|
|
|
Item No.:
10
|
|
Site:
Other-WADING POOL
|
|
Violation:
VERFIY THAT THE DRAIN COVER FOR THE WADING POOL IS ANTI-VORTEX.
|
|
Recommendation:
6.4.1.2.2
Anti-vortex drain covers shall be provided on swimming pools and whirlpool spas.
|
|
|
Item No.:
08
|
|
Site:
Other-UPPER DINING ROOM PANTRY
|
|
Violation:
A PRESSURE TYPE BACKFLOW PREVENTER WAS NOT PROVIDED ON WATER LINES TO THE COFFEE MACHINE.
|
|
Recommendation:
5.7.1.2.1
Backflow preventers shall be installed when air gaps are impractical or when water under pressure is required.
|
|
|
Item No.:
21
|
|
Site:
Other-UPPER DINING ROOM PANTRY
|
|
Violation:
THE WATER LINE TO THE COFFEE MACHINE WAS OF FLEXIBLE BRAIDED STAINLESS STEEL MATERIAL AND LEFT LYING ON THE COUNTER.
|
|
Recommendation:
7.4.2.1.2
Nonfood-contact surfaces of equipment and utensils shall be designed and constructed to be durable and to retain their characteristic qualities under normal use conditions. Piping should be kept off counters to allow for proper cleaning.
|
|
|
Item No.:
34
|
|
Site:
Other-MAIN GALLEY - POTWASHING AREA
|
|
Violation:
HOT WATER LINES FROM THE AUTOMATIC POT WASHER AND OTHER LINES IN THE POTWASHING AREA WERE LEAKING AND WATER WAS POOLING ON THE DECK.
|
|
Recommendation:
7.7.3.3.1
A plumbing system in a food area shall be maintained in good repair.
|
|
|
Item No.:
22
|
|
Site:
Other-MAIN GALLEY - DISHWASHING AREA
|
|
Violation:
THE PRESSURE GAUGE FOR THE DISHWASHER WAS NOT WORKING PROPERLY.
|
|
Recommendation:
7.5.2.1.2
Pressure measuring devices that display the pressures in the water supply line for the fresh hot water sanitizing rinse shall have increments of 7 kilopascals (1 pounds per square inch) or smaller and shall be accurate to ± 14 kilopascals (± 2 pounds per square inch) in the 100-170 kilopascals (15-25 pounds per square inch) range.
|
|
|
Item No.:
24
|
|
Site:
Other-MAIN GALLEY - GLASSWASHING AREA
|
|
Violation:
THE TEMPERATURE OF THE FINAL RINSE WAS INTERMITTANTLY OVER 200°F AND STEAM WAS COMING FROM THE FINAL RINSE DURING THESE TIMES.
|
|
Recommendation:
7.5.6.1.2
In a mechanical operation, the temperature of the fresh hot water sanitizing rinse as it enters the manifold may not be more than 90°C (194°F), or less than:
(1) For a stationary rack, single temperature machine, 74°C (165°F); or (2) For all other machines, 82°C (180°F). (3) A utensil surface temperature of 71°C (160°F) as measured by an irreversible registering temperature indicator shall be achieved. (4) The maximum temperature of 90°C (194°F), does not apply to the high pressure and temperature systems with wand-type, hand-held, spraying devices used for the in-place cleaning and sanitizing of equipment such as meat saws.
|
|
|
Item No.:
37
|
|
Site:
Other-CREW GALLEY
|
|
Violation:
CONDENSATION WAS BUILDING UP AND DRIPPING FROM THE HOOD SYSTEM ABOVE THE SOUP KETTLES.
|
|
Recommendation:
7.4.3.2.1
Ventilation hood systems and devices shall be sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
36
|
|
Site:
Other-FOOD SERVICE GENERAL - LIGHTING
|
|
Violation:
LIGHTING LEVELS IN SEVERAL AREAS WAS TOO LOW, FOR EXAMPLE:
- CREW MESS BUFFET LINE - 4 TO 11 FOOT CANDLES
- PETTY OFFICERS' MESS BUFFET LINE - 10 FOOT CANDLES
- VEGETABLE PREPARATION AT PULPER AREA - 7 TO 10 FOOT CANDLES
- OCEAN BAR AT SERVICE COUNTER - 8 TO 14 FOOT CANDLES
- PETTY OFFICERS' BAR SERVICE COUNTER - 10 FOOT CANDLES
|
|
Recommendation:
7.7.5.1.1
The light intensity shall be at least 220 Lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
|
|
|
Item No.:
19
|
|
Site:
Other-PETTY OFFICERS' MESS
|
|
Violation:
A STAINLESS STEEL MILK JUG WAS BEING USED IN THE MILK DISPENSER INSTEAD OF THE SINGLE USE BOXES WITH BLADDERS AND THE INTERIOR OF THE CONTAINER WAS NOT CLEAN.
|
|
Recommendation:
7.3.3.2.1(3)
Food shall be protected from cross-contamination by:
(3) Cleaning and sanitizing equipment and utensils.
Always utilize appropriate dispensing boxes with bladders for milk dispensers.
|
|
|
Item No.:
21
|
|
Site:
Other-PETTY OFFICERS' BAR
|
|
Violation:
HOLES WERE NOTED BELOW THE BAR ALONG STAINLESS STEEL UP RIGHTS WHERE PIPING LINES ENTER.
|
|
Recommendation:
7.4.2.2.6
Nonfood-contact surfaces shall be free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Seal all such openings.
|
|
|
Item No.:
33
|
|
Site:
Other-DRY STORES
|
|
Violation:
GAPS EXISTS ALONG BULKHEAD DECK JUNCTURES AND WHERE SEALANT IS PEELING OUT OF BULKHEAD DECKHEAD JUNCTURES.
|
|
Recommendation:
7.7.4.1.1
Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be constructed and maintained for easy cleaning.
|
|
|
Item No.:
20
|
|
Site:
Other-CHILD ACTIVITY CENTER - SKY BAR
|
|
Violation:
THE REFRIGERATOR IN THE KITCHENETTE WAS NOT WORKING, AND DID NOT HAVE AN "OUT OF ORDER SIGN" POSTED.
|
|
Recommendation:
Provide " OUT OF ORDER SIGNS" forall food service equipment that is not in working order.
|
|
|
Item No.:
33
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
DECKING IN SEVERAL FOOD SERVICE AREAS HAD MISSING GROUTING AND CHIPPED FLOOR TILE.
|
|
Recommendation:
7.7.4.2.3
Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, shall be maintained in good repair.
|
|
|
Item No.:
*
|
|
Site:
Other-CORRECTIVE ACTION STATEMENT
|
|
Violation:
IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY.
PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO:
USE EMAIL MESSAGE SUBJECT LINE: SHIP NAME - CAS - [INSERT INSPECTION DATE] .
|
|
Recommendation:
|
|
|
Item No.:
*
|
|
Site:
Other-GENERAL COMMENTS
|
|
Violation:
THE ROTTERDAM WAS IN GOOD CONDITION AND THE SHIP'S CAPTAIN AND STAFF WERE VERY KNOWLEDGEABLE AND INVOLVED IN THE ONGOING SANITATION AND MAINTENANCE OF THE VESSEL. DOCUMENTATION WAS ALSO VERY GOOD.
|
|
Recommendation:
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICES ON THE INTERNATIONAL SHORE CONNECTIONS USED FOR THE FIRE SUPRESSION SYSTEM HAVE NOT BEEN TESTED.
THE POTABLE WATER LINES IN THE ENGINE WORK SHOP, GARBAGE ROOM, LAUNDRY ROOM, LIDO POOL ROOM, AND THE POTABLE WATER LINE DIAGONALLY ACROSS FROM FIRE STATION C.05 IN THE ENGINE ROOM HAVE NOT BEEN STRIPED BLUE AS REQUIRED.
BACKFLOW PREVENTION DEVICES WERE NOT PROVIDED AT THE HOSE CONNECTIONS IN THE ENGINE WORK SHOP, AND DIAGONALLY ACROSS FROM FIRE STATION C.05 IN THE ENGINE ROOM.
|
|
Recommendation:
5.7.2.2.2
Backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, shall be inspected and tested with a test kit at least annually. Test results showing the pressure differences on both sides of the valves shall be maintained for each device.
5.7.2.2.3
The inspection and test results for backflow preventers shall be retained for at least 12 months and shall be available to the VSP for review during inspections.
5.3.2.1.1
Potable water piping shall be painted light blue or striped with 15 cm (6 inches) light blue bands or a light blue stripe at fittings on each side of partitions, decks, and bulkheads and at intervals not to exceed 5 m (15 feet) in all spaces, except where the decor would be marred by such markings.
5.7.1.2.1
Backflow preventers shall be installed when air gaps are impractical or when water under pressure is required.
|
|
|
Item No.:
07
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
POTABLE WATER TANK 1 PS WAS DISINFECTED USING 6 PPM CHLORINE FOR 24 HOURS ON 05/27/02.
|
|
Recommendation:
5.3.4.1.4
Disinfection following potential contamination shall be accomplished by increasing free residual halogen to at least 50 mg/L (ppm) throughout the affected area and maintaining this concentration for 4 hours.
|
|
|
Item No.:
09
|
|
Site:
Other-WADING POOL
|
|
Violation:
THE BROMINE RESIDUAL FOR THE WADING POOL HAS NOT BEEN TESTED. THE WADING POOL IS UNDER THE SAME DISINFECTION AND FILTRATION SYSTEM AS THE LIDO POOL. RECORDS OF TESTING FOR HALOGEN RESIDUAL WERE AVAILABLE FOR THE LIDO POOL.
|
|
Recommendation:
6.2.2.1.1
A free residual halogen of >1.0 and <3.0 mg/L (ppm) shall be maintained in recirculated swimming pools.
6.1.1.2.3
No bathers shall be allowed to use the pool before a free residual halogen of 1.0 mg/L (ppm) is achieved.
|
|
|
Item No.:
41
|
|
Site:
Other-VENTILATION
|
|
Violation:
THE CONDENSATE COLLECTION PAN WAS NOT ACCESSIBLE AT UNIT AP 7.5.01.
|
|
Recommendation:
9.2.1.1.1
Air handling unit condensate drain pans and collection systems shall be accessible for inspection, maintenance, and cleaning.
|
|
|
Item No.:
02
|
|
Site:
Other-MEDICAL
|
|
Violation:
ON 06/23/02 A PASSENGER WAS DISPENSED LOPERAMIDE. THIS INDIVIDUAL WAS NOT LISTED IN THE STANDARDIZED GASTROINTESTINAL ILLNESS LOG.
|
|
Recommendation:
4.1.2.1.3
The log shall list:
(1) All reportable cases of gastrointestinal illness; (2) All passengers and crew members who are dispensed antidiarrheal medication from the master of the vessel, the medical staff, or other designated staff.
|
|
|
Item No.:
34
|
|
Site:
Other-HAMBURGER GRILL
|
|
Violation:
A LEAK WAS NOTED IN THE TECHNICAL SPACE UNDER THE STEAM TABLE.
|
|
Recommendation:
7.7.3.3.1
A plumbing system in a food area shall be maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Other-LIDO DISHWASH/GLASSWASH
|
|
Violation:
SLIGHT CORROSION WAS NOTED IN THE DECK SINK UNDER THE HANDWASH SINK.
|
|
Recommendation:
7.7.4.1.8
Surfaces subject to routine splashes, spillage or other soiling during normal use shall have easily cleanable features.
|
|
|
Item No.:
19
|
|
Site:
Other-LIDO BUFFET STARBOARD AND PORT
|
|
Violation:
THE BOWLS OF BROWN SUGAR AND RAISINS WERE NOT PLACED UNDER THE SNEEZE GUARD.
|
|
Recommendation:
7.3.3.6.1
Food on display shall be protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
16
|
|
Site:
Other-LIDO BUFFET
|
|
Violation:
ALTHOUGH TIME WAS BEING USED AS A CONTROL, AND A FOOD LOG WAS BEING MAINTAINED, A WRITTEN TIME CONTROL PLAN WAS NOT AVAILABLE AND SOME STAFF DID NOT UNDERSTAND THE SYSTEM. TEMPERATURES ON THE BUFFET WERE INADEQUATE FOR A SYSTEM WHERE TEMPERATURE IS USED AS THE CONTROL, FOR EXAMPLE;
- SOFT BOILED EGGS WERE TESTED AT 114°F, PORT SIDE
- CREAM OF WHEAT WAS TESTED AT 133°F, STARBOARD SIDE
- COTTAGE CHEESE (VERY SMALL AMOUNT) WAS TESTED AT 54°F, PORT SIDE
- PANCAKE MIX WAS TESTED AT 45°F, STARBOARD SIDE
|
|
Recommendation:
7.3.5.3.5
If time only, rather than time in conjunction with temperature, is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption:
(1) The food shall be marked or otherwise identified to indicate the time that is 4 hours past the point in time when the food is removed from temperature control; (2) The food shall be cooked and served, served if ready-to-eat, or discarded, within 4 hours from the time when the food is removed from temperature control; and (3) The food in unmarked containers or packages or marked to exceed a 4 hour limit shall be discarded.
7.3.5.3.6
Written procedures that ensure compliance with these guidelines shall be maintained on the vessel and made available to the VSP, upon request.
When temperature is used as the control, the following must be applied;
7.3.5.3.1.1
Potentially hazardous food shall be maintained:
(1) At 60°C (140°F) [roasts 54°C (130°F)] or above; or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
19
|
|
Site:
Other-LIDO BUFFET SERVICE
|
|
Violation:
A PAN OF FLOUR WAS NOT LABELED.
|
|
Recommendation:
7.3.3.2.3
Working containers holding food or food ingredients that are removed from their original packages for use on the vessel, such as cooking oils, flour, herbs, potato flakes, salt, spices, and sugar shall be identified with the common name of the food.
|
|
|
Item No.:
33
|
|
Site:
Other-LIDO STARBOARD BEVERAGE STATION
|
|
Violation:
THE DECK SINK WAS SOILED AND THE FINISH WAS PEELING.
|
|
Recommendation:
7.7.4.1.8
Surfaces subject to routine splashes, spillage or other soiling during normal use shall have easily cleanable features.
7.7.4.2.1
Decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, shall be cleaned as often as necessary.
|
|
|
Item No.:
16
|
|
Site:
Other-LIDO GALLEY
|
|
Violation:
SAUSAGE IN THE HOT CABINET ON THE PORT SIDE WAS TESTED AT 124°F.
|
|
Recommendation:
7.3.5.3.1.1
Potentially hazardous food shall be maintained:
(1) At 60°C (140°F) [roasts 54°C (130°F)] or above,; or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
21
|
|
Site:
Other-LIDO ICE MACHINE
|
|
Violation:
A POROUS GASKET WAS NOTED ON THE UPPER PANEL OF THE ICE MACHINE. THIS GASKET WAS WET AND PORTIONS OF IT CAME APART WHEN RUBBED.
|
|
Recommendation:
7.4.1.1.9
Nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning shall be constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
|
Item No.:
27
|
|
Site:
Other-LIDO ICE MACHINE
|
|
Violation:
SLIGHT MOLD GROWTH WAS NOTED ON THE NON-FOOD CONTACT SURFACES OF THE ICE MACHINE.
|
|
Recommendation:
7.5.5.1.3
Nonfood-contact surfaces of equipment shall be kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
33
|
|
Site:
Other-LIDO-ELEVATOR
|
|
Violation:
A SMALL SEAM WAS NOTED AROUND THE DECK PLATE. RESIDUAL SOFT SEALANT WAS NOTED ALONG A PORTION OF THIS SEAM.
|
|
Recommendation:
7.7.4.1.8
Surfaces subject to routine splashes, spillage or other soiling during normal use shall have easily cleanable features. If a sealant is used in this area it must dry to a hard durable finish.
|
|
|
Item No.:
33
|
|
Site:
Other-ICE CREAM PARLOR
|
|
Violation:
THE DECK SINK AND THE DECK AROUND IT WERE SOILED UNDER THE DIPPER WELL. A UTILITY LINE DRAPED THE DECK IN THIS AREA MAKING CLEANING DIFFICULT.
|
|
Recommendation:
7.7.4.2.1
Decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, shall be cleaned as often as necessary.
7.7.4.1.7
Exposed utility service lines and pipes, including lines for fire detection and protection systems, shall be installed so they do not obstruct or prevent cleaning.
|
|