Item No.:
08
|
|
Site:
Recreational Water Facilities-Whirlpool
|
|
Violation:
The air gap for the whirlpool was not listed on the cross-connection control program.
|
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Top Side Buffet - Cold Pantry #5
|
|
Violation:
An open container of milk was stored inside under counter reach-in refrigerator on time according to staff. The time as a public health control plan for this area listed foods under time only control and milk was not on that listing.
|
|
Recommendation:
Ensure that the time only as a public health control plan addresses the open milk containers stored in refrigerators in this pantry.
|
|
|
Item No.:
16
|
|
Site:
Galley-Top Side Galley - Hot Galley
|
|
Violation:
One sheet pan with individual bowls of cracked raw eggs was found in undercounter reach-in refrigerator #2 with a Saturday discard label on the pan. Staff stated these eggs were for breakfast only and under time control.
|
|
Recommendation:
Ensure that when foods are moved from temperature control to time only as a public health control that the 7-day discard labels are removed from the container.
|
|
|
Item No.:
16
|
|
Site:
Galley-Main Galley - Bakery/Pastry
|
|
Violation:
One sheet pan of cooked focaccia bread with cut tomato topping was set out at room temperature for today's lunch service and labeled with a Wednesday discard. Staff stated it was on time control.
|
|
Recommendation:
Ensure that when foods are moved from temperature control to time only as a public health control that the 7-day discard labels are removed from the container.
|
|
|
Item No.:
19
|
|
Site:
Galley-Main Galley - Walk-in Vegetable Refrigerator #22
|
|
Violation:
There were several uncut and unpackaged whole romaine lettuce stacked on the top shelf in the walk-in making contact with the bulkhead, deckhead, and the side of the evaporative condenser, none of which were sufficiently clean for food contact. There were 4-6 large unpackaged celery stalks on the top shelf and several whole radichio lettuce set unprotected on the top shelf of this walk-in refrigerator.
|
|
Recommendation:
Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Top Side Buffet - Cold Pantry #5
|
|
Violation:
There were 8 open jars containing various loose nuts or dried fruit on the overshelf of the cold buffet line. There was no cover for these jars and they were presented for passenger self-service (toppings for muesli).
|
|
Recommendation:
Ensure that each self-service food dispensing utensil is covered or located beneath shielding during service.
|
|
|
Item No.:
19
|
|
Site:
Galley-Top Side Galley - Dishwash
|
|
Violation:
The open deck corridor on the port/aft was used to stage soiled items prior to dishwash. Additionally, there was a clean portable table with ice chests for serving ice. The scoop for the chests was set in a bowl on top of this table outdoors and unprotected. The ice scoop was moved to a protected position during the inspection.
|
|
Recommendation:
During pauses in food preparation or dispensing, ensure that food preparation and dispensing utensils are stored: (5) In a clean, protected location if the utensils, such as ice scoops, are used only with a food that is not potentially hazardous.
|
|
|
Item No.:
19
|
|
Site:
Galley-Main Galley - Provision Corridor
|
|
Violation:
Water from the drain of the evaporative condenser was observed dripping and pooling on the top box of raw shell eggs which were stacked directly below the evaporative condenser inside the fruit walk-in refrigerator #7.
|
|
Recommendation:
Ensure that food is not stored: (1) In locker rooms; (2) In toilet rooms; (3) In dressing rooms; (4) In garbage rooms; (5) In mechanical rooms; (6) Under sewer lines that are not continuously sleeve welded; (7) Under leaking water lines, including leaking automatic fire sprinkler heads, or under lines on which water has condensed; (8) Under open stairwells; or (9) Under other sources of contamination from nonfood items such as ice blocks, ice carvings and flowers.
|
|
|
Item No.:
20
|
|
Site:
Housekeeping-Deck 4 - Pantry 4
Deck 4 - Pantry 4
|
|
Violation:
There was rust and peeling paint above the plastic water tray. In addition, the fastener holding the sensor in front of the cuber was corroded and the fastener holding the plastic backflow device was corroded. There was also a black powder like substance along the bottom of the water tray.
|
|
Recommendation:
Clean and repair all surfaces where paint or corrosion are present in food-contact areas. Remove the accumulated powder inside the water bath of the ice machine.
|
|
|
Item No.:
21
|
|
Site:
Buffet-Deck 2 Crew Mess
|
|
Violation:
The power cables were coiled on the counter below the juice dispenser and the adjacent coffee machine at the beverage counter.
|
|
Recommendation:
Elevate the power cables to the fixed counter equipment so cleaning beneath is easy to perform
|
|
|
Item No.:
21
|
|
Site:
Buffet-Top Side Buffet - Cold Pantry #5
|
|
Violation:
There was an open hole at the electrical penetration in the top of the bulkhead mounted storage cabinet and the deckhead.
|
|
Recommendation:
Profile closed the hole surrounding the electrical cord penetration so there is no gap present. Rubber grommet could improve the seal between the profile and cord.
|
|
|
Item No.:
21
|
|
Site:
Buffet-Top Side Buffet - Cold Pantry #5
|
|
Violation:
The power cables were draped on the counter making cleaning difficult below the WMF coffee machine. Additionally, there was a loose plastic piece which appeared to be a component of the machine hanging on the counter top below the machine.
|
|
Recommendation:
Elevate the power cables to the fixed counter equipment so cleaning beneath is easy to perform.
|
|
|
Item No.:
21
|
|
Site:
Pantry-Deck 4 - Pantry #4
|
|
Violation:
There was a difficult to clean gap between the back of the deck mounted dishwash machine and the bulkhead behind.
|
|
Recommendation:
Ensure that equipment that is fixed because it is not easily movable is installed so that it is: (1) Spaced to allow access for cleaning along the sides, behind, under and above the equipment; (2) Spaced from adjoining equipment, bulkhead, and deckhead at a distance of not more than 0.8 millimeter or 1/32 inch; or (3) Sealed to adjoining equipment or bulkhead, if the equipment is exposed to spillage or seepage.
|
|
|
Item No.:
22
|
|
Site:
Galley-Top Side Galley - Dishwash
|
|
Violation:
There was not sufficient space for the staging of soiled items in this dishwash pantry. Stacks of soiled items were stored throughout the room and on the open deck outside this room.
|
|
Recommendation:
Ensure that drainboards, utensil racks, or tables large enough to accommodate all soiled and cleaned items that may accumulate during hours of operation are provided for necessary utensil holding before cleaning and after sanitizing.
|
|
|
Item No.:
22
|
|
Site:
Galley-Main Galley - Dishwash
|
|
Violation:
During active use of the conveyor dishwashing machine the wash tank temperature was measured at 130 °F and the rinse tank temperature was only 140 °F. The manufacturer's dataplate specifies a minimum wash tank temperature of 150 °F and a rinse tank minimum temperature of 160 °F.
|
|
Recommendation:
Ensure that warewashing machines and their auxiliary components: (1) Are operated in accordance with the machine's data plate and other manufacturer's instructions. (2) A warewashing machine's conveyor speed or automatic cycle times are maintained accurately timed in accordance with manufacturer's specifications.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Top Side Buffet - Cold Pantry #5
|
|
Violation:
The counter below the coffee machine was soiled with old dirt debris, particularly near the back bulkhead where cleaning was difficult.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Deck 2 Crew Mess
|
|
Violation:
There was a layer of dust soil on the top exterior surfaces of the the juice dispenser and the coffee machine at the beverage counter.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Galley-Main Galley
|
|
Violation:
The top exterior surface of the ice machine had a layer of visible dust debris present.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
28
|
|
Site:
Buffet-Deck 2 Crew Mess
|
|
Violation:
One of the gray bins filled with clean utensils was soiled along the lower interior surface where the utensils made contact.
|
|
Recommendation:
Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
|
|
|
Item No.:
28
|
|
Site:
Galley-Top Side Galley - Dishwash
|
|
Violation:
Staff were observed hand polishing just cleaned and wet utensils and placing them in gray storage bins. The towel used for polishing was also moist.
|
|
Recommendation:
After cleaning and sanitizing, ensure that equipment and utensils are air-dried or adequately drained before contact with food. Cleaned, sanitized, and air-dried dishware, glassware, and utensils may be polished with a clean, dry, lint-free cloth that is maintained clean and dry.
|
|
|
Item No.:
28
|
|
Site:
Galley-Top Side Galley - Dishwash
|
|
Violation:
One of the gray bins filled with clean utensils was soiled along the lower interior surface where the utensils made contact.
|
|
Recommendation:
Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
|
|
|
Item No.:
29
|
|
Site:
Galley-Top Side Galley - Hot Galley
|
|
Violation:
There was no handwashing sink in the hot galley. The handwash station in the dishwashing pantry is located within the 25 feet/8 meter distance required, but the door between was closed during the inspection, when there were both dishwashing and preparation taking place in the two areas.
|
|
Recommendation:
Ensure that the handwashing facility is located within 8 m (25 feet) of all parts of the area and is not located in an adjacent area that requires passage through a closed door. where the user makes hand contact with the door.
|
|
|
Item No.:
33
|
|
Site:
Galley-Main Galley - Dishwash
|
|
Violation:
Dishware racks were set on the deck and used as stands for soiled items.
|
|
Recommendation:
Provide and use deck stands for staging soiled items. Ensure there is a minimum 150 mm (6 inch) clearance between the deck and the deck stand.
|
|
|
Item No.:
33
|
|
Site:
Pantry-Deck 4 - Pantry #4
|
|
Violation:
The bulkhead behind the dishwash machine was soiled with dirt residue.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Pantry-Deck 3 - Pantry #3
|
|
Violation:
The drain hose from the dishwash machine was draped on the deck, making cleaning difficult.
|
|
Recommendation:
Elevate the drain hose so there is at least a 150 mm (6 inch) inch clearance for cleaning the deck below.
|
|
|
Item No.:
33
|
|
Site:
Bar-Topsider Bar
|
|
Violation:
The material used for the deckhead above the pantry and the service side was made of sailcloth and was secured by ropes. The surface of the sailcloth was lightly soiled.
|
|
Recommendation:
Ensure that bulkheads and deckheads have smooth, hard finishes, and light colored surfaces. Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Bar-Deck 3 - Pool Bar
|
|
Violation:
Several deck tiles were fractured, making cleaning difficult.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|
|
Item No.:
37
|
|
Site:
Galley-Top Side Galley - Hot Galley and Dishwash
|
|
Violation:
The staff working in both the hot galley and dishwash pantry were perspiring profusely around the head and neck due to the high heat and humidity produced in these two areas.
|
|
Recommendation:
Ensure that all food preparation, warewashing, and toilet rooms have sufficient ventilation to keep them free of excessive heat, steam, condensation, vapors, obnoxious odors, smoke, and fumes.
|
|
|
Item No.:
39
|
|
Site:
Galley-Main Galley - Bakery/Pastry
|
|
Violation:
One filth fly was noted in this area.
|
|
Recommendation:
Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.
|
|
|
Item No.:
40
|
|
Site:
Galley-Top Side Galley - Dishwash
|
|
Violation:
The open deck entry door to the dishwashing pantry was pinned open during operation, leaving open access to flying insects. This was during the end of the breakfast service during staging and transfer of the soiled dishes to cleaning, but it could be this door is pinned open during food service operations as well.
|
|
Recommendation:
Ensure that entry points where pests may enter the food areas are protected.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Deck 4 - Spa
|
|
Violation:
There was no means available for a person exiting the restroom to avoid bare hands contact with the door handle.
|
|
Recommendation:
Equip public toilet facilities so that persons exiting the toilet room are not required to handle the door with bare hands. This may be accomplished by methods such as locating paper towel dispensers at sinks and waste containers near the room door, installing mechanically operated doors, door removal, or other effective means.
|
|