|
|
|
Item No.:
08
|
|
Site:
Potable Water-Bunkering Station
|
|
Violation:
Two bunkering hoses had faded "Potable Water Only" stenciling. The stenciling was near the center of the hoses and not located at each connecting end of the hose sections.
|
|
Recommendation:
Ensure that potable water hoses are labeled for use with the words "potable water only" in letters at least 13mm (0.5 inch) at each connecting end.
|
|
|
Item No.:
05
|
|
Site:
Potable Water-Far Point Analyzer
|
|
Violation:
The analyzer-chart recorder was registering 3.5 ppm free halogen. The inspector's test result was 1.6 ppm (using the test kit high range setting with the high range vial and the free chlorine reagent). The operators test result was 3.5 ppm, however, the operator was observed using the test kit in the high range setting while using the low range vial and total chlorine reagent. The proper test procedure was not being performed by the operator and the analyzer was more than 0.2 ppm out of calibration.
|
|
Recommendation:
Ensure that the free residual halogen measured by the halogen analyzer is ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Far Point Analyzer Charts
|
|
Violation:
On 5/14 the far point analyzer chart indicated that there was no free halogen from 0700-1800 and there was no notation as to why. On 5/13 the far point chart indicated that there was no free halogen level for the entire day and there was no notation as to why. Per staff the primary pump failed and the back-up pump did not function. The pump was being repaired.
|
|
Recommendation:
Ensure that halogen analyzer-chart recorder charts are changed, initialed, and dated daily and contain notations of any unusual water events in the potable water system.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Monthly Sampling
|
|
Violation:
There was no record that the minimum monthly distribution system microbiological sampling was being performed.
|
|
Recommendation:
Ensure that a minimum of four potable water samples per month are collected and analyzed for the presence of Escherichia coli and are collected randomly from locations on the forward, aft, upper, and lower decks of the vessel. Ensure that sample sites are changed each month.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-connection control program
|
|
Violation:
The fuel centrifuge and Ecolab soap dispenser backflow prevention devices were not on the cross-connection control program listing of the backflow prevention method/device. In addition, only one backflow prevention devices for the the washing machine potable water lines was listed.
|
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Potable Water Tank Disinfection
|
|
Violation:
During the last dry dock (December 2008), the maintenance log stated that the potable water tanks were inspected, cleaned and disinfected. However, there was no record of the free halogen residual level used to disinfect the tank or contact time. In addition there was no record that the free halogen residual was below 5 ppm before the tank was placed back on line.
|
|
Recommendation:
Ensure that documentation of any inspection, cleaning, disinfection (including concentration and contact time of disinfectant), and flushing is maintained for 12 months and is available to the VSP for review during inspections. Ensure that the disinfected parts of the system are flushed with potable water until the free residual halogen is at or below 5.00 mg/L (ppm).
|
|
|
Item No.:
33
|
|
Site:
Galley-Reach-in Refrigartion
|
|
Violation:
The deck and bulkhead to the left side of the reach-in refrigeration was soiled.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
21
|
|
Site:
Galley-Storage Spaces
|
|
Violation:
The bulkhead material in the storage spaces was a galvanized metal. The bulkhead surfaces were corroded.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material. Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions.
|
|
|
Item No.:
27
|
|
Site:
Galley-Plate Storage Bins
|
|
Violation:
The floor and drawere sliding track rails were soiled.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
21
|
|
Site:
Provisions-Dry Store
|
|
Violation:
The deck stand leg pads were galvanized metal and were corroded.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions. Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
|
Item No.:
22
|
|
Site:
Galley-
|
|
Violation:
There was only a two-compartment sink in the galley. However, there was a dishwash machine.
|
|
Recommendation:
Ensure that a sink with at least 3 compartments is provided for manually washing, rinsing, and sanitizing equipment and utensils.
|
|
|
Item No.:
21
|
|
Site:
Galley-
|
|
Violation:
The non-food contact surfaces of equipment had gaps, open seams and other difficult to clean features.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance. Ensure that non-food contact equipment is maintained in good repair and proper adjustment including: (1) Equipment maintained in a state of repair and condition that meets the materials, design, construction, and operation specifications of these guidelines. (2) Equipment components such as doors, seals, hinges, fasteners, and kick plates are kept intact, tight, and adjusted in accordance with manufacturer's specifications.
|
|
|
Item No.:
33
|
|
Site:
Galley-
|
|
Violation:
The decks, bulkheads and deckheads in the food preparation and food storage areas had gaps, open seams, gaps between counters, attached equipment, exposed piping , uneven panels and other difficult to clean features.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning. Ensure that exposed utility service lines and pipes, including lines for fire detection and protection systems, are installed so they do not obstruct or prevent cleaning. Ensure that surfaces subject to routine splashes, spillage, or other soiling during normal use have easily cleanable features. Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Port Microbiological Reports
|
|
Violation:
There were no port micorbiolgical reports available and no records on any onboard testing for the month of May. The vessel bunkered water in Seattle, Juneau, and Petersburg.
|
|
Recommendation:
Where available, ensure that the vessel has a copy of the most recent microbiologic report from each port before bunkering potable water to verify that the water meets potable standards.
|
|