Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Balmoral Cruise Line: Fred Olsen Cruise Line Inspection Date: 04/29/2009 Inspection Score: 99
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 08
Site: Potable Water-
Violation: The cross-connection control program only listed the model of the device in the column for type of device. There was no indication of the type of device or the manufacturer of the device so that the type could be determined.
Recommendation: Add either the type of device or the manufacturer of the device to the cross-connection control program. A key that indicates what each model number represents would be acceptable.
Item No.: 08
Site: Potable Water-
Violation: The reduced pressure assemblies for the evaporators were not listed on the cross-connection control program.
Recommendation: Add these devices to the cross-connection control program. Ensure that the assemblies are tested and the results recorded.
Item No.: 08
Site: Potable Water-
Violation: There were no records for the testing of the reduced pressure assemblies. The vessel did not have the means to test these assemblies, but a test kit was on order.
Recommendation: Ensure that backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, are inspected and tested with a test kit at least annually and that the test results showing the pressure differences on both sides of the valves are maintained for each device. Ensure that the inspection and test results for backflow preventers are retained for at least 12 months and are available to the VSP for review during inspections.
Item No.: 41
Site: Housekeeping-Spa
Violation: There was no means to exit the ladies changing to the fitness room without touching the door handle with bare hands. There were tissues, but no trash can by that exit door. There was a toilet room inside the changing room.
Recommendation: Equip public toilet facilities so that persons exiting the toilet room are not required to handle the door with bare hands. This may be accomplished by methods such as locating paper towel dispensers at sinks and waste containers near the room door, installing mechanically operated doors, door removal, or other effective means.
Item No.: 10
Site: Recreational Water Facilities-Deck 7 Pool
Violation: It was unknown if the pool drain cover met anti-entrapment standards. The construction of the drain prevented body entrapment, but it was unclear if it prevented hair entanglement.
Recommendation: Ensure that anti-entrapment drain covers or other drains that prevent entrapment hazards as specified in U.S. Consumer Product Safety Publication 363-009801 (dual drains/channel drains) are provided on swimming pools and whirlpool spas. Ensure that drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in AMSE/ANSI A112.19.8M or an equivalent standard.
Item No.: 11
Site: Medical-
Violation: There was no documentation of the 48 hour interview of close contacts of crew members with gastrointestinal illness.
Recommendation: Ensure that medical staff conduct daily verbal interviews with asymptomatic crew until 48 hours after onset of the ill crew members symptoms. Maintain documentation of the initial, 24-hour and 48-hour interviews with asymptomatic contacts of ill crew members.
Item No.: 16
Site: Buffet-Palms Cafe
Violation: The time as a public health control plan stated that food in the hot hold back-up units were on temperature control. However, the hot hold unit under the bain marie was marked as time control. Per the staff, this label was a left over from the old cruise line and they used this unit as temperature control. No food was in the hot hold unit.
Recommendation: Remove the label from the hot hold unit.
Item No.: 33
Site: Food Service General-Preparation and Service Areas
Violation: There was recessed and missing grout in many of the preparation and service areas.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Other-Clean Elevator # 8
Violation: The back right corner of the elevator had a gap at the floor/bulkhead juncture that was soiled with food. Also the front door slide rail was soiled with food.
Recommendation: Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 33
Site: Galley-Palm Cafe
Violation: The bulkhead between the hot area and the bread station was damaged.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 21
Site: Buffet-Palm Cafe
Violation: The technical space under the right bain marie had an unsealed pipe penetration in the floor.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 33
Site: Buffet-Palm Cafe
Violation: The deck/counter juncture was not coved at the omelet station.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 19
Site: Buffet-Palm Cafe
Violation: There was an unlabeled pan of vegetable oil at the omelet station. Per staff, several different types of oil are used on the vessel including some nut and seed oils.
Recommendation: Ensure that working containers holding food or food ingredients that are removed from their original packages for use on the vessel, such as cooking oils, flour, herbs, potato flakes, salt, spices, and sugar are identified with the common name of the food.
Item No.: 19
Site: Buffet-Avon & Spey
Violation: Side shields were not provided on the sneeze guard at the four center serving areas. Passengers lined up within one meter of the food at these areas.
Recommendation: Install side shields on the sneeze guards where passengers line up within 1 meter of the food on display.
Item No.: 33
Site: Galley-Avon & Spey
Violation: There was an unsealed electrical line opening in the bulkhead behind oven 1 & 2.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 21
Site: Galley-Avon & Spey Dishwash
Violation: A rope was used to tie the clean dish storage rack the clean sorting table. The rope material was hard to clean.
Recommendation: Remove the rope and use a method that is easy to clean.
Item No.: 27
Site: Galley-Avon & Spey Dishwash
Violation: The rope used to tie the clean dish storage rack to the clean sorting table was soiled.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Other-Spey Dining Area
Violation: The deck/cabinet juncture at the center waiter station was not coved. The metal trim at the bottom of the bulkhead was separated creating seams.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters). Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 33
Site: Other-Ballindalloch Dining Area
Violation: The waiter stations were not coved at the deck/cabinet juncture.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 33
Site: Galley-Beveage Station
Violation: There was a hole in the bulkhead behind coffee urn # 2.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 20
Site: Galley-Vegetable & Hot Buffet Station
Violation: There was excessive steam coming from the door of the left Convotherm oven.
Recommendation: Repair the door to the oven to control the excess stream.
Item No.: 37
Site: Galley-Vegetable & Hot Buffet Station
Violation: The steam from the left Convotherm oven was causing condensate to collect on the deckhead above the oven.
Recommendation: Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 34
Site: Galley-Vegetable & Hot Buffet Station
Violation: The drain line from the right Convotherm oven was not directed toward a deck drain. This caused excessive water on the deck.
Recommendation: Direct the drain line toward the deck drain.
Item No.: 33
Site: Galley-Vegetable & Hot Buffet Station
Violation: There were missing tiles and grout under the Convotherm ovens.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 26
Site: Galley-Hot Galley
Violation: The two combination ovens were soiled inside.
Recommendation: Ensure that food only contacts surfaces of equipment and utensils that are cleaned and sanitized.
Item No.: 34
Site: Galley-Potwash
Violation: There were two leaks from the final rinse compartment of the 3-compartment sink.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 33
Site: Buffet-Officer Mess
Violation: There was an open unusued deck penetration, resulting in a hole in the deck.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 34
Site: Preparation Room-
Violation: There was a leak from the first compartment of the 3-compartment sink.
Recommendation: Ensure that a plumbing system in a food area is maintained in good repair.
Item No.: 08
Site: Galley-
Violation: There was a non-continuous pressure device on the potable water line supplying the spray hose of the combination oven.
Recommendation: Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program