Item No.:
08
|
|
Site:
Potable Water-Deck 9 Spa - Thermal Suite
|
|
Violation:
The backflow preventers installed on the potable water lines supplying the boilers, chemical feeds, and showers in two different rooms in the thermal suite were not on the backflow preventer listing. This was corrected during the inspection.
|
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Deck 8 Pavillion Pool Pump Room
|
|
Violation:
There was no blue stripe on the potable water line feeding the compensation tank in the deck 8 pump room for the pavillion pool.
|
|
Recommendation:
Blue stripe the potable water supply line before the backflow preventer.
|
|
|
Item No.:
21
|
|
Site:
Galley-Deck 2 Main Service Hot Line
|
|
Violation:
On the middle grooved grill, the grease chute was loose inside the grease pan housing. One fastener was missing and one was loose. There were also 3 missing fasteners on the housing frame.
|
|
Recommendation:
Repair the grease chute and housing frame so the fit is tight.
|
|
|
Item No.:
22
|
|
Site:
Galley-Lido Dishwash
|
|
Violation:
The in-use conveyor dishwash and glasswash machines had partially blocked upper spray arm nozzles in the final rinse. The spray pattern from the left two upper arm spray nozzles was weak, producing only a narrow water stream.
|
|
Recommendation:
Ensure that warewashing equipment is maintained in good repair and proper adjustment including: (1) Being maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; and (2) Maintaining water pressure, and water temperature measuring devices in good repair and ensuring their accuracy within the intended range of use.
|
|
|
Item No.:
28
|
|
Site:
Galley-Lido Dishwash
|
|
Violation:
The clean dish racks were stacked on a deck stand positioned directly below the flying insect glue lamp. The dish racks were moved away during the inspection.
|
|
Recommendation:
Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
|
|
|
Item No.:
30
|
|
Site:
Galley-Toilet Room
|
|
Violation:
The "wash hands after using toilet" sign was over the toilet and not on the bulkhead near the exit door. Also, when fully open, the exit door would stay open. When closing, it would not close completely.
|
|
Recommendation:
Ensure that signs are conspicuously posted on the bulkhead adjacent to the door of the toilet, reading "WASH HANDS AFTER USING TOILET " in a language that the food employees understand.
|
|
|
Item No.:
30
|
|
Site:
Galley-Deck 2 Toilet Room
|
|
Violation:
The "wash hands after using toilet" sign was over the toilet and not on the bulkhead near the exit door.
|
|
Recommendation:
Ensure that signs are conspicuously posted on the bulkhead adjacent to the door of the toilet, reading "WASH HANDS AFTER USING TOILET " in a language that the food employees understand.
|
|
|
Item No.:
33
|
|
Site:
Dining Room-Todd English Service Pantry
|
|
Violation:
On the right side of the service pantry, there was an electrical cable draped on the deck below the counter.
|
|
Recommendation:
Ensure that exposed utility service lines and pipes, including lines for fire detection and protection systems, are installed so they do not obstruct or prevent cleaning.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-
|
|
Violation:
There were several doors in food service areas that did not have latch pin recesses in the door frames, leaving openings in the door frames. This was noted in the following locations: vegetable preparation walk-in refrigeration unit, provision room #12 (frozen seafood), pastry walk-in refrigeration unit, and main galley production walk-in refrigeration unit (deck 2, left of elevators).
|
|
Recommendation:
Profile closed those door frames where locking pins and latches insert.
|
|
|
Item No.:
37
|
|
Site:
Galley-Deck 2
|
|
Violation:
There was condensation above the flight-type dishwash unit at the soiled end of the unit. This area was also quite warm.
|
|
Recommendation:
Ensure that ventilation hood systems and devices operate effectively to prevent grease and condensate from collecting on the bulkheads and deckheads and remove contaminants generated by equipment located under them.
|
|
|
Item No.:
37
|
|
Site:
Galley-Grills
|
|
Violation:
There was condensation in the hood and on the upper part of the bulkhead at the soiled end of the flight-type dishwash machine.
|
|
Recommendation:
Ensure that ventilation hood systems and devices operate effectively to prevent grease and condensate from collecting on the bulkheads and deckheads and remove contaminants generated by equipment located under them.
|
|
|
Item No.:
41
|
|
Site:
Children Area-Child Center
|
|
Violation:
The wash hands after each diaper change sign was blocked from view with stacked items stored on the top of the changing table lid. These items were moved during the inspection.
|
|
Recommendation:
Maintain the posted signs free of obstructions, so they are completely visible.
|
|