Item No.:
3
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
The chlorine analyzer was not properly calibrated. The unit indicated a chlorine residual of 0.7 ppm while the manual reading indicated a residual of 1.7 ppm chlorine.
|
|
Recommendation:
The ship must have a chlorine or bromine analyzer-recorder, which must be installed at a distant point in the potable water distribution system where a significant water flow exists. The free halogen residual measured by the analyzer must compare within 0.2 ppm of the actual halogen level.
|
|
|
Item No.:
3
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
Several recording charts for the chlorine analyzer recorder were not changed at the same time daily, allowing an overlap of the recorded levels.
|
|
Recommendation:
A review of records from the ship's automatic chlorine or bromine analyzer must show that the ship has maintained adequate amounts of free halogen residual in the water distribution system since the last inspection of the vessel. The review will be deemed unacceptable if the records show a free halogen residual of less than 0.2 ppm for more than 24 consecutive hours. Charts shall be initialed and dated daily and retained for at least 12-months. Charts shall be changed at a designated time each day in order that no overlapping occurs.
|
|
|
Item No.:
26
|
|
Site:
Other-MAIN POT WASH
|
|
Violation:
Ensure that articles placed in the sanitizing sink are submerged for at least 60 seconds when using chemical sanitizing.
|
|
Recommendation:
|
|