Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Crystal Serenity Cruise Line: Crystal Cruises LTD Inspection Date: 12/21/2007 Inspection Score: 96
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 20
Site: Galley-
Violation: Soft sealant was found on the food contact area of the slicer.
Recommendation: Remove the soft sealant from the food contact area and replace it with a hard durable food grade sealant.
Item No.: 08
Site: Bar-Crystal Cove
Violation: The backflow prevention device on the potable water line supplying the coffee machine was not a continuous pressure backflow prevention device.
Recommendation: Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.
Item No.: 20
Site: Bar-Star Dust
Violation: One cutting board was pitted and scored, making cleaning difficult.
Recommendation: Ensure that surfaces such as cutting blocks and boards that are subject to scratching and scoring are resurfaced if they no longer can be effectively cleaned and sanitized, or discarded if they are not capable of being resurfaced.
Item No.: 27
Site: Galley-
Violation: The plastic light covers above the hot service line were soiled.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Galley-
Violation: Minor recessed grout was noted in the hot service area of the main galley, making cleaning difficult.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 08
Site: Potable Water-
Violation: Non-continuous pressure backflow protection devices were installed on the potable lines supplying coffee machines in the deck 11 midship pantry, deck 9 forward pantry, crew galley combination ovens, and Trident Bar coffee machine. The potable water line supplying the juice machine and ice machine in the Trident Grill was not fitted with a backflow protection device.
Recommendation: Ensure that a continuous pressure-type backflow preventer is installed when a valve is located downstream from the backflow preventer.
Item No.: 08
Site: Potable Water-
Violation: The backflow protection device on the pot filling hose in the crew galley was installed on the hose in a location where it could be submerged in a pot.
Recommendation: Relocate this device on the potable water line so that it cannot be submerged.
Item No.: 08
Site: Potable Water-
Violation: The records for the disinfection of the potable water tanks noted the quantity of chlorine added to the tanks but not the concentration. Given this, it was not possible to determine the parts per million used during disinfection. Additionally, the record did not note that the tanks were flushed to 5 ppm or less prior to putting the tanks back into use.
Recommendation: Ensure that documentation of any inspection, cleaning, disinfection (including concentration and contact time of disinfectant), and flushing is maintained for 12 months and is available to the VSP for review during inspections. Ensure that the disinfected parts of the system are flushed with potable water until the free residual halogen is at or below 5.00 mg/L (ppm).
Item No.: 06
Site: Potable Water-
Violation: The distribution system far point analyzer recorder charts did not have notations for calibration for December 16-20.
Recommendation: Ensure that the daily, manual comparison test calibration is recorded on the chart or in a log book.
Item No.: 08
Site: Potable Water-
Violation: The comprehensive cross-connection control program did not list the potable water connections to the spray hose and detergent dispenser in the crew galley and potable water connection to the spa steam generator. The correct type of devices were installed on the potable water lines at these locations. The program listed Oras units were used on the lines supplying the spa showers but these devices were noted to be Socla units instead. The program listed Watts N9 units on the lines supplying coffee machines and combination ovens but during the inspection it was noted that Watts NLF9 devices were installed on the lines supplying the crew galley combination ovens and the deck 11 midship and deck 9 forward coffee machines.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 09
Site: Recreational Water Facilities-
Violation: The chlorine residual in the pool was tested in three locations with measurements of 0.4 ppm, 0.6 ppm and 0.9 ppm. The reading in the bridge was said to be 1.3 ppm. The pool was immediately closed.
Recommendation: Ensure that bathers are not allowed to use the pool before a free residual halogen of 1.0 mg/L (ppm) is achieved.
Item No.: 08
Site: Potable Water-
Violation: Air gaps were not provided between the vents for the reduced pressure backflow protection devices and the wastewater system in the whirlpool pump room.
Recommendation: Provide air gaps between the vents and the wastewater system. Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program