Item No.:
06
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE ANALYZER CHARTS FOR THE DISTRIBUTION SYSTEM DID NOT HAVE A FREE HALOGENATION RANGE OF 0-5 PPM, A RECORDING RANGE OF 24 HOURS AND WERE NOT CHANGED DAILY. THIS IS A REPEAT VIOLATION FROM THE PREVIOUS INSPECTION.
|
|
Recommendation:
5.5.2.1.1
Halogen analyzer-chart recorder charts shall have a range of 0.0 to 5.0 mg/L (ppm) and have a recording period of 24 hours.
5.5.2.2.1
Halogen analyzer-chart recorder charts shall be changed, initialed, and dated daily. Charts shall contain notations of any unusual water events in the potable water system.
Recommend requesting a variance for the use of strip charts for the potable water distribution system.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE POTABLE WATER TANK CLEANING PROCEDURE DID NOT PROVIDE DETAILS ON THE TYPE OR CONCENTRATION OF HALOGENATION USED, HOW IT WAS APPLIED OR THE CONTACT TIME.
|
|
Recommendation:
5.3.4.1.2
Potable water tanks shall be inspected, cleaned, and disinfected during dry docks and wet docks, or every 2 years, whichever is less.
5.3.4.1.3
Documentation of the cleaning shall be maintained for 12 months and shall be available to the VSP for review during inspections.
5.3.4.1.6
The disinfected parts of the system shall be flushed with potable water until the free residual halogen is 5.00 mg/L (ppm).
|
|
|
Item No.:
10
|
|
Site:
Other-SPAS
|
|
Violation:
THE FREE CHLORINE RESIDUAL WAS NOT RAISED TO 10 PPM AND CIRCULATED FOR ONE HOUR AT THE END OF EACH DAY IN THE SPAS.
THE PH OF THE WHIRLPOOLS WERE NOT CONSISTENTLY MAINTAINED BETWEEN 7.2-7.8 PPM.
THE GRANULAR FILTERS WERE NOT INSPECTED MONTHLY FOR CRACKS, MOUNDS OR HOLES IN THE FILTER MEDIA. A MONTHLY SEDIMENTATION TEST WAS NOT DONE TO CHECK FOR EXCESSIVE ORGANIC MATTER.
DOCUMENTATION WAS NOT AVAILABLE STATING THAT THE SAND FILTER MEDIA IS CHANGED EVERY SIX MONTHS.
THE CHLORINE RESIDUAL WAS NOT TESTED HOURLY WHILE THE SPAS WERE OPEN FOR USE.
|
|
Recommendation:
6.3.2.1.1
The free residual halogen shall be increased to at least 10.0 mg/L (ppm) in whirlpool spas and circulated for at least 1 hour at the end of each day.
6.3.1.2.2
The whirlpool spa water shall be maintained with a Ph between 7.2 and 7.8.
6.3.1.1.5
The granular filters shall be opened at least monthly and examined for cracks, mounds, or holes in the filter media. A core sample of the filter media shall be inspected for excessive organic material accumulation using a recommended sedimentation method.
6.3.1.1.6
The granular filter media shall be replaced at least every 6 months. The filter housing shall be cleaned and sanitized before the new filter media is placed in it.
6.3.2.2.2
Residual halogen logs shall be maintained with residuals measured and recorded hourly during operation.
|
|
|
Item No.:
41
|
|
Site:
Other-VENTILATION
|
|
Violation:
THE AIR CONDITIONER CONDENSATE DRIP PAN WAS SOILED WITH A SLIMY FILM.
|
|
Recommendation:
9.2.1.2.1
Air handling units shall be kept clean.
|
|
|
Item No.:
37
|
|
Site:
Other-MAIN GALLEY - WAREWASH
|
|
Violation:
CONDENSATE WAS NOTED ON THE DECKHEAD ABOVE THE CLEAN SIDE OF THE WAREWASH MACHINE.
|
|
Recommendation:
7.4.3.2.1
Ventilation hood systems and devices shall be sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
36
|
|
Site:
Other-NEPTUNE BAR
|
|
Violation:
THE LIGHT BULB IN THE REFRIGERATION UNIT WAS NOT SHIELDED OR SHATTER-RESISTANT.
|
|
Recommendation:
7.7.5.2.1
Light bulbs shall be shielded, coated, or otherwise shatter-resistant in areas where there is exposed food; clean equipment, utensils, and linens; or unwrapped single-service, and single-use articles.
|
|
|
Item No.:
22
|
|
Site:
Other-DOLPHIN HALL BAR
|
|
Violation:
THE WAREWASH UNIT WAS MARKED "OUT OF ORDER".
|
|
Recommendation:
7.5.4.1.1
Warewashing equipment shall be maintained in good repair and proper adjustment including:
(1) Warewashing equipment shall be maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines. (2) Water pressure, and water temperature measuring devices shall be maintained in good repair and be accurate within the intended range of use.
|
|
|
Item No.:
21
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
EXCESSIVE SEALANT WAS NOTED ON THE NON-FOOD CONTACT SURFACE OF THE SALAMANDER UNIT.
|
|
Recommendation:
7.4.2.2.6
Nonfood-contact surfaces shall be free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
*
|
|
Site:
Other-CORRECTIVE ACTION STATEMENT
|
|
Violation:
IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY.
PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV
USE EMAIL MESSAGE SUBJECT LINE: SHIP NAME -NIPPON MARU-CAS - [INSPECTION DATE: 12/31/2003].
|
|
Recommendation:
|
|