Item No.:
21
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
THE VENTILATION HOODS HAD LOOSE SEALANT THAT WAS MISSING AND PEELING THEREFORE EXPOSING OPEN SEAMS MAKING CLEANING DIFFICULT.
|
|
Recommendation:
7.4.2.1.2
Nonfood-contact surfaces of equipment and utensils shall be designed and constructed to be durable and to retain their characteristic qualities under normal use conditions.
|
|
|
Item No.:
37
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
HEAVY CONDENSATION WAS NOTED ON THE DECKHEAD ABOVE THE STEAM KETTLE COOKING STATION.
|
|
Recommendation:
7.7.6.1.1
All food preparation, warewashing, and toilet rooms shall have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|
|
Item No.:
37
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
HEAVY CONDENSATION WAS NOTED ON THE DECKHEAD AT THE DIRTY END OF THE WAREWASHER.
|
|
Recommendation:
7.7.6.1.1
All food preparation, warewashing, and toilet rooms shall have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|
|
Item No.:
26
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
THE FRESH ORANGE JUICE JUICER WAS HEAVILY SOILED WITH DRIED PULP AND JUICE.
|
|
Recommendation:
7.3.3.4.1
Food shall only contact surfaces of equipment and utensils that are cleaned and sanitized.
|
|
|
Item No.:
37
|
|
Site:
Other-CREW GALLEY
|
|
Violation:
HEAVY CONDENSATION WAS NOTED ON THE DECKHEAD ABOVE THE STEAM KETTLE COOKING STATION.
|
|
Recommendation:
7.7.6.1.1
All food preparation, warewashing, and toilet rooms shall have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|
|
Item No.:
*
|
|
Site:
Other-CORRECTIVE ACTION STATEMENT
|
|
Violation:
IN DEVELOPING THE CORRECTIVE ACTION STATEMENT FOR THIS INSPECTION, CRITICAL-ITEM DEFICIENCIES (DESIGNATED WITH YES IN CRITICAL COLUMN (WORTH 3 - 5 POINTS), WHETHER DEBITED OR NOT, SHOULD INCLUDE STANDARD OPERATING PROCEDURES AND MONITORING PROCEDURES IMPLEMENTED TO PREVENT THE RECURRENCE OF THE CRITICAL DEFICIENCY.
PREPARE CORRECTIVE ACTION STATEMENT AS A WORD PROCESSING OR SPREADSHEET FILE WHICH WILL BE SENT TO USPHS / VSP AS AN EMAIL MESSAGE ATTACHMENT. PLEASE EMAIL CORRECTIVE ACTION STATEMENT TO: VSP@CDC.GOV
USE EMAIL MESSAGE SUBJECT LINE: SHIP NAME - CAS - [INSERT INSPECTION DATE] .
|
|
Recommendation:
|
|
|
Item No.:
28
|
|
Site:
Other-PORTOFINO - CENTER WAIT STATION
|
|
Violation:
THREE COFFEE CARAFES WERE NOT STORED INVERTED TO ALLOW THE WATER TO DRAIN FROM THEM.
|
|
Recommendation:
7.5.7.3.2
Clean equipment and utensils shall be stored:
(1) In a self-draining position that allows air drying; and (2) Covered or inverted.
|
|
|
Item No.:
21
|
|
Site:
Other-PORTOFINO - WAIT STATIONS
|
|
Violation:
THE FORMICA WAS DAMAGED IN SOME AREAS OF THE WAITER STATIONS.
|
|
Recommendation:
7.4.2.2.6
Nonfood-contact surfaces shall be free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
08
|
|
Site:
Other-PORTABLE WATER
|
|
Violation:
THE PRESSURE DIFFERENCE NEEDS TO BE RECORDED WHEN TESTING THE TESTABLE REDUCED PRESSURE BACKFLOW ASSEMBLIES.
|
|
Recommendation:
5.7.2.2.2
Backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, shall be inspected and tested with a test kit at least annually. Test results showing the pressure differences on both sides of the valves shall be maintained for each device.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER
|
|
Violation:
ENSURE THAT THE DECK TAPS THAT ARE USED TO ATTACH HOSES TO WASH THE DECK HAVE THE APPROPRIATE BACKFLOW DEVICE INSTALLED ON THEM.
|
|
Recommendation:
5.7.1.1.3
The vessel shall provide a comprehensive cross- connection control program that provides safe connections to the potable water system through air gaps or appropriate backflow devices at the following locations, if present:
(1) Potable water supply lines to swimming pools, whirlpool spas, hot tubs, bathtubs, showers, and similar facilities; (2) Photographic laboratory developing machines and utility sinks; (3) Beauty and barber shop spray-rinse hoses; (4) Potable water faucets where hoses are connected or can be connected by threaded or quick-connect outlets such as those serving tanks containing chlorine and other chemicals, and deck taps; (5) Garbage grinders and pulpers; (6) Mechanical warewashing machines; (7) Hospital and laundry equipment; (8) Air conditioning expansion tanks; (9) Boiler feed water tanks; (10) Fire systems; (11) Toilets; (12) Potable water, bilge, and sanitary pumps that require priming; (13) Freshwater or saltwater ballast systems; (14) Bilge or other waste water locations; (15) International shore connection; and (16) Any other connection between potable and non-potable water systems.
|
|