chemical control equipment, UV disinfection systems, filter, and pumps to maintain adequate water chemistry control while operating at the following minimum turnover rates: (5) whirlpool spa: 0.5 hours; Flow rates from flow meters must be used to calculate turnover rates.
Item No.: 10
Site: Recreational Water Facilities-Halogen Levels - Serenity Pool
Violation: Chlorine residual tests at the open Serenity pool (IRWF) were below the required 2.00ppm. Repeated tests by the crew and inspector's test kits measured 1.65, 1.91, and 1.43. Passengers were instructed to vacate the pool and the pool was immediately closed. Inspection in the pump room found the halogen injection pump was malfunctioning and the halogen level had dropped below 2ppm from ~1015 until we tested at ~1045.
Recommendation: Maintain halogenation and pH control systems in good repair and operate them in accordance with the manufacturer?s recommendations.
Item No.: 10
Site: Recreational Water Facilities-Halogen Levels - Serenity Pool
Violation: Chlorine residual tests at the open Serenity pool (IRWF) were below the required 2.00ppm. Repeated tests by the crew and inspector's test kits measured 1.65, 1.91, and 1.43. Passengers were instructed to vacate the pool and the pool was immediately closed. Inspection in the pump room found the halogen injection pump was malfunctioning and the halogen level had dropped below 2ppm from ~1015 until we tested at ~1045.
Recommendation: Maintain halogenation and pH control systems in good repair and operate them in accordance with the manufacturer?s recommendations. Maintain halogenation and pH control systems in good repair and operate them in accordance with the manufacturer?s recommendations.
Item No.: 10
Site: Recreational Water Facilities-Halogen Levels - Serenity Pool
Violation: Chlorine residual tests at the open Serenity pool (IRWF) were below the required 2.00ppm. Repeated tests by the crew and inspector's test kits measured 1.65, 1.91, and 1.43. Passengers were instructed to vacate the pool and the pool was immediately closed. Inspection in the pump room found the halogen injection pump was malfunctioning and the halogen level had dropped below 2ppm from ~1015 until we tested at ~1045.
Recommendation: Maintain halogenation and pH control systems in good repair and operate them in accordance with the manufacturer?s recommendations.
Item No.: 12
Site: Galley-Deck 9 Blue Iguana
Violation: A crew member cooking raw eggs touched the inside of a cup containing raw egg with his thumb and subsequently proceeded to handle a ready to eat tortilla with the same gloved hand. It was unclear if the crew member's thumb came into contact with the raw egg prior to touching the tortilla. The tortilla was discarded and retraining on proper glove usage and hand washing took place.
Recommendation: Ensure: (1) Single-use gloves are used for only one task of any hand contact with ready-to-eat food, used for no other purpose, and discarded when damaged or soiled or when interruptions occur in the operation.
Item No.: 19
Site: Buffet-Deck 0 Team Dining Room 2
Violation: Bread rolls out for crew self-service were protected by a plastic box without a self-closing hinged lid or sneeze guard.
Recommendation: Protect food on display from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; self-closing hinged lids; or other effective means. Install side protection for sneeze guards if the distance between exposed food and where consumers are expected to stand is less than 1 meter (40 inches).
Item No.: 20
Site: Food Service General-Soda Guns - Slotted Fasteners
Violation: The soda dispensing guns had slotted fasteners on the underside of the nozzle in the food splash zone.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 20
Site: Galley-Deck 3 Steakhouse
Violation: Walk-in refrigerator #51 and undercounter refrigerator #17 were not maintaining temperatures below 41F. The walk-in refrigerator was 70F and the undercounter refrigerator was 61.9F. Pork belly stored in the undercounter refrigerator was within temperature; however, staff moved the item to a refrigerator that was maintaining the proper temperature. No other PHFs were stored in these units. Staff stated the refrigerators were on a defrosting cycle.
Recommendation: Ensure equipment for cooling and heating food, and holding cold and hot food, is sufficient in number and capacity to maintain potentially hazardous food temperatures.
Item No.: 21
Site: Galley-Deck 3 Forward Portside Ice Machines
Violation: The side, stainless-steel profile strip was in disrepair on the undercounter cabinet between the ice machines.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 21
Site: Food Service General-Bulk Coffee Machines
Violation: Sealant around the front housing of the espresso coffee machines was in disrepair and created a difficult to clean surface that was soiled with more than a day's accumulation of coffee residue.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 21
Site: Buffet-Deck 9 Lido Hot Food Islands
Violation: Sealant around countertop hot plates was in disrepair and was soiled at the port and starboard hot food islands. Staff removed and replaced the sealant.
Recommendation: Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 21
Site: Buffet-Deck 0 Team Dining Room 2
Violation: The soda vending machine had inadequate spacing to the bulkhead and the deck below and behind was soiled with more than a day's accumulation of dust.
Recommendation: Ensure deck-mounted equipment that is not easily movable is sealed to the deck or elevated on legs that provide at least a 150 mm (6-inch) clearance between the deck and the equipment.
Item No.: 21
Site: Provisions-Wood Pallets
Violation: Approximately 8 wood pallets were stacked with bottled water in the provisioning corridor. Staff stated these were received on 13 April and yet to be transferred from the wood pallets. This was corrected.
Recommendation: Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 21
Site: Buffet-Deck 9 Forward Portside Ice Cream Station
Violation: The bottom profile strip on the far-right door was in disrepair and peeling away from the door frame.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 22
Site: Galley-Deck 3 Warewash
Violation: The aft flight-type warewash machine was in disrepair since 17 April 2024. Staff were diverting soiled ware to the forward flight-type warewash machine.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 26
Site: Buffet-Deck 0 Team Dining Room 1
Violation: The water and ice dispensing machine was soiled around the black fastener below the ice dispensing nozzle.
Recommendation: Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 27
Site: Food Service General-Bulk Coffee Machines
Violation: Sealant around the front housing of the espresso coffee machines was in disrepair and created a difficult to clean surface that was soiled with more than a day's accumulation of coffee residue.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Buffet-Deck 9 Lido Hot Food Islands
Violation: Sealant around countertop hot plates was in disrepair and was soiled at the port and starboard hot food islands. Staff removed and replaced the sealant.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Buffet-Deck 9 Lido Continental Breakfast
Violation: Approximately 30 display containers of macaroons along the bulkhead behind the continental breakfast line were soiled with more than a day's accumulation of dust.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Galley-Deck 9 JiJi
Violation: The top stacked combination oven was dripping condensate onto the top surface of the bottom combination oven. The food in the lower combination oven was not impacted.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 30
Site: Buffet-Deck 9 Forward Portside Ice Cream Station
Violation: The passenger, automatic handwashing station was out of soap and the water ran for only five seconds when the sensor was engaged.
Recommendation: Ensure water continuously runs from the faucet without having to re-engage the sensor. Provide a handwashing station with: a handwash sink with hot and cold water, soap dispenser, and single-use paper towel dispenser. Provide waste receptacles in close proximity to the handwash sink and size to accommodate the quantity of paper towel waste generated. The handwashing station may be decorative. Ensure the handwashing station is nonabsorbent, durable, and easy cleanable. Ensure water continuously runs from the faucet without having to re-engage the sensor.
Item No.: 33
Site: Buffet-Deck 9 Lido Portside Beverage Station
Violation: A deckhead panel behind the coffee machine was hanging down. Staff corrected immediately.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-Deck 9 Deli
Violation: The sous chef's office door frame was excessively rusted and soiled towards the bottom of the door in the show galley.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair. Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 33
Site: Galley-Deck 9 JiJi
Violation: Excessive condensate collected on the deckhead above the soup kettles. Staff explained this was due to a hood cleaning cycle resulting in the ventilation damper closing. This occurs four times a day for 30 minutes each cycle. At the time of the observation, the soup kettles were closed. Staff stated they wipe the deckhead and minimize operations during these cycles.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 33
Site: Galley-Deck 9 Cucina Del Capitano
Violation: A deck tile was cracked near the pizza oven in the show galley.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-Deck 3 Hot Line
Violation: The deck tile grout was recessed throughout the center port hot food line.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-Deck 3 Portside Cleaning Material Locker
Violation: The locking mechanism was missing from the cleaning material locker room door which created an open penetration and difficult to clean surface.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 33
Site: Galley-Deck 3 Forward Warewash
Violation: The water supply line for the flight-type warewash machine was in disrepair resulting in water leaking and pooling on the deck below.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 33
Site: Buffet-Deck 0 Team Dining Room 2
Violation: The soda vending machine had inadequate spacing to the bulkhead and the deck below and behind was soiled with more than a day's accumulation of dust.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 34
Site: Galley-Deck 3 Forward Warewash
Violation: The water supply line for the flight-type warewash machine was in disrepair resulting in water leaking and pooling on the deck below.
Recommendation: Ensure a plumbing system in a food area is maintained in good repair.
Item No.: 39
Site: Provisions-Deck 0 Dry Store
Violation: Two small flies were in the provisions hallway outside the dry stores.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Galley-Deck 9 Cucina Del Capitano
Violation: One house fly was flying throughout the galley.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 44
Site: Recreational Water Facilities-Halogen Levels - Serenity Pool
Violation: Chlorine residual tests at the open Serenity pool (IRWF) were below the required 2.00ppm. Repeated tests by the crew and inspector's test kits measured 1.65, 1.91, and 1.43. Passengers were instructed to vacate the pool and the pool was immediately closed. Inspection in the pump room found the halogen injection pump was malfunctioning and the halogen level had dropped below 2ppm from ~1015 until we tested at ~1045. Staff reported the low level halogen alarm sounded when the levels dropped below the set point and a pool engineer was sent to correct the issue. The engineer, however, began troubleshooting the issue rather than immediately closing the pool once the residual values fell below 2.0ppm.
Recommendation: Ensure the supervisor or person in charge of recreational water operations on the vessel demonstrates to VSP?during inspections and on request ? knowledge of recreational water operations, is able to demonstrate this knowledge by compliance with Section 6 of the VSP 2018 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 6 of the VSP 2018 Operations Manual as it relates to their assigned duties. When halogen or pH parameters are outside of the acceptable ranges the facility must be closed before troubleshooting the issue.
Item No.: 44
Site: Recreational Water Facilities-Halogen Levels - Serenity Pool
Violation: Chlorine residual tests at the open Serenity pool (IRWF) were below the required 2.00ppm. Repeated tests by the crew and inspector's test kits measured 1.65, 1.91, and 1.43. Passengers were instructed to vacate the pool and the pool was immediately closed. Inspection in the pump room found the halogen injection pump was malfunctioning and the halogen level had dropped below 2ppm from ~1015 until we tested at ~1045. Staff stated the alarm sounded when the halogen dropped below the set point and a pool engineer was notified to resolve the issue. The pool engineer, however, did not immediately close the pool when it fell below 2.0ppm and allowed the pool to remain open while troubleshooting the issue.
Recommendation: Ensure the supervisor or person in charge of recreational water operations on the vessel demonstrates to VSP?during inspections and on request ? knowledge of recreational water operations, is able to demonstrate this knowledge by compliance with Section 6 of the VSP 2018 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 6 of the VSP 2018 Operations Manual as it relates to their assigned duties.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program