Cruise Ship: Nippon Maru Cruise Line: Mitsui O.S.K. Passenger Line, Ltd Inspection Date: 12/31/2000 Inspection Score: 99
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 37
Site: Other-MAIN GALLEY
Violation: CONDENSATION WAS NOTED ON THE DECKHEAD ABOVE THE DISHWASHERS.
Recommendation: Ventilation hood systems and devices shall be sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 22
Site: Other-MAIN GALLEY
Violation: THE PRESSURE GAUGE ON THE DISHWASHER HAD REGISTERED A READING ABOVE 25 POUNDS PER SQUARE INCH ON THE FINAL RINSE.
Recommendation: Pressure measuring devices that display the pressures in the water supply line for the fresh hot water sanitizing rinse shall have increments of 7 kilopascals (1 pounds per square inch) or smaller and shall be accurate to ± 14 kilopascals (± 2 pounds per square inch) in the 100-170 kilopascals (15-25 pounds per square inch) range.
Item No.: 22
Site: Other-MAIN GALLEY
Violation: SPONGES WERE USED IN THE SANITIZING BUCKET OF THE 3 BUCKET CLEANING SYSTEM.
Recommendation: Sponges may not be used in contact with cleaned and sanitized or in-use food-contact surfaces. Only clean cloths shall be used in the sanitizing bucket of the 3 bucket cleaning system.
Item No.: 26
Site: Other-MAIN GALLEY
Violation: COMMERCIAL TYPE FOOD BLENDERS WERE NOT BEING DISASSEMBLED FOR CLEANING AROUND THE GASKET BASE.
Recommendation: Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
Item No.: 19
Site: Other-PROVISIONS
Violation: WATER BOTTLES WERE BEING REUSED TO STORE TERIYAKI SAUCE.
Recommendation: Working containers holding food or food ingredients that are removed from their original packages for use on the vessel, such as cooking oils, flour, herbs, potato flakes, salt, spices, and sugar shall be identified with the common name of the food. Containers must be constructed of materials that permit washing, rinsing, and sanitizing after each use.
Item No.: 33
Site: Other-PROVISIONS
Violation: THERE WAS EXPOSED WIRING AND COILS ALONG BULKHEADS AND DECKHEADS IN THE COLD STORE PROVISION ROOMS.
Recommendation: Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be constructed and maintained for easy cleaning.
Item No.: 33
Site: Other-CREW MESS AND PROVISION AREA
Violation: THERE WAS SOME DAMAGE TO THE DECK IN THE CREW MESS AND PROVISION ROOMS.
Recommendation: Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be constructed and maintained for easy cleaning.
Item No.: *
Site: Other-GENERAL REMARKS #1
Violation: THIS SHIP IS AN EXCELLENT EXAMPLE OF THE COOPERATION BETWEEN THE SHIP OWNERS AND THE U.S.P.H.S., RESULTING IN AN OUTSTANDING LEVEL OF COMPLIANCE WITH PUBLIC HEALTH REQUIREMENTS. BOTH THE FACILITIES AND CREW/MANAGEMENT KNOWLEDGE OF PUBLIC HEALTH ARE EXCELLENT AND THE MITSUI O.S.K. LINES AND THEIR MANAGEMENT STAFF ARE HIGHLY COMMENDED FOR THE DRAMATIC IMPROVEMENTS THEY HAVE MADE.
Recommendation:
Item No.: *
Site: Other-GENERAL REMARKS #2
Violation: TO CONTINUE THIS EXCELLENCE WE RECOMMEND THAT THE CHIEF PURSER AND OTHER MANAGEMENT STAFF ATTEND THE U.S.P.H.S., TRAINING COURSE ON OUR NEW OPERATIONS MANUAL IN MIAMI, FLORIDA.
Recommendation:
Item No.: 06
Site: Other-POTABLE WATER
Violation: THE VESSEL DID NOT HAVE A COPY OF THE MOST RECENT MICROBIOLOGICAL REPORT FROM PORTS WHERE WATER IS BUNKERED. THE TEST WAS ALSO NOT PERFORMED BY THE ALTERNATIVE METHOD OF TESTING ON BOARD THE VESSEL.
Recommendation: Where available, the vessel shall have a copy of the most recent microbiologic report from each port before bunkering potable water to verify that the water meets potable standards. These records shall be maintained on the vessel for 12 months and shall be available to the VSP for review during inspections. If tests are performed on board the vessel analysis shall be consistent with a method accepted in Standard Methods for the Examination of Water and Wastewater.
Item No.: 06
Site: Other-POTABLE WATER
Violation: HOURLY FREE RESIDUAL HALOGEN TESTS WERE NOT PERFORMED DURING BUNKERING OPERATIONS.
Recommendation: During bunkering operations hourly free halogen monitoring tests shall be performed on board the vessel. When the vessel produces water the free residual halogen tests shall be conducted every 4 hours.
Item No.: 06
Site: Other-POTABLE WATER DISTRIBUTION SYSTEM
Violation: THE HALOGEN ANALYZER CHART RECORDER CHARTS WERE NOT INITIALED AND DATED DAILY. CHARTS WERE NOT PROPERLY ANNOTATED BETWEEN 7/15/2000 AND 7/19/2000 PLUS FROM 12/07/2000 AND 12/14/2000.
Recommendation: Halogen analyzer-chart recorder charts shall have a range of 0.0 to 5.0 mg/L (PPM) and have a recording period of 24 hours. Halogen analyzer-chart recorder charts shall be changed, initialed, and dated daily. Charts shall contain notations of any unusual water events in the potable water system. The calibration shall be recorded on the chart or in a log book.
Item No.: 10
Site: Other-SWIMMING POOL AND SPA
Violation: THE SAFETY AND PUBLIC HEALTH REQUIREMENTS OUTLINED IN CHAPTER 6 OF THE VS. OPERATIONS MANUAL WERE NOT IMPLEMENTED ON THIS VESSEL.
Recommendation: A fecal accident response procedure shall be documented and available for review during inspections. Safety signs shall be provided for public swimming pools and whirlpool spas. Depth markers shall be installed for every 1 m (3 feet) in change of depth and shall be displayed prominently so they can be seen from the deck and from in the pool. Easy access shepherd's hook and approved floatation device shall be provided at a prominent location near each public swimming pool. Anti-vortex drain covers shall be provided on swimming pools and whirlpool spas.
Item No.: 41
Site: Other-VENTILATION SYSTEM
Violation: THERE WAS NOT A PLAN FOR THE ROUTINE INSPECTION OF THE AIR HANDLING SYSTEMS ABOARD THE VESSEL.
Recommendation: Vessels shall have a plan to inspect and maintain heating, ventilation, and air conditioning systems in accordance with manufactures recommendations and industry standards.
Item No.: 41
Site: Other-HOUSEKEEPING
Violation: THE VESSEL DID NOT CLEAN AND DISINFECT SHOWER HEADS EVERY 6 MONTHS.
Recommendation: The potable hot-water system including shower heads shall be maintained to preclude growth of Mycobacterium legionella. Shower heads shall be cleaned and disinfected every 6 months to preclude growth of Mycobacterium legionella.
Item No.: 02
Site: Other-MEDICAL DEPARTMENT
Violation: THE MEDICAL STAFF WERE NOT USING THE APPROPRIATE LOGS TO RECORD GASTROINTESTINAL ILLNESSES, DISPENSING OF ANTIDIARRHEAL MEDICATIONS AND USE OF DIARRHEAL QUESTIONNAIRES.
Recommendation: A standardized gastrointestinal illness surveillance log for each cruise shall be maintained daily by the master of the vessel, the medical staff, or other designated staff. The gastrointestinal illness surveillance log shall list the name of the vessel, the cruise dates and the cruise number. The log shall list: (1) All reportable cases of gastrointestinal illness; (2) All passengers and crew members who are dispensed antidiarrheal medication from the master of the vessel, the medical staff, or other designated staff. A separate inventory of the daily total, by quantity and type, of antidiarrheal medications sold or dispensed to the passengers or crew members in all areas of the vessel shall be maintained alongside the gastrointestinal illness surveillance log. Questionnaires detailing activities and meal locations for the 72 hours before illness onset shall be available and distributed to all passengers and crew members who are gastrointestinal illness cases. The self-administered questionnaires shall contain all of the data elements that appear in the questionnaire found in Annex 13.2. The completed questionnaires shall be maintained alongside the gastrointestinal illness surveillance log.
*Inspections scores of 85 or lower are NOT satisfactory