Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Seven Seas Navigator Cruise Line: Regent Seven Seas Inspection Date: 12/28/2009 Inspection Score: 99
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 02
Site: Medical-
Violation: There were two individuals who were dispensed anti-diarrheal medication who were not listed in the gastrointestinal illness log.
Recommendation: The log shall list: (1) All reportable cases of gastrointestinal illness; (2) All passengers and crew members who are dispensed antidiarrheal medication from the master of the vessel, the medical staff, or other designated staff.
Item No.: 08
Site: Potable Water-
Violation: The air gap for the main laundry tank was not sufficient.
Recommendation: Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
Item No.: 08
Site: Potable Water-
Violation: The potable water lines in the main laundry were not painted or striped blue.
Recommendation: Ensure that potable water piping and fittings are painted or stripped auxiliary blue, or in accordance with ISO 14726, at 5 m (15 feet) intervals on each side of partitions, decks, and bulkheads in all spaces, except where the decor would be marred by such markings.
Item No.: 08
Site: Potable Water-
Violation: Backflow preventers were not installed on the potable water lines supplying the bathtub hose in cabin 1119, and shower hoses in cabins 1112 and 1125.
Recommendation: Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
Item No.: 08
Site: Potable Water-
Violation: The potable water connections to the bathtub hoses in the passenger cabins were not on the cross-connection control list.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 08
Site: Potable Water-
Violation: There was no listing of connections to the potable water system below deck 4. The main laundry connection was not on the cross-connection control list. The connections in the swimming pool mechanical room were not on cross-connection control list.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 08
Site: Potable Water-
Violation: A potable water hose was stored in an open trolley. The hose was less than 18 inches from the deck.
Recommendation: Ensure that potable water hoses are stowed rolled tight with the ends capped, on reels, or racks or with ends coupled together in potable water hose lockers. Ensure that the potable water hose lockers are mounted at least 460 mm (18 inches) above the deck and are self-draining.
Item No.: 06
Site: Potable Water-
Violation: There was no test for E. coli conducted on the water that was bunkered in Bremerhaven.
Recommendation: Where available, ensure that the vessel has a copy of the most recent microbiologic report from each port before bunkering potable water to verify that the water meets potable standards. Ensure that these records are maintained on the vessel for 12 months and available to the VSP for review during inspections.
Item No.: 30
Site: Buffet-Handwash Stations
Violation: There were no "wash hands often" signs at the handwash stations in the new and renovated areas of the buffet.
Recommendation: Ensure that a sign stating "WASH HANDS OFTEN" in a language that the food employees understand is posted over handwashing sinks.
Item No.: 21
Site: Buffet-Deck BBQ
Violation: In the technical compartment of the center island preparation counter, there was a vertical seam in the back of the compartment. The penetration in the floor of the compartment was rough along the top surface where the cables entered the penetration.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance. Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 21
Site: Buffet-Deck BBQ
Violation: In the technical compartment of the back counter, there were excess cables and cables draped on the floor of the compartment.
Recommendation: Remove or raise the excess cables from the floor of the technical compartment.
Item No.: 19
Site: Buffet-Deck BBQ
Violation: On each end of the buffet, the side shields were not large enough to protect the food on display from passengers lining up for service. Staff stated that passengers would enter from both ends of the buffet counter. Also, there were no side shields near the pillar in the center of the buffet and the pillar did not completely prevent access to the food on display.
Recommendation: Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
Item No.: 38
Site: Pantry-Prime 7 Pantry
Violation: The cleaning locker was not labeled.
Recommendation: Ensure that maintenance tools such as mops, brooms, and similar items are stored in a designated locker so they do not contaminate food, food-contact surfaces of utensils, and equipment, linens, and single-service and single-use articles.
Item No.: 21
Site: Buffet-La Veranda
Violation: In the technical compartment for Port 11 & 12 (DL 003237), there was a seam along the lower right area of the compartment that was not completely sealed.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 21
Site: Buffet-La Veranda
Violation: There was a gap at the juncture between the new bulkhead tiles and the buffet counter.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 33
Site: Buffet-La Veranda
Violation: The bottom of the center door from the buffet to the galley was damaged.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 16
Site: Buffet-La Veranda
Violation: The time control plan indicated that the back-up trolleys were on time control, but the trolleys were not labeled as time control. The ship had new trolleys.
Recommendation: Place time control labels on the back-up trolleys where food is held under time control.
Item No.: 08
Site: Potable Water-
Violation: There was no backflow prevention device on the cold potable water connection to the overhead spray hose by the hood-type dishwash machine. This was in the La Veranda galley.
Recommendation: Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
Item No.: 33
Site: Galley-La Veranda
Violation: There were old table mounts in the deck by the undercounter dishwash machine. These mounts were open on top and holding water.
Recommendation: Ensure that surfaces subject to routine splashes, spillage, or other soiling during normal use have easily cleanable features.
Item No.: 33
Site: Dining Room-Compass Rose
Violation: The deck/cabinet juncture at the wine stands was not coved.
Recommendation: Ensure that bulkhead and deck junctures are coved (including galleys, pantries, deck/counter junctures at buffets, bars, waiter stations, and dining room work counters).
Item No.: 37
Site: Galley-
Violation: The ventilation over the tilting pans did not remove steam when the tilting pan was opened.
Recommendation: Ensure that ventilation hood systems and devices operate effectively to prevent grease and condensate from collecting on the bulkheads and deckheads and remove contaminants generated by equipment located under them.
Item No.: 30
Site: Galley-Bakery & Pastry
Violation: The "wash hands often" sign was on the side of the pillar and not above then handwash station in the bakery. There was no sign at the handwash station in the pastry.
Recommendation: Ensure that a sign stating "WASH HANDS OFTEN" in a language that the food employees understand is posted over handwashing sinks.
Item No.: 30
Site: Galley-Toilet Room
Violation: The toilet room door was self closing, but it hit against the door jam and would not close completely. There was no "wash hands after using toilet" sign.
Recommendation: Ensure that toilet rooms are completely enclosed and shall have tight-fitting, self-closing doors which shall be kept closed except during cleaning or maintenance. Ensure that signs are conspicuously posted on the bulkhead adjacent to the door of the toilet, reading "WASH HANDS AFTER USING TOILET " in a language that the food employees understand.
Item No.: 21
Site: Provisions-Dry Stores
Violation: Some of the bars attached to the shelving units to secure the items for rough seas were hollow and open on the ends.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 19
Site: Provisions-Dry Stores
Violation: The lowest shelf of the can storage rack was less than 6 inches above the deck. The cans on the lowest rack were moved to higher racks.
Recommendation: Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
Item No.: 29
Site: Galley-
Violation: The water at the handwash station by the potwash was measured at greater than 125°F and crew members could not adjust the temperature. This was corrected.
Recommendation: Ensure that handwashing sinks are equipped to provide water at a temperature of at least 43°C (110°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, where the user cannot make temperature adjustments, ensure that the temperature provided to the user does not exceed 52°C (125°F).
Item No.: 20
Site: Galley-
Violation: Two of the cutting boards had visible cuts in the surface.
Recommendation: Ensure that surfaces such as cutting blocks and boards that are subject to scratching and scoring are resurfaced if they no longer can be effectively cleaned and sanitized, or discarded if they are not capable of being resurfaced.
Item No.: 22
Site: Galley-Dishwash
Violation: The temperature gauge for the final rinse indicated a temperature of at least 20 °F lower than the actual temperature. The plate surface was measured at greater than 160°F.
Recommendation: Ensure that water temperature measuring devices: (1) That are scaled in Celsius or dually scaled in Celsius and Fahrenheit are designed to be accurate to ±1.5°C in the intended range of use. (2) That are scaled only in Fahrenheit are designed to be accurate to ±3°F in the intended range of use.
Item No.: 33
Site: Galley-
Violation: The deck was soiled below the utility sink near the entrance to the buffet.
Recommendation: Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
Item No.: 33
Site: Buffet-Beverage Station
Violation: There were pipes on the deck inside the drain of the technical compartment below the ice dispenser.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning.
Item No.: 08
Site: Potable Water-
Violation: There was no backflow prevention device on the Vitality coffee machine in the crew mess beverage station.
Recommendation: Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
Item No.: 21
Site: Bar-Navigation Bar
Violation: In the technical compartment below the speed rail, there was a gap at the right side of the deck drain area where the floor of the compartment met the drain.
Recommendation: Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 08
Site: Potable Water-
Violation: There was no backflow prevention device on the potable water line to the coffee machine in the navigation bar.
Recommendation: Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
Item No.: 22
Site: Pantry-Navigation Bar
Violation: There was no data plate on the dishwash machine.
Recommendation: Ensure that warewashing machines are provided with an easily accessible and readable data plate affixed to the machine by the manufacturer that indicates the machine's design and operating specifications including the: (1) Temperatures required for washing, rinsing, and sanitizing; (2) Pressure required for the fresh water sanitizing rinse; and (3) Conveyor speed for conveyor machines or cycle time for stationary rack machines.
Item No.: 38
Site: Pantry-Navigation Bar
Violation: The cleaning locker was not labeled.
Recommendation: Ensure that maintenance tools such as mops, brooms, and similar items are stored in a designated locker so they do not contaminate food, food-contact surfaces of utensils, and equipment, linens, and single-service and single-use articles.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program