*General Comments-Pool, Whirlpool & Potable Water Records
|
|
Violation:
The records for the pools, whirlpools and potable water were some of the best organized and complete that the inspector has reviewed. The environmental officer was very knowledgeable about all public health-related areas of his job.
|
|
Recommendation:
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Crew Pool
|
|
Violation:
There were no depth markers on the pool. There was no safety equipment for the pool, which was measured at 1.3 meters. The cover on the drain was not anti-entrapment. The drain was only for emptying the pool and not for recirculation.
|
|
Recommendation:
Ensure that the depth of each pool is prominently displayed so that it can be seen from the deck and in the pool. Ensure that depth markers are labeled in feet or meters, or both,. Additionally, ensure that depth markers are installed for every 1 m (3 feet) in change of depth. Ensure that an easy-access shepherd's hook and approved floatation device (with a length of line 1/2 the pool width or 16 m (50 feet)) is provided at a prominent location near each public swimming pool. Ensure that anti-entrapment drain covers or other drains that prevent entrapment hazards as specified in U.S. Consumer Product Safety Publication 363-009801 (dual drains/channel drains) are provided on swimming pools and whirlpool spas. Ensure that drain covers have either the plumbing/engineering approving organization stamp and flow rate affixed to the cover, or that a letter is maintained aboard the vessel certifying that the cover meets the safety requirements outlined in AMSE/ANSI A112.19.8M or an equivalent standard.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Tanks
|
|
Violation:
There was no documentation that the manufacturer's recommendations for drying/curing of the coating used in the potable water tank. The Chief Officer stated that the tanks were dried with blowers attached for several days before disinfecting the tanks and refilling with water.
|
|
Recommendation:
Ensure that interior coatings on potable water tanks are approved for potable water contact, and all manufacturer's recommendations for application, drying, or curing are followed. Ensure written documentation for the coating used and recommendations followed are available for review during inspections.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Program
|
|
Violation:
The record in the AMOS system for the reduced pressure assemblies did not include the plumbing component for the devices installed in the galleys (hood cleaning).
|
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
|
|
|
Item No.:
21
|
|
Site:
Bar-Pool Bar
|
|
Violation:
In the back left corner of the technical compartment below the cocktail station, the profile strip was bent causing a gap and a hole to the void space between the compartment and the bar counter.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
37
|
|
Site:
Preparation Room-Fish
|
|
Violation:
There was condensation dripping from the underside of the cooling unit pan onto the preparation counter. This area was not open at the time of the inspection, and no food items were exposed.
|
|
Recommendation:
Adjust the temperature and/or ventilation in the room to ensure that condensate does not collect on the underside of the cooling unit pan.
|
|
|
Item No.:
36
|
|
Site:
Galley-Hot Grill
|
|
Violation:
One of the light bulbs was not working above the fryers. It was unclear if there was insufficient light intensity. The light bulb was replaced.
|
|
Recommendation:
Ensure that the light intensity is at least 220 Lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
|
|
|
Item No.:
20
|
|
Site:
Galley-Marina Steakhouse
|
|
Violation:
The round plastic panel in the upper interior of the microwave was not secured. All of the fasteners were in place, but the panel was not flush with the top of the microwave. The edges of the panel were lightly soiled.
|
|
Recommendation:
Properly secure the upper interior panel of the microwave.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Crew Mess
|
|
Violation:
There was no side sneeze shield at the carving station. Also, because the sneeze shield was too high and/or the food too far forward, the food was not completely protected by the sneeze shields at the carving station or at the bread station
|
|
Recommendation:
Ensure that food on display is protected from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; or other effective means.
|
|
|
Item No.:
21
|
|
Site:
Buffet-Officer Mess
|
|
Violation:
The potable water line and the electrical cord from the juice machine were draped across the counter top, making cleaning difficult.
|
|
Recommendation:
Shorten the potable water line and electrical cords or secure them above the counter top to ensure the area is easy to clean.
|
|