Item No.:
08
|
|
Site:
Potable Water-Main Galley Windows Dishwash Area
|
|
Violation:
There was no air gap or backflow prevention device for the pre wash spray hose.
|
|
Recommendation:
The vessel shall provide a comprehensive cross- connection control program that provides safe connections to the potable water system through air gaps or appropriate backflow devices at the following locations, if present:
(1) Potable water supply lines to swimming pools, whirlpool spas, hot tubs, bathtubs, showers, and similar facilities; (2) Photographic laboratory developing machines and utility sinks; (3) Beauty and barber shop spray-rinse hoses; (4) Potable water faucets where hoses are connected or can be connected by threaded or quick-connect outlets such as those serving tanks containing chlorine and other chemicals, and deck taps; (5) Garbage grinders and pulpers; (6) Mechanical warewashing machines; (7) Hospital and laundry equipment; (8) Air conditioning expansion tanks; (9) Boiler feed water tanks; (10) Fire systems; (11) Toilets; (12) Potable water, bilge, and sanitary pumps that require priming; (13) Freshwater or saltwater ballast systems; (14) Bilge or other waste water locations; (15) International shore connection; and (16) Any other connection between potable and non-potable water systems.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Mineralizers
|
|
Violation:
There was not a distance of 2 times the diameter of the discharge line at the end of the drain for the mineralizer backwash.
|
|
Recommendation:
Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Bunker Hoses
|
|
Violation:
One of the in-use bunker hoses was not labeled "potable water only" at each connecting end.
|
|
Recommendation:
Ensure that potable water hoses are labeled for use with the words "potable water only" in letters at least 13mm (0.5 inch) at each connecting end.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Photo Lab
|
|
Violation:
There was no backflow prevention device for the potable water line to the sink in the photo lab. A hose had been attached to the sink and it extended into the basin of the sink.
|
|
Recommendation:
The vessel shall provide a comprehensive cross- connection control program that provides safe connections to the potable water system through air gaps or appropriate backflow devices at the following locations, if present:
(1) Potable water supply lines to swimming pools, whirlpool spas, hot tubs, bathtubs, showers, and similar facilities; (2) Photographic laboratory developing machines and utility sinks; (3) Beauty and barber shop spray-rinse hoses; (4) Potable water faucets where hoses are connected or can be connected by threaded or quick-connect outlets such as those serving tanks containing chlorine and other chemicals, and deck taps; (5) Garbage grinders and pulpers; (6) Mechanical warewashing machines; (7) Hospital and laundry equipment; (8) Air conditioning expansion tanks; (9) Boiler feed water tanks; (10) Fire systems; (11) Toilets; (12) Potable water, bilge, and sanitary pumps that require priming; (13) Freshwater or saltwater ballast systems; (14) Bilge or other waste water locations; (15) International shore connection; and (16) Any other connection between potable and non-potable water systems.
|
|
|
Item No.:
11
|
|
Site:
Medical-
|
|
Violation:
On 20 October 2009, a room steward was a reportable case of gastrointestinal illness. The room steward was isolated for only 24 hours following the last symptom. The Assistant Housekeeping Manager stated that room stewards fill ice buckets for the passenger cabins.
|
|
Recommendation:
Ensure that symptomatic food employees meeting the case definition for AGE are isolated in cabin or designated, restricted area until symptom-free for a minimum of 48 hours.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Raffles Starboard Toast Station
|
|
Violation:
The bowls of jelly and peanut butter were not fully protected under the sneeze shield. This was corrected.
|
|
Recommendation:
Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Raffles Midship Pastry Area
|
|
Violation:
Two bowls of pastries were not fully protected under the sneeze shield. This was corrected.
|
|
Recommendation:
Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
21
|
|
Site:
Galley-Special Order Section
|
|
Violation:
The underside drain panel on the flat grill was rough and bent. In addition, there was a large gap where the drain pipe intersected the panel.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material. Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
22
|
|
Site:
Pantry-Champagne Charlie
|
|
Violation:
The data plate on the dishwash machine was worn and difficult to read.
|
|
Recommendation:
Ensure that warewashing machines are provided with an easily accessible and readable data plate affixed to the machine by the manufacturer that indicates the machine's design and operating specifications including the: (1) Temperatures required for washing, rinsing, and sanitizing; (2) Pressure required for the fresh water sanitizing rinse; and (3) Conveyor speed for conveyor machines or cycle time for stationary rack machines.
|
|
|
Item No.:
25
|
|
Site:
Bar-Coffee
|
|
Violation:
A wiping cloth was draped on the side of the sanitizing bucket.
|
|
Recommendation:
Ensure that wet wiping cloths used with a freshly made sanitizing solution and dry wiping cloths are free of food debris and visible soil.
|
|
|
Item No.:
27
|
|
Site:
Galley-Special Order Section
|
|
Violation:
The underside drain panel on the flat grill was soiled.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Galley-Special Order Section
|
|
Violation:
The bottom of the technical compartment 2 was soiled. In addition, there was a wet and soiled insect trap.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
29
|
|
Site:
Galley-Special Order Section
|
|
Violation:
The temperature of the water at the handwash sink was 130°F. This was corrected.
|
|
Recommendation:
Ensure that handwashing sinks are equipped to provide water at a temperature of at least 43°C (110°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, where the user cannot make temperature adjustments, ensure that the temperature provided to the user does not exceed 52°C (125°F).
|
|
|
Item No.:
33
|
|
Site:
Pantry-Windows Restaurant Starboard
|
|
Violation:
The plastic coving was rough and torn at the deck juncture.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Buffet-
|
|
Violation:
The plastic coving at the entrance to the galley was torn.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Galley-
|
|
Violation:
There was missing and recessed grout between the deck tiles by the tilt pans, soup kettles, and combination ovens.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Other-Sushi Bar
|
|
Violation:
The plastic coving on the right hand side of the handwash station was loose.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Raffles Port Waffles/French Toast Station
|
|
Violation:
There was a piece of worn wood at the lower left hand corner of the cabinet on the working side of the buffet line at the deck/cabinet juncture. The wood was difficult to clean and soiled.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Buffet-Raffles Starboard Smoked Salmon Area
|
|
Violation:
The plastic coving at the deck/bulkhead juncture on the working side of the buffet line at the entrance to the galley was torn and rough.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Galley-Hot Buffet Area
|
|
Violation:
There was recessed and missing grout between the deck tiles in the tilt pan area.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Galley-Vegetable Section
|
|
Violation:
There was missing and recessed grout between the deck tiles near the tilt pans.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Galley-Fish Grill Area
|
|
Violation:
There was missing and recessed grout between the deck tiles in this area.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Pantry-Blue Lagoon
|
|
Violation:
There was recessed and missing grout between the deck tiles in this area.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
37
|
|
Site:
Galley-Hot Buffet Area
|
|
Violation:
There was condensate on the exhaust hood above the combination oven.
|
|
Recommendation:
Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
37
|
|
Site:
Pantry-Raffles Lido
|
|
Violation:
There was condensation on the underside of the shelf above the steam table. There was no food on the table.
|
|
Recommendation:
Ensure that all food preparation, warewashing, and toilet rooms have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|