Cruise Ship: Europa Cruise Line: Hapag-Lloyd Cruises Inspection Date: 10/10/2004 Inspection Score: 94
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 41
Site: Other-VENTILATION
Violation: THE AIR CONDITIONING CONDENSATE COLLECTION PANS WERE NOT ACCESSIBLE FOR INSPECTION. VSP REVIEWED THE ATTEMPTED CORRECTION, BUT IT DOES NOT ALLOW VIEW OF THE COLLECTION PAN.
Recommendation: 9.2.1.1.1 Air handling unit condensate drain pans and collection systems shall be accessible for inspection, maintenance, and cleaning.
Item No.: 26
Site: Other-MAIN GALLEY / COLD PANTRY
Violation: A SOILED SERRATED KNIFE WAS FOUND IN A KNIFE STORAGE DRAWER STORED AS CLEAN.
Recommendation: 7.5.5.1.1 Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
Item No.: 20
Site: Other-MAIN GALLEY / COLD PANTRY
Violation: A SERRATED KNIFE WAS FOUND WITH IT'S HANDLE BROKEN AT THE HILT MAKING IT DIFFICULT TO CLEAN. THE KNIFE WAS DISCARDED DURING THE INSPECTION.
Recommendation: 7.4.2.2.1 Multiuse food-contact surfaces shall be: (1) Smooth; (2) Free of breaks, open seams >1 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel such as screwdrivers, pliers, open-end wrenches, and Allen wrenches.
Item No.: 26
Site: Other-MAIN GALLEY / COLD PANTRY
Violation: TWO SERVING SPOONS WERE FOUND IN A STORAGE DRAWER SOILED WITH FOOD RESIDUE AND STORED AS CLEAN.
Recommendation: 7.5.5.1.1 Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
Item No.: 26
Site: Other-MAIN GALLEY / MEAT PREPARATION
Violation: THE MEAT TENDERIZING HAMMER WAS FOUND SOILED WITH FOOD RESIDUE AND STORED AS CLEAN.
Recommendation: 7.5.5.1.1 Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
Item No.: 16
Site: Other-MAIN GALLEY / HOT GALLEY
Violation: A SHALLOW BAINS MARIE PAN OF THYME SAUCE WAS FOUND IN THE BLAST CHILLER WITH AN INTERNAL PRODUCT TEMPERATURE 0F 78°F. THE BLAST CHILLER LOG INDICATED THAT THE SAUCE WAS PLACED IN THE UNIT APPROXIMATELY 2.5 HOURS EARLIER AT A TEMPERATURE OF 168°F. THERE WAS NO DOCUMENTATION THAT THE TEMPERATURE WAS CHECKED AFTER TWO HOURS OF COOLING. OTHER PRODUCTS IN THE BLAST CHILLERS, WHEN COMPARED TO THE LOG INDICATED THAT THEY HAD REACHED A TEMPERATURE OF 70°F WITHIN THE REQUIRED TWO HOURS PERIOD.
Recommendation: 7.3.5.2.1 Cooked potentially hazardous food shall be cooled: (1) Within 2 hours, from 60°C (140°F) to 21°C (70°F); and (2) Within 4 hours, from 21°C (70°F) to 5°C (41°F) or less. Recommend that an additional column be added to the blast chiller logs to record the product temperature after 2 hours to ensure it has cooled to a temperature of 70°F or less.
Item No.: 26
Site: Other-MAIN GALLEY / POTWASH
Violation: SEVERAL PREVIOUSLY CLEANED BAINS MARIE PANS WERE FOUND SOILED WITH FOOD RESIDUE AND STORED AS CLEAN.
Recommendation: 7.5.5.1.1 Food-contact surfaces of equipment and utensils shall be clean to sight and touch.
Item No.: 24
Site: Other-FOOD SERVICE - GENERAL
Violation: THE FINAL RINSE TEMPERATURES MEASURED AT THE DISH SURFACE OF WAREWASHERS WAS MEASURED AT 180°F OR ABOVE. THE MACHINE MOUNTED THERMOMETER ON THE DISHWASHING MACHINE IN THE MAIN GALLEY INDICATED A TEMPERATURE OF 250°F. THE MANIFOLD AND/OR TANK TEMPERATURES FOR THE FINAL, SANITIZING RINSE SHOULD BE BETWEEN 180-194°F AND THE DISH SURFACE TEMPERATURE A MINIMUM OF 160°F. THE HIGH TEMPERATURE MADE THE MAIN GALLEY DISHWASH AREA VERY HOT AND HUMID.
Recommendation: 7.5.6.1.2 In a mechanical operation, the temperature of the fresh hot water sanitizing rinse as it enters the manifold may not be more than 90°C (194°F), or less than: (1) For a stationary rack, single temperature machine, 74°C (165°F); or (2) For all other machines, 82°C (180°F). (3) A utensil surface temperature of 71°C (160°F) as measured by an irreversible registering temperature indicator shall be achieved. (4) The maximum temperature of 90°C (194°F), does not apply to the high pressure and temperature systems with wand-type, hand-held, spraying devices used for the in-place cleaning and sanitizing of equipment such as meat saws.
Item No.: 08
Site: Other-CREW DISHWASH AREA
Violation: THE SPRING ON THE PRE-WASH HOSE ALLOWED THE NOZZLE TO HANG BELOW THE FLOOD LEVEL RIM OF THE SINK AND THERE WAS NO BACKFLOW PREVENTION DEVICE INSTALLED ON THE FIXED END OF THE PRE-WASH HOSE.
Recommendation: Install a continuous pressure type backflow prevention device or install or adjust the spring to ensure the air-gap is maintained.
Item No.: 15
Site: Other-PROVISIONS
Violation: SHELLSTOCK SHELLFISH TAGS WERE NOT RETAINED ONBOARD FOR 90 CALENDAR DAYS FROM THE DATE THE CONTAINERS WERE EMPTIED. ADDITIONALLY, THERE WAS NO WAY TO CORRELATE BETWEEN THE SHELLSTOCK AND THE DATE WHEN THE SHELLSTOCK WAS SERVED.
Recommendation: 7.3.2.3.2 Shellstock shellfish tags shall: (1) Remain attached to the container in which the shellstock are received until the container is empty. (2) Be maintained by retaining shellstock tags or labels for 90 calendar days from the date the container is emptied by using an approved record keeping system that keeps the tags or labels in chronologic order correlated to the date when the shellstock are served.
Item No.: 16
Site: Other-PROVISIONS
Violation: THERE WAS NO DOCUMENTATION THAT THE SMOKED FISH, TROUT, HALIBUT, AND SALMON SERVED UNCOOKED WAS FROZEN FOR PARASITE DESTRUCTION OR CERTIFIED PARASITE FREE FROM THE PROVIDER.
Recommendation: 7.3.4.2.1 Before service in ready-to-eat form, raw, raw-marinated, partially cooked, or marinated-partially cooked fish other than molluscan shellfish: (1) Shall be frozen throughout to a temperature of -20°C (-4°F) or below for 168 hours (7 days) in a freezer; or -35°C (-31°F) or below for 15 hours in a blast freezer.
Item No.: *
Site: Other-CORRECTIVE ACTION STATEMENT
Violation: IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY. PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV USE EMAIL MESSAGE SUBJECT LINE: EUROPA - CAS - 10/10/2004.
Recommendation:
Item No.: 40
Site: Other-INTEGRATED PEST MANAGEMENT
Violation: THE WRITTEN INTEGRATED PEST MANAGEMENT (IPM) PLAN DID NOT CONTAIN INFORMATION ON ACTIVE MONITORING NOR DID THE LOG PROVIDE SPACE FOR REPORTING THE SIGHTING OF LIVE INSECTS OTHER THAN IN TRAPS. THIS ACTIVE MONITORING SHOULD INCLUDE INSPECTIONS DURING BOTH DAYTIME AND NIGHT TIME HOURS AND THE LOG SHOULD INCLUDE SPACE TO LIST THE TIME THE INSPECTIONS WERE CONDUCTED.
Recommendation: Add active monitoring for pests to the written plan and include space for this monitoring, include times on the log.
Item No.: 08
Site: Other-BACKFLOW PREVENTION - GENERAL
Violation: BACKFLOW PREVENTERS WERE NOT INSTALLED ON THE FOLLOWING CROSS CONNECTED EQUIPMENT: DECK 7 SPA - FLEXIBLE SHOWER IN THE MEN'S AND WOMEN'S CHANGING ROOMS, FOOT BATH FLEXIBLE SHOWERS IN THE MIXED USE ROOM, MASSAGE THERAPY ROOM #1 AT THE FLEXIBLE SHOWER HOSE, AND THE FOAM HOSE CONNECTION TO THE JAPANESE BATH. HANDICAP CABINS 733 AND 734. BACKFLOW PREVENTION DEVICES WERE INSTALLED DURING THE INSPECTION.
Recommendation: Install appropriate backflow protection devices on these potable water connections.
Item No.: 08
Site: Other-BACKFLOW PREVENTION - GENERAL
Violation: THE DOUBLE CHECK VALVE BACKFLOW PREVENTERS IN THE GALLEY HOOD CLEANING CABINET WERE NOT EQUIPPED WITH INTERMEDIATE VENTS AND SHOULD BE REPLACED. THE ORAS MODEL BACKFLOW PREVENTERS INSTALLED AT HOSE BIBBS IN THE GARBAGE ROOM AND ALL DECK TAP HOSE BIBBS IN MECHANICAL EQUIPMENT ROOMS HAVE SPRAY NOZZLE VALVES INSTALLED ON THE HOSES DOWNSTREAM OF THE BACKFLOW PREVENTER. VSP HAS REVIEWED THE MANUFACTURERS GUIDANCE ON THESE PREVENTERS, THEY ARE NOT DESIGNED FOR CONTINUOUS PRESSURE APPLICATIONS. THE REDUCED PRESSURE ASSEMBLY BACKFLOW PREVENTER AT THE REVERSE OSMOSIS UNIT IS POSITIONED DOWNSTREAM OF A DIVIDED PIPE SECTION, LEAVING ONLY ONE PIPE PROTECTED FROM BACKFLOW FROM THE HOSPITAL DIALYSIS TANKS.
Recommendation: Provide continuous pressure type backflow prevention devices on these connections. Modify the position of the reduced pressure principle backflow preventer from the osmosis so that it protects all of the potable water piping.
Item No.: 09
Site: Other-MAIN POOL
Violation: THE POOL WAS OPEN FOR USE AND THE WATER HAD A FREE CHLORINE RESIDUAL AVERAGING 0.75 PPM, FOLLOWING 3 REPEATED TESTS WITH TWO TEST KITS. ONBOARD STAFF WERE MEASURING TOTAL CHLORINE RATHER THAN FREE CHLORINE RESIDUALS.
Recommendation: 6.2.2.1.1 A free residual halogen of >1.0 and <3.0 mg/L (ppm) shall be maintained in recirculated swimming pools.
Item No.: 09
Site: Other-WHIRLPOOL SPA
Violation: THE WHIRLPOOL SPA WAS OPEN AND THE WATER HAD A FREE CHLORINE RESIDUAL OF 2 PPM AFTER REPEATED TESTS WITH TWO TEST KITS. THE ONBOARD STAFF WERE TESTING TOTAL CHLORINE RATHER THAN FREE CHLORINE RESIDUAL.
Recommendation: 6.3.2.1.1 Whirlpool spas shall maintain a free residual chlorine of >3.0 mg/L (ppm) and <10 mg/L (ppm), or a free residual bromine of >4.0 mg/L (ppm) and <10 mg/L (ppm).
Item No.: 41
Site: Other-KINDERGARTEN CHILDREN'S CENTER
Violation: THERE WAS NO GUIDANCE ON SYMPTOMS OF COMMON CHILDHOOD INFECTIOUS ILLNESSES AVAILABLE AT THE CENTER, AND NO WRITTEN POLICY ON PROCEDURES TO FOLLOW IF A CHILD DEVELOPS SYMPTOMS OF INFECTIOUS ILLNESS WHILE AT THE CENTER.
Recommendation: 10.4.1.1.1 Written guidance on symptoms of common childhood infectious illnesses shall be maintained in the child-activity center. 10.4.1.1.2 The child-activity center shall have a written policy on procedures to be followed when a child develops symptoms of an infectious illness while at the center.