Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
DURING BUNKERING THE FREE CHLORINE RESIDUAL WAS NOT TESTED EVERY HOUR.
|
|
Recommendation:
5.2.1.2.2
Free residual halogen monitoring shall be performed at least hourly during the bunkering of potable water and performed at least once every 4 hours during the onboard production of potable water.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
A VENTED BACKFLOW PREVENTION DEVICE WAS NOT NOTED ON THE GARBAGE ROOM SPRAY HOSE.
|
|
Recommendation:
Install a vented device on the potable water line supplying the hose.
|
|
|
Item No.:
26
|
|
Site:
Other-BACKFLOW PREVENTION-SODA UNITS
|
|
Violation:
BRASS FITTINGS WERE NOTED BETWEEN THE BACKFLOW PREVENTION DEVICES AND THE CARBONATORS.
|
|
Recommendation:
7.4.1.1.5
Copper and copper alloys such as brass:
(1) May not be used in contact with a food that has a pH below 6 such as vinegar, fruit juice, or wine or for a fitting or tubing installed between a backflow prevention device and a carbonator.
|
|
|
Item No.:
10
|
|
Site:
Other-POOLS
|
|
Violation:
A SAFETY SIGN WAS NOT PROVIDED AT EACH POOL.
A SHEPHERD'S HOOK WAS NOT PROVIDED AT EACH POOL. THE HOOK THAT WAS PROVIDED WAS INADEQUATE.
A FLOATATION DEVICE WITH AN ATTACHED ROPE WAS NOT PROVIDED AT EACH POOL.
|
|
Recommendation:
6.4.1.1.1
Safety signs shall be provided for public swimming pools and whirlpool spas.
6.4.1.2.1
Easy access shepherd's hook and approved floatation device shall be provided at a prominent location near each public swimming pool. A length of rope 1.5 times the width of the pool should be attached to the floatation device.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE PRESSURE DIFFERENTIALS WERE NOT RECORDED DURING TESTING OF THE REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICE THAT WAS LOCATED BETWEEN THE POTABLE AND INDUSTRIAL WATER SYSTEMS.
|
|
Recommendation:
5.7.2.2.2
Backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, shall be inspected and tested with a test kit at least annually. Test results showing the pressure differences on both sides of the valves shall be maintained for each device.
|
|
|
Item No.:
06
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE FORT DU FRANCE PORT WATER WAS TESTED FOR E. COLI, FROM THE POTABLE WATER TANK, TWO DAYS AFTER THE WATER WAS BUNKERED.
|
|
Recommendation:
Test the port water the day water is bunkered. The sample should be collected prior to the start of bunkering and before any additional chlorine is added.
|
|
|
Item No.:
30
|
|
Site:
Other-GRAND BLEU-HOT BUFFET
|
|
Violation:
A WASTE RECEPTACLE WAS NOT PROVIDED AT THE HANDWASH SINK. DISCARDING OF USED PAPER TOWELS REQUIRES OPENING A DOOR.
|
|
Recommendation:
Install a waste receptacle for used paper towels adjacent to this sink.
|
|
|
Item No.:
20
|
|
Site:
Other-GRAND BLEU-HOT BUFFET
|
|
Violation:
COTTAGE CHEESE WAS TESTED AT 49°F AND MILK WAS TESTED AT 50°F. THESE ITEMS WERE NOT PROPERLY ICED FOR COLD HOLDING.
|
|
Recommendation:
7.4.3.1.1
Equipment for cooling and heating food, and holding cold and hot food, shall be sufficient in number and capacity to maintain specified potentially hazardous food temperatures.
|
|
|
Item No.:
29
|
|
Site:
Other-GRAND BLEU-DISHWASH
|
|
Violation:
A SOILED SILVERWARE RACK WAS PLACED TOO CLOSE TO THE HANDWASH SINK PARTIALLY BLOCKING ACCESS TO THE SINK.
|
|
Recommendation:
Do not block handwash sinks.
|
|
|
Item No.:
19
|
|
Site:
Other-GRAND BLEU-COLD BUFFET
|
|
Violation:
THE LIDS FOR THE BREAD AT THE SELF-SERIVCE BUFFET HAD LARGE OPENINGS.
|
|
Recommendation:
7.3.3.6.1
Food on display shall be protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
26
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
THE SALAD SPINNER WAS SOILED AND STORED AS CLEAN.
|
|
Recommendation:
7.5.5.1.1
Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
|
|
|
Item No.:
21
|
|
Site:
Other-PROVISIONS-VEGETABLE PREPARTION
|
|
Violation:
THE PLASTIC LID WAS CRACKED ON THE POTATO PEELER.
|
|
Recommendation:
Replace the lid.
|
|
|
Item No.:
30
|
|
Site:
Other-GARBAGE ROOM
|
|
Violation:
THE HANDWASH SINK IN THE GARBAGE ROOM WAS NOT PROVIDED WITH A SOAP DISPENSER, PAPER TOWEL DISPENSER, WASTE RECEPTACLE, AND A "WASH HANDS OFTEN" SIGN.
|
|
Recommendation:
7.7.1.1.6
A handwashing facility shall include a sink, soap dispenser, single-use towels dispenser, and waste receptacle.
7.7.1.1.7
A sign stating "WASH HANDS OFTEN" in a language that the food employees understand shall be posted over handwashing sinks.
|
|
|
Item No.:
21
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
THEREMOMETERS WERE NOT PLACED IN THE WARMEST PART OF THE REFRIGERATORS.
|
|
Recommendation:
7.4.2.4.9.1
Temperature measuring devices shall conform to the following guidelines:
(1) In a mechanically refrigerated or hot-food storage unit, the sensor of a temperature measuring device shall be located to measure the air temperature in the warmest part of a mechanically refrigerated unit and in the coolest part of a hot-food storage unit.
|
|
|
Item No.:
33
|
|
Site:
Other-DINING ROOM
|
|
Violation:
A SMALL OPEN SEAM WAS NOTED BETWEEN THE BULKHEAD AND THE CLEAN STATION BACK-SPLASH ON THE STARBOARD SIDE OF THE DINING ROOM.
|
|
Recommendation:
Seal this open seam.
|
|
|
Item No.:
*
|
|
Site:
Other-
|
|
Violation:
IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY.
PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV
USE EMAIL MESSAGE SUBJECT LINE: CLUB MED 2 - CAS - [11/27/2001] .
|
|
Recommendation:
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE INTERNATIONAL SHORE CONNECTIONS WERE NOT FITTED WITH REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICES.
|
|
Recommendation:
Install reduced pressure principle backflow prevention devices on all international shore connections supplying non-potable water systems.
|
|
|
Item No.:
06
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE ANALYZER-CHART RECORDER CHARTS DID NOT HAVE A RANGE OF 0-5 PPM.
|
|
Recommendation:
5.5.2.1.1
Halogen analyzer-chart recorder charts shall have a range of 0.0 to 5.0 mg/L (ppm) and have a recording period of 24 hours.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
PORT WATER WAS NOT COLLECTED AND TESTED FOR HALOGEN DEMAND AND PH PRIOR TO THE START OF BUNKERING.
|
|
Recommendation:
5.2.1.2.1
A halogen demand test and pH shall be conducted on the shore-side water supply before starting the bunkering process to establish the correct halogen dosage.
|
|
|
Item No.:
33
|
|
Site:
Other-GRAND BLEU-HOT BUFFET
|
|
Violation:
BROKEN COVE TILE WAS NOTED IN THE SMALL PANTRY BEHIND THE HOT BUFFET.
|
|
Recommendation:
7.7.4.1.3
Bulkhead and deck junctures shall be coved.
7.7.4.1.1
Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be constructed and maintained for easy cleaning.
|
|
|
Item No.:
21
|
|
Site:
Other-GRAND BLEU-HOT BUFFET
|
|
Violation:
LOOSE SOFT SEALANT WAS NOTED IN THE CARBONATOR CABINET.
|
|
Recommendation:
7.4.2.2.6
Nonfood-contact surfaces shall be free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
22
|
|
Site:
Other-GRAND BLEU-DISHWASH
|
|
Violation:
THE FINAL RINSE PRESSURE AT THE GLASSWASH UNIT WAS NOTED TO BE 40 PSI WHICH WAS ABOVE THE MANUFACTURER'S RECOMMENDED PRESSURE RANGE.
|
|
Recommendation:
7.5.4.1.3
A warewashing machine and its auxiliary components:
(1) Shall be operated in accordance with the machine's data plate and other manufacturer's instructions. (2) A warewashing machine's conveyor speed or automatic cycle times shall be maintained accurately timed in accordance with manufacturer's specifications.
|
|
|
Item No.:
27
|
|
Site:
Other-BAKERY
|
|
Violation:
THE NON-FOOD CONTACT SURFACES UNDER THE BELT OF THE DOUGH ROLLER WERE WET AND SLIGHTLY DISCOLORED.
|
|
Recommendation:
These non-food contact areas should be dried to prevent the growth of mold.
|
|
|
Item No.:
20
|
|
Site:
Other-PROVISIONS-VEGETABLE PREPARATION
|
|
Violation:
THE GASKET AREA OF THE POTATO PEELER HATCH WAS DIFFICULT TO CLEAN AND ROUGH.
|
|
Recommendation:
7.4.1.1.2
Materials that are used in the construction of multiuse utensils and food-contact surfaces of equipment shall be:
(1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
38
|
|
Site:
Other-GARBAGE ROOM
|
|
Violation:
THE MOPS AND BROOMS WERE STORED ON THE DECK. A MOP WAS NOTED IN A PAIL OF SOILED WATER.
|
|
Recommendation:
7.7.7.1.4
After use, mops shall be placed in a position that allows them to air-dry without soiling walls, equipment, or supplies.
|
|
|
Item No.:
20
|
|
Site:
Other-VENICE BAR
|
|
Violation:
THE PLASTIC ICE PAN IN THE UPPER COMPARTMENT OF THE ICE MACHINE WAS CRACKED.
|
|
Recommendation:
Replace the ice pan.
|
|
|
Item No.:
22
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
SPONGES WERE NOTED IN THE SANITIZING BUCKETS.
|
|
Recommendation:
7.5.5.5.2
Sponges may not be used in contact with cleaned and sanitized or in-use food-contact surfaces.
|
|
|
Item No.:
40
|
|
Site:
Other-INTEGRATED PEST MANAGEMENT
|
|
Violation:
THE INTEGRATED PEST MANAGEMENT PLAN DID NOT MENTION SIGHTINGS LOGS OR TRAINING OF PERSONNEL.
|
|
Recommendation:
8.1.1.1.3
The Integrated Pest Management Plan shall include provisions for active monitoring including pest sighting logs for the operational areas of the vessel and training for crew members in charge of log completion.
8.1.2.1.3
The training of the pest-control personnel shall be documented in the Integrated Pest Management Plan.
|
|