Item No.:
08
|
|
Site:
Potable Water-Device Tests Records
|
|
Violation:
There was no indication in the records that the annual testing for the two international shore connection reduced pressure type backflow prevention devices had been completed. Per staff, the test kit had failed and a new kit had been ordered and was just received.
|
|
Recommendation:
Ensure that backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, are inspected and tested with a test kit at least annually and that the test results showing the pressure differences on both sides of the valves are maintained for each device. Ensure that the inspection and test results for backflow preventers are retained for at least 12 months and are available to the VSP for review during inspections.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Spa - Hair Rinse Sink
|
|
Violation:
The backflow prevention devices on both the hot and cold water lines were installed with the intermediate atmospheric vents facing up.
|
|
Recommendation:
Ensure that the backflow prevention devices are installed to prevent pooling of water in the intermediate atmospheric vent ports.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Spa - Hair Rinse Sink
|
|
Violation:
The backflow prevention device type listed in the cross-connection control plan did not match the installed unit.
|
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Poop Deck
|
|
Violation:
The water line was not striped blue at this location.
|
|
Recommendation:
Ensure that potable water piping and fittings are painted or stripped auxiliary blue, or in accordance with ISO 14726, at 5 m (15 feet) intervals on each side of partitions, decks, and bulkheads in all spaces, except where the decor would be marred by such markings.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Swimming Pool and Spa
|
|
Violation:
The drain covers appeared to be an anti-vortex design, however, they were not stamped as being anti-vortex and there was no manufacturers data indicating that the units had been tested. Staff provided emails and purchase order information showing that anti-vortex covers were ordered and received, however, the manufacturer has not provided the VSP required certification literature.
|
|
Recommendation:
Ensure that anti-entrapment drain covers or other drains that prevent entrapment hazards as specified in U.S. Consumer Product Safety Publication 363-009801 (dual drains/channel drains) are provided on swimming pools and whirlpool spas. Ensure that drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in AMSE/ANSI A112.19.8M or an equivalent standard.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-Dinning Room
|
|
Violation:
The center wait station were coved with a non-durable caulking. The bussing stations were not coved.
|
|
Recommendation:
Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
|
|
|
Item No.:
33
|
|
Site:
Food Service General-Decks
|
|
Violation:
Some of the deck areas in the food service areas had recessed grout and cracked or chipped deck tiles. In addition, some of the deck surfaces were rough, especially beneath and adjacent to equipment. Some of the areas were not coved at the deck-bulkhead junctures. These items are due to be corrected at the March-April 2007 dry dock period.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
20
|
|
Site:
Food Service General-Reach-in Refrigerators
|
|
Violation:
The interior surfaces of several of the reach-in refrigerators were rough, making cleaning difficult. These units are due to be replaced during the upcoming dry dock period.
|
|
Recommendation:
Ensure that multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams >1 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel such as screwdrivers, pliers, open-end wrenches, and Allen wrenches.
|
|
|
Item No.:
21
|
|
Site:
Galley-Hot Galley
|
|
Violation:
A peeling label was noted on the exterior of the convection oven, making cleaning difficult. This item was corrected during the inspection.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
26
|
|
Site:
Galley-Hot Galley
|
|
Violation:
Three previously cleaned pans were found soiled and stored as clean.
|
|
Recommendation:
Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Galley-Potwash
|
|
Violation:
Two previously cleaned hotel pans were found soiled and stored as clean.
|
|
Recommendation:
Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
21
|
|
Site:
Other-Officer's Mess
|
|
Violation:
Holes were noted in the non-food-contact areas of the undercounter reach-in refrigerator.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
33
|
|
Site:
Galley-Verandah - Portside
|
|
Violation:
The carpeting in front of the dry storage cabinet was soiled. The carpeting was difficult to clean.
|
|
Recommendation:
Remove carpeting and replace with a material that is smooth and easily cleanable. Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Galley-Verandah - Portside
|
|
Violation:
Standing water was noted on the deck under the flat-top grill. This item was corrected during the inspection.
|
|
Recommendation:
Remove standing water.
|
|
|
Item No.:
21
|
|
Site:
Galley-Verandah - Portside
|
|
Violation:
Peeling labels were noted on the flat-top grill.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
27
|
|
Site:
Galley-Verandah - Starboard
|
|
Violation:
The soup container well was soiled. This area was previously cleaned.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
21
|
|
Site:
Galley-Verandah - Starboard
|
|
Violation:
The countertop warmer unit was missing an end cap, leaving an opening, making cleaning difficult.
|
|
Recommendation:
Replace the missing end cap.
|
|
|
Item No.:
20
|
|
Site:
Galley-Verandah - Portside
|
|
Violation:
The undercounter refrigerator was posted out of order since the last inspection. This is a repeat item from the last inspection. This item is due to be replaced during the upcoming dry dock period.
|
|
Recommendation:
Repair or replace the undercounter refrigerator.
|
|
|
Item No.:
39
|
|
Site:
Provisions-Dry Storage
|
|
Violation:
Numerous insects (grain beetles) were observed on the countertop under two 50 lb bags of dry beans. The insects were observed coming out of the bags as well. These items were discarded during the inspection and the area was inspected, cleaned and sanitized.
|
|
Recommendation:
Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Dry Storage
|
|
Violation:
The deckhead above the storage area were buckled, leaving an opening, making cleaning difficult. This item is due to be corrected during the upcoming dry dock period.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Pop Deck
|
|
Violation:
The deck tap was not provided with a backflow prevention device.
|
|
Recommendation:
Install a backflow prevention device on the deck tap.
|
|