Item No.:
03
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
FOR 9 DAYS SINCE THE LAST INSPECTION, SOME OF THE FREE CHLORINE RESIDUAL TESTS TAKEN FOR POTABLE WATER PRODUCTION SHOWED THAT WATER WAS NOT BEING PRODUCED AT 2.0 PPM.
|
|
Recommendation:
5.2.1.1.1
Potable water shall be continuously halogenated to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
FOR NUMEROUS DAYS SINCE THE LAST INSPECTION, MANUAL TESTS WERE NOT CONDUCTED EVERY FOUR HOURS DURING POTABLE WATER PRODUCTION.
|
|
Recommendation:
5.2.1.2.2
Free residual halogen monitoring shall be performed at least hourly during the bunkering of potable water and performed at least once every 4 hours during the onboard production of potable water.
|
|
|
Item No.:
03
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
ON 7/15, DURING POTABLE WATER BUNKERING THE TESTS TAKEN AT 9 AM, 10 AM, AND 11 AM WERE BELOW 2.0 PPM. NO CORRECTIVE ACTIONS WERE TAKEN.
|
|
Recommendation:
5.2.1.1.1
Potable water shall be continuously halogenated to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device.
|
|
|
Item No.:
05
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE ENGINEER'S TEST RESULT AT THE FAR POINT OF THE DISTRIBUTION SYSTEM WAS 2.99 PPM WHILE THE ANALYZER WAS READING 3.50 PPM, GIVING A DIFFERENCE OF 0.51 PPM. THE SECOND TEST RESULT WAS 3.17 PPM WHILE THE ANALYZER WAS READING 3.72 PPM, GIVING A DIFFERENCE OF 0.55 PPM.
|
|
Recommendation:
5.5.1.2.3
The free residual halogen measured by the halogen analyzer shall be ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
|
|
|
Item No.:
06
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE HALOGEN ANALYZER-CHART RECORDER CHARTS FOR THE DISTRIBUTION SYSTEM HAD A RANGE OF 0-50 PPM. THIS WAS NOTED ON THE LAST INSPECTION.
|
|
Recommendation:
5.5.2.1.1
Halogen analyzer-chart recorder charts shall have a range of 0.0 to 5.0 mg/L (ppm) and have a recording period of 24 hours.
|
|
|
Item No.:
26
|
|
Site:
Other-LEDA LOUNGE PANTRY
|
|
Violation:
ONE BOWL AND ONE SAUCER WERE SOILED AND STORED AS CLEAN.
|
|
Recommendation:
7.5.5.1.1
Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
|
|
|
Item No.:
28
|
|
Site:
Other-LEDA LOUNGE PANTRY
|
|
Violation:
CURTAINS WERE STORED ON TOP OF A RACK OF CLEAN GLASSES.
|
|
Recommendation:
7.5.7.3.1
Cleaned equipment and utensils, laundered linens, and single-service and single-use articles shall be stored:
(1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and
(3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
18
|
|
Site:
Other-LEDA LOUNGE PANTRY
|
|
Violation:
A CUP OF CREAM WAS STORED UNCOVERED IN THE REFRIGERATOR.
|
|
Recommendation:
7.3.3.2.1.1
Food shall be protected from cross-contamination by: (4) Storing the food in packages, covered containers, or wrappings.
|
|
|
Item No.:
26
|
|
Site:
Other-GALLEY
|
|
Violation:
ONE KNIFE AND ONE MIXER BLADE WERE SOILED AND STORED AS CLEAN IN THE VEGETABLE PREPARATION AREA.
ONE PAN WAS SOILED AND STORED AS CLEAN IN THE POTWASH AREA.
|
|
Recommendation:
7.5.5.1.1
Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
|
|
|
Item No.:
21
|
|
Site:
Other-PROVISIONS
|
|
Violation:
CRATES WERE USED AS DECK STANDS IN THE DRY STORES AREA. NEW DECK STANDS ARE ON ORDER.
|
|
Recommendation:
7.4.1.1.9
Nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning shall be constructed of a corrosion-resistant, nonabsorbent, and smooth material.
7.4.2.2.6
Nonfood-contact surfaces shall be free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
31
|
|
Site:
Other-MESS ROOM
|
|
Violation:
ONE UNLABELED BOTTLE OF MULTI-PURPOSE CLEANER WAS NOTED IN THE DISHWASH AREA.
|
|
Recommendation:
7.6.1.1.2
Working containers used for storing poisonous or toxic materials such as cleaners and sanitizers taken from bulk supplies shall be clearly and individually identified with the common name of the material.
|
|
|
Item No.:
19
|
|
Site:
Other-MESS ROOM
|
|
Violation:
BREAD PLACED OUT FOR SERVICE WAS NOT PLACED UNDER A SNEEZE GUARD.
|
|
Recommendation:
7.3.3.6.1
Food on display shall be protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
01
|
|
Site:
Other-MEDICAL
|
|
Violation:
A 24-HOUR PRIOR TO ARRIVAL GASTROINTESTINAL ILLNESS REPORT WAS NOT MADE BEFORE THE VESSEL ARRIVED IN SAULT STE. MARIE FROM CANADA.
THERE WAS NO EVIDENCE TO SHOW THAT THE SHIP HAD BEEN MAKING ANY REPORTS BEFORE ARRIVING IN A U.S. PORT FROM A FOREIGN PORT. THIS WAS NOTED ON THE LAST INSPECTION.
INSTRUCTIONS WERE LEFT WITH THE VESSEL ON HOW AND WHEN TO REPORT, INCLUDING E-MAIL ADDRESSES, FAX AND PHONE NUMBERS.
|
|
Recommendation:
4.2.1.1.1
The master, the medical staff, or other designated staff of a vessel destined for a U.S. port from a foreign port shall submit at least one standardized gastrointestinal illness report based on the number of reportable cases in the gastrointestinal illness log to the VSP no less than 24 hours, but not more than 30 hours before the vessel's expected arrival at the U.S. port.
4.2.1.1.2
If the number of cases changes after submission of the initial report, an updated report shall be submitted no less than 4 hours before the vessel's arrival at the U.S. port.
4.2.1.2.1
The gastrointestinal illness report shall contain:
(1) The name of the vessel; (2) The ports of embarkation and disembarkation; (3) The dates of embarkation and disembarkation; (4) The total numbers of reportable cases of gastrointestinal illness among passengers and crew members, including those who have been disembarked or removed because of illness, even if the number is 0; and (5) The total number of passengers and crew members on the cruise.
|
|
|
Item No.:
*
|
|
Site:
Other-CORRECTIVE ACTION STATEMENT
|
|
Violation:
IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY.
PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV
USE EMAIL MESSAGE SUBJECT LINE: ORION - CAS - 9/10/2004.
|
|
Recommendation:
|
|