Cruise Ship: Silver Whisper Cruise Line: Silversea Inspection Date: 03/16/2003 Inspection Score: 92
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 08
Site: Other-POTABLE WATER BUNKERING
Violation: THE POTABLE WATER FILLING HOSE CAP WAS LAYING ON A WOODEN HOSE SUPPORT ON THE DECK. THE BUNKERING HOSES WERE CLAMPED TO THE CONNECTION FITTINGS WITH A HOSE CLAMP. THE HOSE FITTINGS WERE STORED IN THE BUNKERING CABINET WITH ALUMINUM FOIL WRAPPED AROUND THE FITTINGS INCLUDING THE END OF THE HOSES.
Recommendation: 5.3.2.1.4 The potable water filling line shall have a screw cap or plug fastened by a non-corroding chain to an adjacent bulkhead or surface in such a manner that the cap or plug shall not touch the deck when hanging free.
Item No.: 05
Site: Other-POTABLE WATER DISTRIBUTION
Violation: THE MANUAL LOG CHLORINE RESIDUE RECORDED LESS THAN .63 PPM AND THE ANALYZER CHART RECORDED 4.25 PPM CHLORINE. DOCUMENTATION OF THE DIFFERENT CONCENTRATIONS WERE NOT RECORDED ON THE CHART OR THE MANUAL LOG.
Recommendation: 5.5.1.2.3 The free residual halogen measured by the halogen analyzer shall be ±0.2 mg/L (ppm) of the free residual halogen measured by the manual test.
Item No.: 34
Site: Other-PLUMBING
Violation: THE WATER FILTER CONTAINER WAS BROKEN AND REPAIRED WITH A FIBERGLASS EPOXY. THE FILTER MATERIAL APPEARED RUSTY AND NEEDED TO BE REPLACED.
Recommendation: 7.7.3.3.1 A plumbing system in a food area shall be maintained in good repair.
Item No.: 10
Site: Other-SPAS
Violation: THE ANTI-VORTEX DRAIN COVERS FOR BOTH SPAS COULD NOT BE LOCATED. APPARENTLY WHEN THE SPAS ARE CLEANED THE DRAIN COVERS ARE REMOVED.
Recommendation: 6.4.1.2.2 Anti-vortex drain covers shall be provided on swimming pools and whirlpool spas.
Item No.: 10
Site: Other-SPAS/POOLS
Violation: DOCUMENTATION OF CHILDREN IN DIAPERS OR NOT TOILET TRAINED NOT ALLOWED IN THE POOLS OR SPAS WAS NOT AVAILABLE.
Recommendation: 6.4.1.3.1 Children in diapers or who are not toilet trained are not permitted in the public swimming pools and whirlpool spas.
Item No.: 19
Site: Other-PROVISIONS - MEAT AND VEGETABLE ROOMS
Violation: THERE WAS A CONTAINER OF OPEN CHERRIES IN THE WALK-IN FREEZER AND THERE WAS ANOTHER BOX OF HAM THAT WASN'T SEALED PROPERLY.
Recommendation: 7.3.3.2.1(4) Food shall be protected from cross-contamination by: (4) Storing the food in packages, covered containers, or wrappings.
Item No.: 15
Site: Other-PROVISIONS - DRY STORES
Violation: THERE WAS ONE CAN WITH A SEVERE DENT IN THE SIDE.
Recommendation: 7.3.2.2.5 Food packages shall be in good condition and protect the integrity of the contents so that the food is not exposed to adulteration or potential contaminants. Canned goods with dents on end or side seams may not be used.
Item No.: 20
Site: Other-BUTCHER SHOP
Violation: THE CUTTING BOARDS WERE SEVERELY PITTED AND SCORED.
Recommendation: 7.4.5.1.3 Surfaces such as cutting blocks and boards that are subject to scratching and scoring shall be resurfaced if they no longer can be effectively cleaned and sanitized, or discarded if they are not capable of being resurfaced.
Item No.: 38
Site: Other-VEGETABLE PREPARATION ROOM
Violation: THE POTATO PEELER HAS BEEN MARKED "OUT OF ORDER" FOR SIX MONTHS.
Recommendation: 7.7.7.1.1 Only articles necessary for the food service operation shall be stored in food preparation, food storage, and warewashing areas.
Item No.: 38
Site: Other-MAIN GALLEY - BAKERY
Violation: THE PROOFER HAS BEEN MARKED "OUT OF ORDER".
Recommendation: 7.7.7.1.1 Only articles necessary for the food service operation shall be stored in food preparation, food storage, and warewashing areas.
Item No.: 33
Site: Other-MAIN GALLEY - BREAKFAST STATION
Violation: THERE WAS A LOT OF BREAD CRUMBS UNDERNEATH THE SLICER.
Recommendation: 7.7.4.2.1 Decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, shall be cleaned as often as necessary.
Item No.: 16
Site: Other-CREW MESS - BUFFET LINE
Violation: THE RICE IN THE HOT HOLD UNIT HAD AN INTERNAL TEMPERATURE OF 115°F. THERE WERE MANY PANS OF RICE IN THIS HOT HOLD UNIT.
Recommendation: 7.3.5.3.1.1 Potentially hazardous food shall be maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above,; or (2) At 5°C (41°F) or less.
Item No.: 21
Site: Other-CREW MESS - BUFFET LINE
Violation: THERE WAS NO AMBIENT TEMPERATURE MEASURING DEVICE IN THE HOT HOLD UNIT.
Recommendation: 7.4.2.4.9.2 Temperature measuring devices shall conform to the following guidelines: (2) Cold or hot holding equipment used for potentially hazardous food shall be designed to include and shall be equipped with at least one integral or affixed temperature measuring device that is located to allow easy viewing of the device's temperature display.
Item No.: 21
Site: Other-MAIN GALLEY - HOT GALLEY
Violation: THE NON-FOOD CONTACT AREA UNDERNEATH THE MIXING COLLAR WAS VERY CORRODED.
Recommendation: 7.4.1.1.9 Nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning shall be constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 36
Site: Other-MAIN GALLEY - HOT LINE
Violation: THE FACES OF THE BULBS EXTENDED BEYOND THE METAL SLEEVES OF THE HEAT LAMPS.
Recommendation: 7.7.5.2.2 An infrared or other heat lamp shall be protected against breakage by a shield surrounding and extending beyond the bulb so that only the face of the bulb is exposed.
Item No.: 28
Site: Other-MAIN GALLEY - POTWASH
Violation: FRYING PANS WERE NOTED HANGING IN DIRECT CONTACT WITH THE BULKHEAD. PANS WERE ALSO VERY CLOSE TO THE WALL MOUNTED DETERGENT DISPENSER AND POSSIBLEY SUBJECT TO SPLASH.
Recommendation: 7.5.7.3.1 Cleaned equipment and utensils, laundered linens, and single-service and single-use articles shall be stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Other-MAIN GALLEY - ICE CREAM STATION
Violation: THE ICE CREAM DISPENSING UTENSIL WELL OVERDRAIN WAS NOT FUNCTIONING PROPERLY.
Recommendation: 7.3.3.4.2.4 During pauses in food preparation or dispensing, food preparation and dispensing utensils shall be stored: (4) In running water of sufficient velocity to flush particulates to the drain, if used with moist food such as ice cream or mashed potatoes.
Item No.: 22
Site: Other-POT WASH GENERAL
Violation: THE WALL MOUNTED TEMPERATURE GAUGE FOR THE FINAL RINSE COMPARTMENTS WERE NOT ACCURATE.
Recommendation: 7.5.4.1.1 Warewashing equipment shall be maintained in good repair and proper adjustment including: (1) Warewashing equipment shall be maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines. (2) Water pressure, and water temperature measuring devices shall be maintained in good repair and be accurate within the intended range of use.
Item No.: 33
Site: Other-FOOD SERVICE GENERAL
Violation: THE DEEP FLOOR SCUPPERS IN FRONT OF THE SOUP KETTLES WERE CORRODED.
Recommendation: 7.7.4.1.5 Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be corrosion-resistant.
Item No.: 13
Site: Other-MAIN GALLEY - HOT GALLEY
Violation: KITCHEN STAFF WERE OBSERVED USING A WIPING RAG, WHICH THEY KEPT AT THERE WAIST FOR WIPING THEIR HANDS.
Recommendation: 7.2.1.2.1.4 The person in charge of the food operations on the vessel shall ensure that: (4) Food employees are effectively cleaning their hands, by routinely monitoring the employees' handwashing.
Item No.: 06
Site: Other-POTABLE WATER
Violation: THE BACKUP CHLORINE PUMP WAS NOT INSTALLED TO ACTIVATE AUTOMATICALLY IN THE EVENT OF THE CHLORINE PUMP FAILURE ON THE POTABLE WATER DISTRIBUTION SYSTEM.
Recommendation: 5.4.1.2.3 At least one backup halogen pump shall be available with automatic switchover to maintain the free residual halogen in the event that the primary pump fails.
Item No.: *
Site: Other-CORRECTIVE ACTION STATEMENT
Violation: IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY. PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV USE EMAIL MESSAGE SUBJECT LINE: SILVER WHISPER - CAS - [INSERT INSPECTION DATE: 03/16/2003] .
Recommendation:
Item No.: 19
Site: Other-TERRACE CAFÉ
Violation: THE ROLLS WERE NOT STORED BENEATH THE SNEEZE GUARD ON THE BUFFET.
Recommendation: 7.3.3.6.1 Food on display shall be protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
Item No.: 18
Site: Other-TERRACE CAFÉ WALK IN REFRIGERATOR
Violation: HAM WAS STORED ABOVE PRE-COOKED HASHBROWN POTATOES IN THE WALK-IN COOLER.
Recommendation: 7.3.3.2.1.1 Food shall be protected from cross-contamination by: (1) Physically separating raw animal foods during storage, preparation, holding, and display from raw ready-to-eat food including other raw animal food such as fish for sushi or molluscan shellfish, or other raw ready-to-eat food such as vegetables, and cooked ready-to-eat food; so products do not physically touch, and so as to prevent dripping of one product into another.
Item No.: 33
Site: Other-PANORAMA BAR
Violation: BLACK MOLD WAS NOTED ON THE CAULK IN THE FLOOR SINK'S TECHNICAL AREA BENEATH THE COUNTER.
Recommendation: 7.7.4.2.1 Decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, shall be cleaned as often as necessary.
Item No.: 33
Site: Other-POOL BAR
Violation: HOSES WERE NOTED ON THE DECK BEHIND THE DISHWASH MACHINE MAKING THIS AREA HARD TO CLEAN.
Recommendation: 7.7.4.1.7 Exposed utility service lines and pipes, including lines for fire detection and protection systems, shall be installed so they do not obstruct or prevent cleaning.
Item No.: 41
Site: Other-VENTILATION
Violation: THE CONDENSATE COLLECTION PANS WERE NOT ACCESSIBLE FOR INSPECTION DURING THIS SURVEY. AN ACCESS PANEL BEHIND PIPING MAY PROVIDE ACCESS TO THE CONDENSATE PAN BUT THIS WOULD REQUIRE TAKING OUT A SECTION OF THE VENTILATION CABINET. CLEANING RECORDS WERE NOT AVAILABLE. THIS WAS NOTED ON THE PREVIOUS INSPECTION.
Recommendation:
Item No.: *
Site: Other-COMMENT
Violation: PINK, BLACK AND WHITE MOLDS WERE GROWING PROFUSELY WITHIN THE VENTILATION PIPE INSULATION PILLOWS.
Recommendation: RECOMMEND THAT THE MOLD GROWTH BE REMOVED AND ACTIONS TAKEN TO PREVENT FUTURE MOISTURE PROBLEMS.
Item No.: 40
Site: Other-INTEGRATED PEST MANAGEMENT
Violation: THE PESTICIDE APPLICATERS WERE NOT TRAINED AND DOCUMENTATION WAS NOT PROVIDED IN THE INTEGRATED PEST MANAGEMENT PLAN. NIGHT INSPECTIONS FOR VERMIN WERE BEING CONDUCTED BUT THE TIMES WERE NOT DOCUMENTED IN THE PEST SIGHTING LOGS.
Recommendation: 8.1.1.2.2 Reviews shall be documented and changes noted in the vessel's Integrated Pest Management Plan. 8.1.2.1.3 The training of the pest-control personnel shall be documented in the Integrated Pest Management Plan.
Item No.: 08
Site: Other-POTABLE WATER BUNKERING
Violation: THERE WERE TEN DATES FROM THE MONTH OF NOVEMBER WHERE HOURLY CHLORINE RESIDUES WERE NOT TAKEN DURING BUNKERING. SOME DAYS HAD EIGHT TIMES WHERE THE HOURLY TESTS WERE MISSED.
Recommendation: 5.2.1.2.2 Free residual halogen monitoring shall be performed at least hourly during the bunkering of potable water and performed at least once every 4 hours during the onboard production of potable water. 5.2.1.2.3 Accurate records of this monitoring shall be maintained aboard for 12 months and shall be available to the VSP for review during inspections.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program