Item No.:
4
|
|
Site:
Other-MAIN GALLEY / DISHWASHING AREA
|
|
Violation:
THERE WAS A NON-CONTINUOUS PRESSURE TYPE BACKFLOW PREVENTER (WATTS 8S TYPE) ON ONE OF THE SPRAY HOSES.
|
|
Recommendation:
Replace this backflow preventer with a continuous pressure type backflow preventer (Watts N9 type).
|
|
|
Item No.:
38
|
|
Site:
Other-CREW MESS
|
|
Violation:
THERE WAS WATER UNDER THE DECK TILES BY THE HANDWASHING SINK. WHEN YOU WALKED IN THIS AREA WATER CAME UP BETWEEN THE TILE.
|
|
Recommendation:
It is required that decks be maintained so as to be durable and easily cleanable.
|
|
|
Item No.:
21
|
|
Site:
Other-FOOD SERVICE - GENERAL
|
|
Violation:
THE AREAS SURROUNDING THE GRILL GREASE PANS ARE DIFFICULT TO CLEAN BECAUSE OF EXPOSED INSULATION, GAPS AND SEAMS.
|
|
Recommendation:
Surfaces of equipment not intended for contact with food, but which are exposed to splash or food debris or which otherwise require frequent cleaning, shall be designed and fabricated to be smooth, washable, free of unnecessary ledges, projections, or crevices, and readily accessible for cleaning, and shall be of such material and in such repair as to be easily maintained in a clean and sanitary condition.
|
|
|
Item No.:
38
|
|
Site:
Other-FOOD SERVICE - GENERAL
|
|
Violation:
THE DECKS IN GALLEY AREAS AND PROVISIONS HAD DIFFICULT TO CLEAN FEATURES SUCH AS ROUGH TEXTURED CONCRETE, MISSING OR CRACKED DECK TILES AND RECESSED GROUTING.
|
|
Recommendation:
It is required that decks be maintained so as to be durable and easily cleanable.
|
|
|
Item No.:
3
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
THE ANALYZER/RECORDER WAS OUT OF CALIBRATION WITH THE DIGITAL TEST KIT OF THE INSPECTOR. THE ANALYZER WAS READING 1.4 PPM AND THE MANUAL TEST WAS GREATER THAN 2.20 PPM FREE CHLORINE. THE SHIP'S TEST KIT IS GRADUATED IN 0.5 INCREMENTS ABOVE 1.0 PPM. THE CHIEF ENGINEER PROVIDED A PURCHASE REQUEST TO THE INSPECTOR FROM MARCH 9, 2000 FOR A DIGITAL TEST KIT BUT HE HAS NOT BEEN SUCCESSFUL IN RECEIVING THIS UNIT.
|
|
Recommendation:
The ship must have a chlorine or bromine analyzer-recorder, which must be installed at a distant point in the potable water distribution system where a significant water flow exists. The free halogen residual measured by the analyzer must compare within 0.2 ppm of the actual halogen level.
|
|