Item No.:
37
|
|
Site:
Galley-Hot Galley
|
|
Violation:
Condensate was noted on the undersurface of the shelf above the hot food line. The water was boiling in the bain marie.
|
|
Recommendation:
Ensure that exhaust ventilation hood systems in food preparation and warewashing areas including components such as hoods, fans, guards, and ducting are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
19
|
|
Site:
Galley-Hot Galley
|
|
Violation:
Condensate was noted above food on the hot line.
|
|
Recommendation:
Ensure that condensate is not allowed to form above food or to drip on to food.
|
|
|
Item No.:
20
|
|
Site:
Food Service General-
|
|
Violation:
Slotted fasteners were noted in the ice/water contact areas of the upper compartment of the ice machines, making cleaning difficult.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
37
|
|
Site:
Galley-Dishwash/Glasswash Area
|
|
Violation:
This area was very hot and humid. Per the staff, the ventilation was turned off for a short time in this area.
|
|
Recommendation:
Ensure that all food preparation, warewashing, and toilet rooms have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|
|
Item No.:
33
|
|
Site:
Other-Deck 2 Dining Room
|
|
Violation:
Gaps and seams were noted along the corners of the wait stations at the deck junctures. A loose cove base was noted at the starboard wait station. A profile strip was missing along the bulkhead at the starboard wait station. These conditions made cleaning difficult.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
20
|
|
Site:
Food Service General-
|
|
Violation:
The milk tubes at the bulk dispensers were longer than one inch.
|
|
Recommendation:
Ensure that the bulk milk container dispensing tube is cut on the diagonal leaving no more than 25mm (1 inch) protruding from the chilled dispensing head.
|
|
|
Item No.:
22
|
|
Site:
Galley-Potwash
|
|
Violation:
There were several items in the final rinse compartment and the top item, a cutting board, was not fully submerged.
|
|
Recommendation:
Ensure that the items sanitized at this sink can be full submerged.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Crew Mess Service Side
|
|
Violation:
Rags and debris were noted in the sliding door void space.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
28
|
|
Site:
Preparation Room-
|
|
Violation:
A small amount of standing water was noted in the bottom of the previously cleaned vegetable washers.
|
|
Recommendation:
After cleaning and sanitizing, ensure that equipment and utensils are air-dried or adequately drained before contact with food.
|
|
|
Item No.:
21
|
|
Site:
Other-Medussa Dining Room
|
|
Violation:
A small gap was noted at the wait stations along the mirrored sections near the deck, making cleaning difficult. A marble section was missing along the front portion of the portable wait station exposing a rough surface that was difficult to clean.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Middle Beverage Station
|
|
Violation:
Peeling paint was noted in the technical spaces, making cleaning difficult.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
34
|
|
Site:
Buffet-Middle Beverage Station
|
|
Violation:
A leak was noted at the water filter.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Dessert Station
|
|
Violation:
Sugar free mousse, and other potentially hazardous desserts were tested at 52°F in the refrigeration unit under the buffet line. The thermometer in this unit was broken. These items had been in the unit less than 1/2hour and were to be discarded in less than 2 hours. The refrigerator was on temperature control.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Port Service Line
|
|
Violation:
The handles of two sets of tongs were in contact with the cold cuts on the trays. This was noted prior to the buffet opening for service.
|
|
Recommendation:
During pauses in food preparation or dispensing, ensure that food preparation and dispensing utensils are stored: (1) In the food with their handles above the top of the food and the container.
|
|
|
Item No.:
19
|
|
Site:
Buffet-
|
|
Violation:
The soup urns were not placed under a sneeze guard. The urns had hinged lids.
|
|
Recommendation:
Ensure that the soup urns are placed under an appropriate sneeze guard.
|
|
|
Item No.:
33
|
|
Site:
Other-
|
|
Violation:
The decorative finishes on the doors at the grill and at the bars were slightly damaged, making cleaning difficult.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
02
|
|
Site:
Medical-
|
|
Violation:
The standardized gastrointestinal illness log used by the vessel did not have a column on whether or not the individuals were reportable cases.
|
|
Recommendation:
Ensure that all of the data required elements are included in the vessel's log.
|
|
|
Item No.:
01
|
|
Site:
Medical-
|
|
Violation:
A review of the gastrointestinal illness logs noted a discrepancy between the reportable cases and the cases reported in the 24-hour report. The lead nurse indicated that individuals who were dispensed anti-diarrheal medications who were not seen by the doctor were not reported as cases.
|
|
Recommendation:
Ensure that all individuals meeting the case definition are included in the reports.
|
|
|
Item No.:
08
|
|
Site:
Pantry-Armonia
|
|
Violation:
The potable water line supplying the flaked ice machine was not provided with backflow protection.
|
|
Recommendation:
Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Desssert Station
|
|
Violation:
The refrigeration unit under this station was not maintaining potentially hazardous foods at or below 41°F.
|
|
Recommendation:
Ensure that equipment for cooling and heating food, and holding cold and hot food, is sufficient in number and capacity to maintain specified potentially hazardous food temperatures.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Engine Room
|
|
Violation:
The technical water lines were striped blue. There were a few technical water lines that were striped blue with a secondary color.
|
|
Recommendation:
Remove the blue striping from the technical water lines or add an appropriate secondary color to these lines.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Spa
|
|
Violation:
The backflow prevention device for the men's steam generator was leaking.
|
|
Recommendation:
Repair or replace this device.
|
|
|
Item No.:
08
|
|
Site:
DO NOT USE (whirlpool/spa)-Deck 8 Spa Pump Room
|
|
Violation:
The water lines located after the reduced pressure backflow protection device were striped blue.
|
|
Recommendation:
Remove the blue striping downstream of the reduced pressure backflow protection device.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-
|
|
Violation:
The staff member stated he received pest management training. There was no documentation of the training.
|
|
Recommendation:
Ensure that the training of the pest-control personnel is documented in the Integrated Pest Management Plan.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-
|
|
Violation:
There were no pest inspections conducted of incoming shipments of food and supplies.
|
|
Recommendation:
Ensure that incoming shipments of food and supplies are routinely inspected for evidence of insects, rodents, and other pests. A record of these inspections shall be maintained onboard the vessel and shall be available for review during inspections.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Outbreak Prevention and Response Plan
|
|
Violation:
The Outbreak Prevention and Response Plan stated that public bathrooms were to be disinfected every 4 hours and did not give a disinfection frequency for the public areas.
|
|
Recommendation:
Ensure that the public bathrooms are disinfected on a continuous basis when the rate of illness in passengers or crew members reaches 2%. In addition, ensure that the disinfection frequency for public areas is noted in the plan.
|
|