Item No.:
10
|
|
Site:
Other-SWIMMING POOL
|
|
Violation:
THERE WERE NO DEPTH MARKINGS AT THE SWIMMING POOL.
|
|
Recommendation:
6.4.1.1.2
Depth markers shall be installed for every 1 m (3 feet) in change of depth and shall be displayed prominently so they can be seen from the deck and from in the pool.
Since the pool depth does not have a change greater than 1 m it is acceptable to provide a single marking on the bulkhead listing the depth range from the shallow to the deeper end.
|
|
|
Item No.:
04
|
|
Site:
Other-POTABLE WATER SYSTEM
|
|
Violation:
THE FREE HALOGEN RESIDUAL IN THE POTABLE WATER DISTRIBUTION SYSTEM WAS LESS THAN 0.2 PPM. THE ANALYZER WAS READING 0.09 PPM AND THE MANUAL TEST SHOWED 0.17 PPM.
|
|
Recommendation:
5.4.1.2.1
The halogenation device shall provide continuous halogenation of the potable water distribution system and shall maintain a free residual halogen of 0.2 mg/L (ppm) and 5.0 mg/L (ppm) throughout the distribution system.
|
|
|
Item No.:
06
|
|
Site:
Other-POTABLE WATER SYSTEM
|
|
Violation:
THE ANALYZER/RECORDER CHARTS HAD A RANGE OF 0-2 PPM.
|
|
Recommendation:
5.5.2.1.1
Halogen analyzer-chart recorder charts shall have a range of 0.0 to 5.0 mg/L (ppm) and have a recording period of 24 hours.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER / BACKFLOW PROTECTION
|
|
Violation:
THE AIR LINE USED TO PRESSURIZE THE POTABLE WATER HYDROPHORE TANK WAS PERMANENTLY CONNECTED AND DID NOT HAVE A BACKFLOW PREVENTER INSTALLED.
|
|
Recommendation:
5.7.1.3.1
The air supply to a compressed air system that supplies pressure to both non-potable and potable water pneumatic tanks shall be through a press-on (manual) type of air valve or hose.
Either install a continuous pressure type backflow preventer or provide a fitting that requires the air hose to be held in place by hand while pressurizing the tank.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER / BACKFLOW PREVENTION
|
|
Violation:
THE ATMOSPHERIC VENT ON THE BACKFLOW PREVENTER FOR THE DISHWASHING MACHINE IN THE PANORAMA BAR WAS PLUGGED.
|
|
Recommendation:
Remove the plug and ensure that the atmospheric vent remains open to allow the device to work properly.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER / BACKFLOW PREVENTION
|
|
Violation:
THERE WERE NON-CONTINUOUS PRESSURE TYPE BACKFLOW PREVENTERS INSTALLED ON SEVERAL OF THE CLOTHES WASHING MACHINES IN THE CREW LAUNDRY.
|
|
Recommendation:
Recommend installing a continuous pressure type backflow prevention device on the main hot and cold water lines to the laundry.
|
|
|
Item No.:
21
|
|
Site:
Other-CREW MESS AND OFFICER MESS
|
|
Violation:
THE "JET SPRAY" JUICE MACHINE SPLASH SHIELDS WERE MISSING, EXPOSING THE TECHNICAL AREA TO SPLASH.
|
|
Recommendation:
Reinstall the splash shields on these units.
|
|
|
Item No.:
16
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
THE VESSEL DID NOT HAVE A CONSUMER ADVISORY NOTICE.
|
|
Recommendation:
7.3.6.1.1
If an animal food such as beef, eggs, fish, lamb, milk, pork, poultry, or shellfish that is raw, undercooked, or not otherwise processed to eliminate pathogens is offered in a ready-to-eat form or as a raw ingredient in another ready-to-eat food, the passengers shall be informed by vessel newsletter articles, brochures, embarkation television broadcasts, menu advisories, placards, or other written means of the significantly increased risk to certain especially vulnerable consumers eating such foods in raw or undercooked form.
|
|
|
Item No.:
33
|
|
Site:
Other-MAIN DINING ROOM BUFFET STATION
|
|
Violation:
THE DECK WAS SOILED AT THE JUNCTION BETWEEN THE BUFFET STATION AND THE CARPET ALONG THE BUFFET STATION.
|
|
Recommendation:
7.7.4.1.3
Bulkhead and deck junctures shall be coved.
7.7.4.2.1
Decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, shall be cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Other-MAIN GALLEY DISHWASH AREA
|
|
Violation:
THERE WAS AN OPEN SEAM NOTED BETWEEN THE HANDWASH SINK AND THE BULKHEAD.
|
|
Recommendation:
Seal the handwash sink, back splash to the bulkhead.
|
|
|
Item No.:
37
|
|
Site:
Other-CREW MESS
|
|
Violation:
THERE WAS NO MECHANICAL VENTILATION IN THE WAREHASHING AREA. THERE WAS A HOOD INSTALLED BUT IN A PREVIOUS INSPECTION CONDENSATION WAS NOTED. THE VESSEL MAY WANT TO CONSIDER CHEMICAL SANITIZING OF DISHWARE.
|
|
Recommendation:
|
|
|
Item No.:
*
|
|
Site:
Other-GENERAL COMMENT
|
|
Violation:
THE VESSELS' INTERNAL SANITATION TRAINING AND TESTING PROGRAM WAS EVALUATED DURING THIS SURVEY. THE VESSEL'S SANITATION TRAINING PROGRAM IS A GOOD INTERNAL TOOL.
|
|
Recommendation:
|
|
|
Item No.:
22
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
SPONGES OR OTHER POROUS ITEMS SHOULD NOT BE USED IN THE SANITIZING BUCKET OF THE THREE BUCKET CLEANING SYSTEM.
|
|
Recommendation:
7.5.5.5.2
Sponges may not be used in contact with cleaned and sanitized or in-use food-contact surfaces.
|
|
|
Item No.:
40
|
|
Site:
Other-INTEGRATED PEST MANAGEMENT
|
|
Violation:
THE INTEGRATED PEST MANAGEMENT PLAN NEEDS FURTHER REVISION TO COMPLY WITH CHAPTER 8 OF THE VSP OPERATIONS MANUAL. SOME MONITORING SHOULD ALSO BE DONE AT NIGHT. STAFF ARE SCHEDULED TO BE TRAIN NED IN THE APPLICATION OF PEST CONTROL CHEMICALS.
|
|
Recommendation:
8.1.1.1.2
The Integrated Pest Management Plan shall set a schedule for periodic monitoring inspections including some at night.
8.1.2.1.3
The training of the pest-control personnel shall be documented in the Integrated Pest Management Plan.
|
|
|
Item No.:
10
|
|
Site:
Other-SWIMMING POOL
|
|
Violation:
THERE WAS NO SHEPERD'S HOOK OR LIFE RING (WITH LINE ATTACHED) PROVIDED AT THE SWIMMING POOL.
|
|
Recommendation:
6.4.1.2.1
Easy access shepherd's hook and approved floatation device shall be provided at a prominent location near each public swimming pool.
|
|
|
Item No.:
10
|
|
Site:
Other-SWIMMING POOL
|
|
Violation:
THERE WAS NO WRITTEN FECAL ACCIDENT PLAN AVAILABLE FOR REVIEW.
|
|
Recommendation:
6.3.1.2.3
A fecal accident response procedure shall be documented and available to the VSP for review during inspections.
|
|
|
Item No.:
06
|
|
Site:
Other-POTABLE WATER SYSTEM
|
|
Violation:
THE ANALYZER/RECORDER CHARTS WERE NOT SIGNED AND NUMEROUS CHARTS HAD RECORDED FOR GREATER THAN 24 HOURS.
|
|
Recommendation:
5.5.2.2.1
Halogen analyzer-chart recorder charts shall be changed, initialed, and dated daily. Charts shall contain notations of any unusual water events in the potable water system.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER SYSTEM
|
|
Violation:
THERE WAS NO LOG OF THE BUNKER AND PRODUCTION WATER HALOGEN LEVELS. HOURLY TESTS ARE REQUIRED DURING BUNKERING AND A TEST EVERY FOUR HOURS IS REQUIRED DURING ONBOARD PRODUCTION.
|
|
Recommendation:
5.2.1.2.2
Free residual halogen monitoring shall be performed at least hourly during the bunkering of potable water and performed at least once every 4 hours during the onboard production of potable water.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER / BACKFLOW PREVENTION
|
|
Violation:
THERE WAS NO INDICATION THAT THE PRESSURE VACUUM BREAKER INSTALLED BETWEEN THE TECHNICAL AND POTABLE WATER SYSTEM WAS TESTED ANNUALLY.
|
|
Recommendation:
5.7.2.2.2
Backflow prevention devices requiring testing, for example reduced pressure backflow preventer and double check valves with test cocks, shall be inspected and tested with a test kit at least annually. Test results showing the pressure differences on both sides of the valves shall be maintained for each device.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER / BACKFLOW PREVENTION
|
|
Violation:
THE DECK WASHING TAP HAD A NON-CONTINUOUS PRESSURE TYPE BACKFLOW PREVENTER INSTALLED BUT THE END OF THE HOSE THAT WAS CONNECTED HAD A SHUT-OFF AT THE END. THE HOSE WAS IN USE AT THE TIME.
|
|
Recommendation:
Install a continuous pressure type backflow preventer or do not allow shut-off valves on these hoses.
|
|
|
Item No.:
08
|
|
Site:
Other-POTABLE WATER / BACKFLOW PREVENTION
|
|
Violation:
THE SMALL CLOTHES WASHING MACHINE IN THE MAIN LAUNDRY DID NOT APPEAR TO HAVE A BACKFLOW PREVENTER INSTALLED. ADDITIONALLY, THE CHEMICAL DISPENSING UNIT DID NOT APPEAR TO HAVE A BACKFLOW PREVENTER INSTALLED.
|
|
Recommendation:
Recommend installing a continuous pressure type backflow prevention device on the main hot and cold water lines to the laundry.
|
|
|
Item No.:
19
|
|
Site:
Other-PROVISIONS BEVERAGE STORAGE
|
|
Violation:
BOXES OF WINE WERE FOUND STORED ON THE DECK.
|
|
Recommendation:
7.3.3.7.1
Food shall be protected from contamination that may result from a factor or source such as seawater, bilge water, or hydraulic or fuel lines.
|
|
|
Item No.:
*
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
THE OVERALL CLEANLINESS OF THE FOOD PREP AND STORAGE AREAS WAS OUTSTANDING.
|
|
Recommendation:
|
|
|
Item No.:
30
|
|
Site:
Other-GENERAL COMMENT FOOD SERVICE
|
|
Violation:
ENSURE THAT ALL HANDWASH STATIONS HAVE ACCESSIBLE WASTE RECEPTACLE.
|
|
Recommendation:
7.7.1.1.6
A handwashing facility shall include a sink, soap dispenser, single-use towels dispenser, and waste receptacle.
|
|
|
Item No.:
*
|
|
Site:
Other-MAIN GALLEY
|
|
Violation:
THE BLAST CHILLER WAS OUT OF SERVICE.
|
|
Recommendation:
Ensure that this unit is repaired as soon as the ordered parts arrive.
|
|
|
Item No.:
33
|
|
Site:
Other-MAIN GALLEY BEVERAGE STATION
|
|
Violation:
A PROFILE WAS MISSING FROM THE BEVERAGE COUNTER ALONG THE STARBOARD SIDE.
|
|
Recommendation:
Replace the missing profile.
|
|
|
Item No.:
20
|
|
Site:
Other-CREW MESS
|
|
Violation:
THE MICROWAVE DID NOT COMPLY WITH AMERICAN NATIONAL STANDARDS INSTITUTE OR OTHER INTERNATIONAL ACCREDITED FOOD-EQUIPMENT SANITATION STANDARDS.
|
|
Recommendation:
7.4.2.5.1
Food-contact surfaces of food equipment shall comply with American National Standards Institute (ANSI) or other internationally accredited food-equipment sanitation standards for materials, design, and construction.
|
|
|
Item No.:
22
|
|
Site:
Other-FOOD SERVICE GENERAL
|
|
Violation:
THE WAREWASH MACHINES DID NOT HAVE DATA PLATES.
|
|
Recommendation:
7.5.2.2.3
A warewashing machine shall be provided with an easily accessible and readable data plate affixed to the machine by the manufacturer that indicates the machine's design and operating specifications including the:
(1) Temperatures required for washing, rinsing, and sanitizing; (2) Pressure required for the fresh water sanitizing rinse; and (3) Conveyor speed for conveyor machines or cycle time for stationary rack machines.
|
|
|
Item No.:
33
|
|
Site:
Other-PANORAMA BAR
|
|
Violation:
THERE WAS A GAP UNDERNEATH THE BAR COUNTER NEXT TO THE ENTRY.
|
|
Recommendation:
7.7.4.1.1
Decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas shall be constructed and maintained for easy cleaning.
|
|