Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Plan
|
|
Violation:
The backflow preventers installed the outer deck cleaning connection points and engine room areas were either Watts S8 or ORAS, both of which are designed only for non-continuous pressure. One outer deck hose was coiled next to a connecting point and another was attached to the deck tap and both had spray nozzles.
|
|
Recommendation:
Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer. Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Plan
|
|
Violation:
There were a number of backflow preventer models listed which did not match the backflow preventers installed in the beauty salon hair sinks, the deckwashing taps, and the cabin showers.
|
|
Recommendation:
Review the model backflow preventer used in the various areas and correct the overall cross-connection listing.
|
|
|
Item No.:
10
|
|
Site:
DO NOT USE (whirlpool/spa)-Deck 10 Whirlpool Spas - Port and Starboard
|
|
Violation:
The starboard side whirlpool spa main drain cover was broken and had one screw missing. Both the port and starboard side whirlpool spa drain covers had no markings indicating covers meet ASME/ANSI A112.19.8M or an equivalent standard.
|
|
Recommendation:
Ensure that anti-entrapment drain covers or other drains that prevent entrapment hazards as specified in U.S. Consumer Product Safety Publication 363-009801 (dual drains/channel drains) are provided on swimming pools and whirlpool spas. Ensure that drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in ASME/ANSI A112.19.8M or an equivalent standard.
|
|
|
Item No.:
11
|
|
Site:
Medical-Recordkeeping
|
|
Violation:
In reviewing the documentation for a crew gastrointestinal illness case on a recent cruise, there was complete information provided for the crew member's asymptomatic cabin mate, but nothing recorded about an immediate contact.
|
|
Recommendation:
Ensure that there is some documentation of whether or not the ill crew member has an immediate contact, and provide the necessary follow-up with them. Ensure that medical staff conduct verbal interviews with asymptomatic cabin mates or immediate contacts to confirm their condition, advise them of the hygiene and handwashing facts, and instruct them to report immediately to medical if they develop illness symptoms. Ensure that medical staff conduct daily verbal interviews with asymptomatic crew until 48 hours after onset of the ill crew members symptoms.
|
|
|
Item No.:
16
|
|
Site:
Galley-Cold Galley
|
|
Violation:
There were prepared lunch foods in the reach-in refrigeration unit at 1000. The refrigeration unit was labeled as being under time control management with a start time of 1100 for the lunch service and the time as a public health control plan indicated the unit was on time management from 1100 - 1400. The items were moved to the walk-in refrigerator.
|
|
Recommendation:
Maintain prepared lunch items under temperature control in a refrigeration unit that is utilized for temperature control. Alternatively, modify the time as a public health control plan to indicate that the food preparation time is included in the 4-hour window and that the prepared food items are held in the refrigeration unit(s) labeled for time control.
|
|
|
Item No.:
16
|
|
Site:
Galley-Cold Galley
|
|
Violation:
A tray of sliced melons in the undercounter refrigerator had an internal temperature of 45°F. The temperature measurement was taken at 1000 and, per staff, the tray of melons was prepared at 0800. The tray was immediately placed in the blast chiller.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
16
|
|
Site:
Galley-Walk-in Refrigerator
|
|
Violation:
A 1/2 rib of roast beef had an internal temperature of 50°F. The 7-day discard label indicated that the beef was prepared and placed in the unit on 3/12/2008. The beef portion was immediately discarded.
|
|
Recommendation:
Ensure that cooked potentially hazardous food is cooled: (1) Within 2 hours, from 60°C (140°F) to 21°C (70°F); and (2) Within 4 hours, from 21°C (70°F) to 5°C (41°F) or less. Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
17
|
|
Site:
Galley-Cooling Logs
|
|
Violation:
The cooling logs did not list the times for all the foods that were placed in the blast chiller.
|
|
Recommendation:
Ensure that logs documenting cooked, potentially hazardous food cooling temperatures and times from the starting points designated in 7.3.5.2.1 thru the control points at 2 and 6 hours are maintained onboard the vessel for a period of 30 days form the date the food was placed in the cooling process.
Ensure that logs documenting cooling of potentially hazardous foods prepared from ingredients at ambient temperatures, with the start time to the time when 5°C (41 °F) is reached are also maintained for a period of 30 days, beginning with the day of preparation.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Baine-Marie
|
|
Violation:
Condensate was forming on the cover and sneeze guard at the bain-marie. Heavy steam was emanating from the bain-marie prior to insertion of the food pans. No liquid was observed dripping into the foods.
|
|
Recommendation:
Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
19
|
|
Site:
Preparation Room-Walk-in Refrigerator
|
|
Violation:
Ground beef was stored above pork cuts. This was corrected immediately.
|
|
Recommendation:
Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
21
|
|
Site:
Food Service General-LaVeranda and Dining Room
|
|
Violation:
There were gaps along the trim/door panel interface of each waiter station, making cleaning difficult.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
21
|
|
Site:
Buffet-LaVeranda
|
|
Violation:
The wood trim corners of the fruit and juice islands were damaged, making cleaning difficult.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions.
|
|
|
Item No.:
21
|
|
Site:
Galley-LaVeranda
|
|
Violation:
The lower bin access door of the ice crusher was badly damaged, making cleaning difficult.
|
|
Recommendation:
Ensure that non-food contact equipment is maintained in good repair and proper adjustment including: (1) Equipment maintained in a state of repair and condition that meets the materials, design, construction, and operation specifications of these guidelines. (2) Equipment components such as doors, seals, hinges, fasteners, and kick plates are kept intact, tight, and adjusted in accordance with manufacturer's specifications.
|
|
|
Item No.:
21
|
|
Site:
Galley-LaVeranda
|
|
Violation:
The upper interior surface of the cuber/water bath compartment had peeling plastic film, making cleaning difficult.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
26
|
|
Site:
Galley-Starboard Dishwash
|
|
Violation:
A few plates were soiled and stored as clean.
|
|
Recommendation:
Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
27
|
|
Site:
Food Service General-LaVeranda and Dining Room
|
|
Violation:
The gaps along the trim/door panel interface of each waiter station was soiled.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
28
|
|
Site:
Preparation Room-Pot-Wash
|
|
Violation:
Condensate from the potwash exhaust hood was dripping onto the clean storage rack and onto the clean items in the rack.
|
|
Recommendation:
Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
|
|
|
Item No.:
28
|
|
Site:
Bar-Stars
|
|
Violation:
The paper towel dispenser was approximately 8 feet from the handwash station, requiring staff to pass over the service counter with wet hands, potentially contaminating the service counter surface or equipment/food items stored on the counter.
|
|
Recommendation:
Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
|
|
|
Item No.:
30
|
|
Site:
Galley-LaVeranda
|
|
Violation:
There was no waste receptacle at the soiled drop-off landing handwash station.
|
|
Recommendation:
Ensure that a handwashing facility includes a sink, soap dispenser, single-use towels dispenser, and waste receptacle.
|
|
|
Item No.:
33
|
|
Site:
Galley-LaVeranda
|
|
Violation:
There was recessed tile grout at the soiled drop-off landing.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Galley-Pool Grill
|
|
Violation:
The deck below undercounter refrigeration unit #170 was soiled. Per staff this area was cleaned the night before.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Port Service Line
|
|
Violation:
Refrigeration unit 330 technical space deck was pitted and rough, making cleaning difficult. The deck was soiled.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-
|
|
Violation:
Cables were draped on the floor of several technical spaces in the galleys.
|
|
Recommendation:
Ensure that exposed utility service lines and pipes, including lines for fire detection and protection systems, are installed so they do not obstruct or prevent cleaning.
|
|
|
Item No.:
33
|
|
Site:
Galley-Clean Stoarge Racks
|
|
Violation:
The deck under the clean storage racks was soiled.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Preparation Room-
|
|
Violation:
There was recessed grout around the preparation table near the potwash clean storage.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
36
|
|
Site:
Bar-Observation
|
|
Violation:
The lighting intensity did not appear to be 220 Lux.
|
|
Recommendation:
Ensure that the light intensity is at least 220 Lux (20 foot candles) in bars and at dining room waiter stations during periods of cleaning.
|
|
|
Item No.:
37
|
|
Site:
Preparation Room-Pot-Wash
|
|
Violation:
Excessive steam was emanating from the potwash and condensation was forming on the exhaust hood edge. Condensate was dripping onto the clean storage rack and onto the clean items in the rack.
|
|
Recommendation:
Ensure that exhaust ventilation hood systems in food preparation and warewashing areas including components such as hoods, fans, guards, and ducting are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
37
|
|
Site:
Galley-Starboard Dishwash
|
|
Violation:
Excessive steam was emanating from the clean end. Condensation was forming on the deckhead and bulkhead.
|
|
Recommendation:
Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
37
|
|
Site:
Galley-Scullery
|
|
Violation:
Excessive steam was emanating from the clean end. Condensation was forming on the deckhead and bulkhead.
|
|
Recommendation:
Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Integrated Pest Management (IPM) - Rat Guards
|
|
Violation:
The rodent guards on the ship's mooring lines were in poor condition and did not appear to be effective in blocking rodent access to the ship.
|
|
Recommendation:
Ensure that entry points where pests may enter the food areas are protected.
|
|