Item No.:
10
|
|
Site:
DO NOT USE (whirlpool/spa)-
|
|
Violation:
The contact time for super bromination was not recorded.
|
|
Recommendation:
Ensure that the contact time is recorded.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-
|
|
Violation:
There were only two sites per month from the distribution system that were tested for the presence of E. coli. Additionally, these sample sites did not change each month.
|
|
Recommendation:
Ensure that a minimum of four potable water samples per month are collected and analyzed for the presence of Escherichia coli and are collected randomly from locations on the forward, aft, upper, and lower decks of the vessel. Ensure that sample sites are changed each month.
|
|
|
Item No.:
07
|
|
Site:
Potable Water-
|
|
Violation:
The variance for skin tanks required that an Ecolab Technician test the salinity meters and alarm system every six months. There was no record of this.
|
|
Recommendation:
Ensure that potable water tanks do not share a common wall with the hull of the vessel or with tanks containing non-potable water or other liquids. Ensure that all of the requirements/recommendations in the variance procedure are followed.
|
|
|
Item No.:
41
|
|
Site:
Ventilation-
|
|
Violation:
The drain pan in air conditioning unit 1 was soiled.
|
|
Recommendation:
Ensure that air handling units are kept clean.
|
|
|
Item No.:
28
|
|
Site:
Galley-Wine Station
|
|
Violation:
The soiled milk dispensing tube and parts for the coffee machine were soaking in a cleanser inside the refrigerated compartment of the coffee machine.
|
|
Recommendation:
Do not store soiled equipment in this compartment.
|
|
|
Item No.:
20
|
|
Site:
Food Service General-
|
|
Violation:
Slotted fasteners and exposed coils were in the undercounter refrigeration units, making cleaning difficult. A very jagged surface was on the upper drip pan inside the salad refrigeration unit, making cleaning difficult.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-
|
|
Violation:
There were several rough surfaces and peeling finishes on the deck in the galley, making cleaning difficult. There was a seam between the left bulkhead and the deck in dry stores, making cleaning difficult. Additionally, these areas were not coved.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning. Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
|
|
|
Item No.:
33
|
|
Site:
Provisions-Dry Stores Room
|
|
Violation:
The left back corner of the deck was soiled.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
16
|
|
Site:
Food Service General-
|
|
Violation:
Per the letter from the supplier, the cold smoked salmon was only frozen for 72 hours at -4°F and not the required 168 hours.
|
|
Recommendation:
Before service in ready-to-eat form, ensure that raw, raw-marinated, partially cooked, or marinated-partially cooked fish other than molluscan shellfish: (1) Are frozen throughout to a temperature of -20°C (-4°F) or below for 168 hours (7 days) in a freezer; or -35°C (-31°F) or below for 15 hours in a blast freezer.
|
|
|
Item No.:
21
|
|
Site:
Galley-
|
|
Violation:
The knob for the broiler shelf handle was missing, resulting in exposed threads that were not easy to clean.
|
|
Recommendation:
Replace the knob.
|
|
|
Item No.:
27
|
|
Site:
Galley-
|
|
Violation:
There was a slight accumulation of grease around the oil discharge pipe of the fryer.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
34
|
|
Site:
Galley-
|
|
Violation:
There was a slight leak at the steam line under the kettle.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
20
|
|
Site:
Galley-Bakery/Pastry
|
|
Violation:
There were rough repair welds along the inside bottom of the mixer bowl, making cleaning difficult.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
33
|
|
Site:
Galley-
|
|
Violation:
The deck was rough and difficult to clean under refrigeration units 9 and 10.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Dry Stores
|
|
Violation:
There was an opening around the sprinkler head, making cleaning difficult.
|
|
Recommendation:
Ensure that bulkheads and deckheads have smooth, hard finishes, and light colored surfaces.
|
|
|
Item No.:
15
|
|
Site:
Food Service General-
|
|
Violation:
The shellstock tags were kept for 90 days, but there was no correlation between the tags and the date of service.
|
|
Recommendation:
Ensure that shellstock shellfish tags: (1) Remain attached to the container in which the shellstock are received until the container is empty. (2) Are maintained by retaining shellstock tags or labels for 90 calendar days from the date the container is emptied by using an approved record keeping system that keeps the tags or labels in chronologic order correlated to the date when the shellstock are served.
|
|
|
Item No.:
19
|
|
Site:
Buffet-
|
|
Violation:
The bread and pastry items were not under a sneeze guard. These items were in covered containers on the top of the buffet line. The tongs for serving these items were not protected.
|
|
Recommendation:
Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means. Ensure that each self-service food dispensing utensil is covered or located beneath shielding during service.
|
|
|
Item No.:
36
|
|
Site:
Bar-Main Bar
|
|
Violation:
The two light bulbs at the entrance to the pantry area were not shielded and were not working. The light level in the entrance was inadequate.
|
|
Recommendation:
Ensure that the light intensity is at least 110 Lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure that the light intensity is at least 220 Lux (20 foot candles) in bars and at dining room waiter stations during periods of cleaning.
|
|
|
Item No.:
19
|
|
Site:
Pantry-Main Bar
|
|
Violation:
Cans of soda were stored under the handwash sink waste line.
|
|
Recommendation:
Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
21
|
|
Site:
Buffet-Topsiders
|
|
Violation:
The utility lines for the coffee machines draped the counter, making cleaning difficult.
|
|
Recommendation:
To facilitate cleaning, ensure that these lines do not drape the counter.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Topsiders
|
|
Violation:
Side shields were not provided between the two buffet stations.
|
|
Recommendation:
Install side shields between these two stations. Because passengers can approach the stations from either side install the shields on both sides of these stations.
|
|