Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Nippon Maru Cruise Line: Mitsui O.S.K. Passenger Line, Ltd Inspection Date: 12/31/2004 Inspection Score: 97
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 26
Site: Other-MAIN GALLEY - CLEAN STORAGE ROOM
Violation: A FEW OF THE PREVIOUSLY CLEANED CHAFFER PANS WERE FOUND SOILED WITH FOOD RESIDUE ON THE CLEAN STORAGE SHELF.
Recommendation: 7.3.3.4.1 Food shall only contact surfaces of equipment and utensils that are cleaned and sanitized.
Item No.: 33
Site: Other-FOOD SERVICE GENERAL
Violation: BULKHEADS AND DECKHEADS WERE DIFFICULT TO CLEAN IN SOME GALLEY AREAS AND ALL PROVISIONS PREPARATION AND WALK-IN STORAGE UNITS, DUE TO ATTACHED ELECTRICAL BOXES, BELLS, AND SWITCHES AND ATTACHED PIPING AND WIRING RUNS. WALK-IN FREEZERS HAD LAYERED FROST ON THE EXTERIOR OF THE CHILLED PIPING INSULATION.
Recommendation: 7.7.4.1.7 Exposed utility service lines and pipes, including lines for fire detection and protection systems, shall be installed so they do not obstruct or prevent cleaning. 7.7.4.1.1 Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be constructed and maintained for easy cleaning.
Item No.: 08
Site: Other-MAIN GALLEY - SOUP AREA
Violation: THE SPRAY RINSE HOSES ATTACHED TO THE 4 TILTING KETTLES WERE PROTECTED FROM BACKFLOW WITH ATMOSPHERIC VACUUM BREAKERS, WHICH WERE NOT DESIGNED FOR CONTINUOUS PRESSURE APPLICATIONS.
Recommendation: Either install separate continuous pressure type backflow preventers on the hot and cold water supply lines to the kettles, or install a single continuous pressure type backflow preventer where the spray hose connects to its base for each kettle.
Item No.: 36
Site: Other-MAIN GALLEY - SOUP AREA
Violation: THE ARTIFICIAL LIGHT LEVEL IN THE PORT FORWARD CORNER AT THE SOUP KETTLE WAS BELOW THE MINIMUM 22O LUX (20 FOOT CANDLES).
Recommendation: 7.7.5.1.1 The light intensity shall be at least 220 Lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
Item No.: 24
Site: Other-MAIN GALLEY - POT WASH
Violation: THE STAFF MEMBER WORKING AT THE CHLORINE SANITIZING SINK WAS OBSERVED SOMETIMES DIPPING PANS IN THE SINK FOR ONLY 2 SECONDS.
Recommendation: 7.5.6.2.2 A chemical sanitizer shall be used in accordance with the EPA-approved manufacturer's label use instructions at a minimum temperature of 24°C (75°F) with an exposure time of 7 seconds for a chlorine solution and 30 seconds for other chemical sanitizers.
Item No.: 06
Site: Other-POTABLE WATER - DISTRIBUTION SYSTEM
Violation: THE MONITORING SYSTEM IN-PLACE FOR THE POTABLE WATER DISTRIBUTION HALOGEN LEVELS RECORDS ON A STRIP CHART WHICH IS CHANGED ON A 30 DAY SCHEDULE.
Recommendation: 5.5.2.2.1 Halogen analyzer-chart recorder charts shall be changed, initialed, and dated daily. Charts shall contain notations of any unusual water events in the potable water system.
Item No.: 10
Site: Other-GRAND BATH WHIRPOOLS
Violation: THE MONTHLY TESTING OF THE SAND FROM THE GRAND BATH FILSTERS DID NOT INCLUDE COLLECTING A CORE SAMPLE OF SAND, BUT RATHER INVOLVED COLLECTING SURFACE WATER FROM THE TOP OF THE FILTER. THE WATER WAS THEN EXAMINED FOR COLIFORM BACTERIA WITH AN ONBOARD TEST KIT.
Recommendation: 6.3.1.1.5 The granular filters shall be opened at least monthly and examined for cracks, mounds, or holes in the filter media. A core sample of the filter media shall be inspected for excessive organic material accumulation using a recommended sedimentation method.
Item No.: 02
Site: Other-MEDICAL
Violation: THERE WAS NO METHOD FOR DETERMINING IF CREW MEMBERS HAD SYMPTOMS OF GASTROINTESTINAL ILLNESS UP TO 3 DAYS PRIOR TO BOARDING THE SHIP.
Recommendation: 4.1.1.1.2 The reportable cases shall include those crew members with a symptom onset time of up to 3 days before boarding the vessel.
Item No.: *
Site: Other-COMMENT - CORRECTIVE ACTION
Violation: IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY. PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV USE EMAIL MESSAGE SUBJECT LINE: SHIP NAME - CAS - [INSERT INSPECTION DATE] .
Recommendation:
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program