|
|
|
Item No.:
33
|
|
Site:
Galley-
|
|
Violation:
The coving at the deck/bulkhead juncture under the fryer was missing.
|
|
Recommendation:
Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
|
|
|
Item No.:
19
|
|
Site:
Buffet-Officer's Mess
|
|
Violation:
There was a missing side shield on the sneeze guard at the last section of the buffet line.
|
|
Recommendation:
Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
34
|
|
Site:
Galley-Sabitini
|
|
Violation:
There was a leak at the valve on the drain line for the kettle.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Galley-Crowne Grill
|
|
Violation:
There were unsealed openings around the deckhead pipe penetrations inside the hood cleaning cabinet.
|
|
Recommendation:
Seal the openings.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Distribution System
|
|
Violation:
It appeared that the ship had a forward and aft distribution loop that was interconnected and shared a common return line. However, the E3 line off of the manifold that served the bell box pantry and the Sky Walker Bar was not interconnected with the rest of the system except at the return line. This left a far point of the system that was not being analyzed for a free halogen residual by an automatic halogen analyzer with a chart recorder. Per the staff's records, two manual free halogen residual tests were performed each day at the Sky Walker Bar and were within the acceptable range of 0.2 to 5 ppm free residual chlorine.
|
|
Recommendation:
Ensure that a halogen analyzer-chart recorder is installed at a distant point in the potable water distribution system where a significant water flow exists. In cases where dual distribution loops exist, and no pipes connect the loops, ensure that an analyzer and chart recorder is installed on each loop.
|
|
|
Item No.:
11
|
|
Site:
Medical-Asymptomatic Crew
|
|
Violation:
During the last cruise, the ill crew member's close contact was not interviewed at the 48 hour interval after the onset of crew illness. The contact was interviewed immediately and at 24 hours only.
|
|
Recommendation:
Ensure that medical staff conduct daily verbal interviews with asymptomatic crew until 48 hours after onset of the ill crew member's symptoms.
|
|
|
Item No.:
34
|
|
Site:
Food Service General-Deck Drains
|
|
Violation:
The following areas had clogged deck drains:
1. Gazebo area aft technical compartment 150611A
2. Cafe Caribe portside deck drain
3. Room Service handwash sink in warewash area and hot galley
4. Lido Galley Deck 14 soup stations
Per staff, the ship was listing and this caused those deck drains to be clogged.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Gazebo Area Aft
|
|
Violation:
Technical compartments 150611A and 150609 were soiled.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Gazebo Area Forward
|
|
Violation:
The paint on the wood trim under the handsink was peeling.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Cafe Caribe
|
|
Violation:
The stone plate inside the middle oven was cracked.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Cafe Caribe
|
|
Violation:
The coving at the deck/bulkhead juncture under the carving station was missing.
|
|
Recommendation:
Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
|
|
|
Item No.:
33
|
|
Site:
Other-Exit/Entrance to Horizon Court
|
|
Violation:
The decks under the waiter stations were constructed of a raw wood.
|
|
Recommendation:
Ensure that surfaces subject to routine splashes, spillage, or other soiling during normal use have easily cleanable features.
|
|
|
Item No.:
33
|
|
Site:
Other-Pizzeria
|
|
Violation:
The profile strip on the edge of the column to the left of the oven was damaged.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
34
|
|
Site:
Galley-Garde Manger
|
|
Violation:
There was a leak at the drain line of the handwash sink.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
21
|
|
Site:
Galley-Hot Galley
|
|
Violation:
The sealant on the front edges of the fryer was peeling.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions.
|
|
|
Item No.:
37
|
|
Site:
Galley-Soup Station
|
|
Violation:
There was an excessive amount of condensation on the deckhead above the round tilting kettles.
|
|
Recommendation:
Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
16
|
|
Site:
Galley-Time As A Public Health Control Plan
|
|
Violation:
The time as a public health control plan stated the bain marie units in the galley were on temperature control. Per staff, these units were on time control. This was corrected.
|
|
Recommendation:
Ensure the time as a public health control plan reflects the service.
|
|
|
Item No.:
21
|
|
Site:
Galley-Deck 6 Hot Galley
|
|
Violation:
The gasket for the blast chiller was loose.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions.
|
|
|
Item No.:
34
|
|
Site:
Galley-Deck 6 Starboard Forward Warewash
|
|
Violation:
There was a leak at the steam line under the three compartment sink.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
34
|
|
Site:
Galley-Deck 6 Hot Galley
|
|
Violation:
There was a leak at the steam line in the technical compartment for the starboard forward bain marie.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 6 and Deck 5
|
|
Violation:
There were slotted fasteners inside the ovens and on the collar of the mixers.
|
|
Recommendation:
Replace the slotted fasteners with smooth, low profile and non-corroding fasteners.
|
|
|
Item No.:
33
|
|
Site:
Galley-Deck 5 Pastry
|
|
Violation:
The deck grout was missing in front of the mixers.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|