Cruise Ship: Europa Cruise Line: Hapag-Lloyd Cruises Inspection Date: 06/28/2003 Inspection Score: 97
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 29
Site: Other-MAIN GALLEY-COLD GALLEY
Violation: THE HANDWASH SINK WAS PARTIALLY BLOCKED BY THE THREE BUCKET CLEANING TROLLEY. ENSURE ALL HANDWASH SINKS ARE FULLY ACCESSIBLE AT ALL TIMES.
Recommendation: 7.7.1.3.1 Handwashing facilities shall be used for no other purpose and shall be accessible at all times.
Item No.: 21
Site: Other-MAIN GALLEY - FOOD SERVICE GENERAL
Violation: THE VENTILATION HOODS HAD BROKEN PROFILES EXPOSING SEAMS THAT MADE CLEANING DIFFICULT.
Recommendation: 7.4.2.2.6 Nonfood-contact surfaces shall be free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 27
Site: Other-MAIN GALLEY- WAREWASH
Violation: ONE GLASS STORAGE RACK WAS SOILED WITH FOOD RESIDUE.
Recommendation: 7.5.5.1.3 Nonfood-contact surfaces of equipment shall be kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 37
Site: Other-MAIN GALLEY - WAREWASH
Violation: HEAVY CONDENSATION WAS NOTED ON THE DECKHEAD AND THE TEMPERATURE IN THE AREA WAS VERY HOT.
Recommendation: 7.4.2.4.1 Exhaust ventilation hood systems in food preparation and warewashing areas including components such as hoods, fans, guards, and ducting shall be designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
Item No.: 28
Site: Other-MESS AREA
Violation: A STACK OF COFFEE CUPS WERE STORED IN RACKS ON A PALLET LESS THAN (6 INCHES) ABOVE THE DECK.
Recommendation: 7.5.7.3.1 Cleaned equipment and utensils, laundered linens, and single-service and single-use articles shall be stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
Item No.: *
Site: Other-HOUSEKEEPING
Violation: THE OVERALL HOUSEKEEPING PROGRAM WAS VERY COMPREHENSIVE AND COULD BE USED AS A MODEL FOR OTHER COMPANY VESSELS.
Recommendation:
Item No.: 08
Site: Other-POTABLE WATER
Violation: THE PRESSURE DIFFERENTIALS WERE NOT RECORDED FOR THE REDUCED PRESSURE DEVICES ON THE FIRE SYSTEM INTERNATIONAL SHORE CONNECTIONS. APPROPRIATE BACKFLOW PREVENTION DEVICES WERE NOT INSTALLED ON THE POTABLE LINES SUPPLYING THE SINKS IN THE BEAUTY PARLOR. THIS WAS CORRECTED DURING THE INSPECTION.
Recommendation: Ensure the pressure differentials are recorded for the reduce pressure devices on the international shore connections fire system.
Item No.: 07
Site: Other-POTABLE WATER
Violation: THE RECORD OF DISINFECTION OF THE POTABLE WATER TANKS WAS NOT ADEQUATE.
Recommendation: 5.3.4.1.4 Disinfection following potential contamination shall be accomplished by increasing free residual halogen to at least 50 mg/L (ppm) throughout the affected area and maintaining this concentration for 4 hours.
Item No.: 41
Site: Other-VENTILATION
Violation: THE CONDENSATE COLLECTION SYSTEM AND DRAIN PAN WERE NOT ACCESSIBLE FOR INSPECTION.
Recommendation: 9.2.1.2.2 Evaporative condensers shall be inspected at least annually and cleaned as necessary to remove scale and sediment. Cooling coils and condensate pans shall be cleaned as necessary to remove dirt and organic material.
Item No.: 10
Site: Other-POOL
Violation: THE POOL WAS TESTED EVERY 4-HOUR SHIFT. THE TIME OF THE TEST WAS NOT RECORDED. GIVEN THIS METHOD OF TESTING IT WAS POSSIBLE TO EXCEED FOUR HOURS BETWEEN TESTS. THE SHEPHERD'S HOOK DID NOT HAVE A RIGID METAL HOOK ON THE END BUT A FLEXIBLE HOSE.
Recommendation: Ensure the time of testing for the pools is recorded and a rigid metal hook for the Shepard's hook is provided.
Item No.: 10
Site: Other-WHIRLPOOL
Violation: THE WHIRLPOOL WAS TESTED EVERY 4-HOUR SHIFT AND NOT HOURLY AS REQUIRED. THE MONTHLY INSPECTION OF THE GRANULAR FILTER MEDIA WAS NOT RECORDED. A MONTHLY SEDIMENTATION TEST WAS NOT PERFORMED. THE CHLORINE RESIDUAL WAS NOT RAISED TO 10 PPM AT THE END OF EACH DAY AND CIRCULATED FOR ONE HOUR. THERE WERE NUMEROUS DAYS WHEN THE PH WAS ABOVE 7.8.
Recommendation: Ensure the whirlpool is tested every hour and the monthly inspection of the granular filter media is recorded also ensure a monthly sedimentation test is performed. Ensure the chlorine residual is raised to 10 ppm and recirculated for one hour.
Item No.: 22
Site: Other-LIDO DISHWASH
Violation: THE FINAL RINSE THERMOMETER WAS BROKEN.
Recommendation: Ensure the final rinse thermometer is fixed or replaced.
Item No.: 26
Site: Other-LIDO PREPARATION
Violation: FOUR COOKING UTENSILS WERE SOILED AND STORED AS CLEAN.
Recommendation: 7.5.5.1.1 Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
Item No.: 16
Site: Other-BELVEDERE PANTRY
Violation: THE TIME AS A CONTROL PLAN FOR DAIRY PRODUCTS DID NOT NOTE A 4-HOUR DISCARD TIME.
Recommendation: Ensure a 4-hour discard time is provided for the dairy products time control plan.
Item No.: 30
Site: Other-BELVEDERE BAR
Violation: A "WASH HANDS OFTEN" SIGN WAS NOT POSTED OVER THE HANDWASH SINK.
Recommendation: 7.7.1.1.7 A sign stating "WASH HANDS OFTEN" in a language that the food employees understand shall be posted over handwashing sinks.
Item No.: 20
Site: Other-BELVEDERE BAR PANTRY
Violation: THE BOTTOM OF THE ICE CHUTE WAS CRACKED OVER THE ICE BIN.
Recommendation: 7.4.2.2.1 Replace the bottom of the ice chute.
Item No.: 31
Site: Other-BELVEDERE PANTRY
Violation: TWO UNLABELED BOTTLES OF BLEACH WERE NOTED IN THE CLEANING LOCKER.
Recommendation: 7.6.1.1.2 Working containers used for storing poisonous or toxic materials such as cleaners and sanitizers taken from bulk supplies shall be clearly and individually identified with the common name of the material.
Item No.: *
Site: Other-CORRECTIVE ACTION STATEMENT
Violation: IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY. PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV USE EMAIL MESSAGE SUBJECT LINE: SHIP NAME - CAS - [INSERT INSPECTION DATE] .
Recommendation:
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program