Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Wind Spirit Cruise Line: Windstar Cruises Inspection Date: 12/10/2006 Inspection Score: 92
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 09
Site: DO NOT USE (whirlpool/spa)-Whirlpool Records
Violation: The free bromine residual recorded on the chart was less than 4 ppm for 2 hours on 12/08/06. There was no indication that the whirlpool was closed. When questioned, staff stated the pH was adjusted and that the whirlpool remained open during that time. This is a repeat violation from the previous inspection dated 03/25/06.
Recommendation: Ensure that whirlpool spas are maintained at a free residual chlorine of >3.0 mg/L (ppm) and <10 mg/L (ppm), or a free residual bromine of >4.0 mg/L (ppm) and <10 mg/L (ppm). Ensure the whirlpool spa is closed if the bromine residual is less than 4 ppm or greater than 10 ppm.
Item No.: 08
Site: Potable Water-
Violation: The reduced pressure backflow preventers on the fire main shore connections were tested on 09/16/06. However, the pressure differentials were not recorded.
Recommendation: Ensure that backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, are inspected and tested with a test kit at least annually and that the test results showing the pressure differences on both sides of the valves are maintained for each device.
Item No.: 08
Site: Potable Water-Potable Water Tank
Violation: The sample cock for the FW.2.Port potable water tank was pointing horizontally.
Recommendation: Ensure that potable water tanks have sample valves which are turned down.
Item No.: 08
Site: Potable Water-Engine Room
Violation: The backflow prevention device on the spray hose which was connected to the potable water line was not vented. This hose was located near the sink.
Recommendation: Replace the device with a vented continuous pressure backflow prevention device.
Item No.: 10
Site: Recreational Water Facilities-Pool and Whirlpool
Violation: The drain covers were not stamped to indicate that they were anti-entrapment by design. There was no documentation on the vessel that these drain covers were anti-entrapment in design. This was a repeat violation from the previous inspection. Staff stated new drain covers were on order.
Recommendation: Ensure that anti-entrapment drain covers or other drains that prevent entrapment hazards as specified in U.S. Consumer Product Safety Publication 363-009801 (dual drains/channel drains) are provided on swimming pools and whirlpool spas. Ensure that drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in AMSE/ANSI A112.19.8M or an equivalent standard.
Item No.: 41
Site: Ventilation-Air Conditioning Unit 4
Violation: This unit had an excessive amount of corrosion inside. Staff stated this unit will be repainted during the next dry dock.
Recommendation: Ensure that air handling units are kept clean.
Item No.: 20
Site: Galley-Verandah Galley - Port
Violation: The undercounter refrigerator was posted out of order. The ship was awaiting replacement parts.
Recommendation: Ensure the undercounter refrigerator is in working order.
Item No.: 21
Site: Galley-Verandah Galley - Port
Violation: Peeling labels were noted on the flat-top grill, making cleaning difficult.
Recommendation: Remove the peeling labels.
Item No.: 26
Site: Galley-Verandah Galley
Violation: Five previously cleaned plates were found soiled and stored as clean.
Recommendation: Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 16
Site: Galley-Garde Manger
Violation: A pan of cooked cauliflower salad was measured with an internal product temperature of 78° F inside the reach-in refrigerator. According to the chef, the item was prepared approximately 40 minutes prior to testing. The item was placed immediately in the blast chiller.
Recommendation: Ensure that cooked potentially hazardous food is cooled: (1) Within 2 hours, from 60°C (140°F) to 21°C (70°F); and (2) Within 4 hours, from 21°C (70°F) to 5°C (41°F) or less.
Item No.: 29
Site: Galley-Garde Manger
Violation: The handwash station was blocked by two large garbage cans. There was no active food preparation at the time of the finding. In addition, there was evidence that the handwash station was being used to dump food as a large amount of shredded salad was found in the sink.
Recommendation: Ensure that handwashing facilities are used for no other purpose and are accessible at all times.
Item No.: 26
Site: Pantry-Lounge Bar
Violation: One previously cleaned bar glass was found soiled with lipstick.
Recommendation: Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 24
Site: Bar-Pool Bar
Violation: The final rinse of the single compartment glasswash utilized a chemical (Chlorine-based) sanitizer. On testing the machine using a 50 - 200 ppm test strip, there was no color change. The machine was tested several times without any indication of adequate chlorine in the final sanitizing rinse. The machine was in active use, as there were glasses inside that had just been washed. The bar appeared open as people around the bar had alcohol and non-alcohol beverages. A review of the dishwasher logs indicated testing for the wash cycle only.
Recommendation: Ensure that a chlorine solution used as a sanitizing solution has a concentration between 50 mg/L (ppm) and 200 mg/L (ppm).
Item No.: 33
Site: Buffet-
Violation: Coving was not provided at the bulkhead-deck juncture, making cleaning difficult. An accumulation of water was noted along a gap at the bulkhead-deck juncture under the handwash sink. This is a repeat item from the previous inspection.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters). Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 33
Site: Food Service General-
Violation: Some areas of the deck in the food service areas had recessed grout and cracked and chipped deck tiles (especially along the gutterways in the main galley). Some areas of the deck adjacent to and beneath equipment were rough, making cleaning difficult. In addition, some areas were not coved.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning. Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program