Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Azura Cruise Line: P&O Cruises Inspection Date: 12/19/2010 Inspection Score: 97
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 06
Site: Potable Water-Halogen Analyzer Charts
Violation: The chart range was 0.0 to 10.0 mg/L (ppm).
Recommendation: Ensure that the halogen analyzer-chart recorder charts have a range of 0.0 to 5.0 mg/L (ppm) and have a recording period of 24 hours.
Item No.: 10
Site: DO NOT USE (whirlpool/spa)-Backwash
Violation: The whirlpool spas are backwashed daily on an automatic cycle, however the water is not viewed through the sight glass or discharge point to ensure that it is clear at the end of the cycle on a daily basis.
Recommendation: Ensure that granular filters are backwashed at least daily. Repeat backwashing, if necessary, until the water viewed through the sight glass or discharge point is clean flowing.
Item No.: 08
Site: Potable Water-
Violation: Maintenance was performed on potable water tanks 2 starboard (11/08), 7 port (11/3), and 10 starboard (11/5). There was no indication in the records that the tanks were flushed with potable water or otherwise de-chlorinated until the free residual halogen was < 5.00 mg/L (ppm).
Recommendation: Ensure that the disinfected parts of the system are flushed with potable water until the free residual halogen is at or below 5.00 mg/L (ppm).
Item No.: 08
Site: Potable Water-
Violation: Potable water tank 10 starboard was disinfected on 11/05. There was no indication in the records of the free residual halogen contact time.
Recommendation: Ensure that documentation of any inspection, cleaning, disinfection (including concentration and contact time of disinfectant), and flushing is maintained for 12 months and is available to the VSP for review during inspections.
Item No.: 06
Site: Potable Water-Microbiologic Monitoring
Violation: Two of the four monthly potable water samples sites were repeated each month.
Recommendation: Ensure that a minimum of four potable water samples per month are collected and analyzed for the presence of Escherichia coli and are collected randomly from locations on the forward, aft, upper, and lower decks of the vessel. Ensure that sample sites are changed each month.
Item No.: 08
Site: Potable Water-Cross-connection Control Program
Violation: The list of cross-connections and the backflow prevention device/method for each did not include the disabled passenger and passenger suite cabin showers, the Elro steamers, or the deck 8 (FZ6) Hydro Streamline dispenser in the trolley wash. These areas were all listed as "to be identified".
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 41
Site: Housekeeping-Outbreak Prevention and Response Plan
Violation: The plan did not include disinfecting the of the casino and photo galley public areas on a continuous basis until the proportion of gastrointestinal cases decreases to <2%. The plan is in active revision.
Recommendation: Ensure that when the cumulative proportion of cases of gastrointestinal illness among passengers or crew members is 2%, the infection control response includes cleaning and disinfecting all public areas, including handrails and restrooms, on a continuous basis until the proportion decreases to < 2%.
Item No.: 41
Site: Children Area-
Violation: The toilet room for disabled children did not have wipes or gloves.
Recommendation: Ensure that each toilet facility is provided with a supply of toilet tissue, disposable gloves, and sanitary wipes. Ensure that each toilet facility is provided with a supply of toilet tissue, disposable gloves, and sanitary wipes. Ensure that each toilet facility is provided with a supply of toilet tissue, disposable gloves, and sanitary wipes. Ensure that each toilet facility is provided with a supply of toilet tissue, disposable gloves, and sanitary wipes.
Item No.: 41
Site: Children Area-
Violation: Toys used in the child activity area are not cleaned and disinfected daily.
Recommendation: Ensure that toys used in the child-activity center are cleaned and disinfected daily. Ensure that surfaces that children touch with their hands are cleaned and disinfected at least daily with products labeled by the manufacturer for that purpose.
Item No.: 33
Site: Provisions-Fresh Fruit
Violation: There was a hole in the bulkhead across from the door, exposing the insulation. It appeared a plug was missing.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
Item No.: 33
Site: Provisions-General Frozen
Violation: There was a gap between the coving strip and the bulkhead juncture across from the door.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
Item No.: 33
Site: Provisions-Egg Room
Violation: There was a gap between the coving strip and the bulkhead juncture to the right of the door.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
Item No.: 20
Site: Preparation Room-
Violation: There were slotted fasteners in the food contact zone of the potato peelers.
Recommendation: Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
Item No.: 33
Site: Preparation Room-
Violation: There was a gap in the deck/bulkhead profile strip juncture to the left of refrigerator #D4VP5.
Recommendation: Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
Item No.: 21
Site: Galley-Deck 6 Soup Section
Violation: The door gasket inside the upper compartment of the hot holding unit next to refrigerator #D6MG17 was cracked.
Recommendation: Ensure that non-food contact equipment is maintained in good repair and proper adjustment including: (1) Equipment maintained in a state of repair and condition that meets the materials, design, construction, and operation specifications of these guidelines. (2) Equipment components such as doors, seals, hinges, fasteners, and kick plates are kept intact, tight, and adjusted in accordance with manufacturer's specifications.
Item No.: 24
Site: Galley-Deck 6 Potwash
Violation: The potwash machine final sanitizing rinse temperature gauge read 140°F, and the inspector's thermometer placed inside the machine read 150°F for two cycles. Staff stated that all items are placed through the potwash machine. The potwash machine was in active use at the time of the inspection. This was corrected.
Recommendation: In a mechanical operation, ensure that the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F), or less than: (1) For a stationary rack, single temperature machine, 74°C (165°F); or (2) For all other machines, 82°C (180°F); or (3) A utensil surface temperature of 71°C (160°F) as measured by an irreversible registering temperature indicator shall be achieved. (4) The maximum temperature of 90°C (194°F), does not apply to the high pressure and temperature systems with wand-type, hand-held, spraying devices used for the in-place cleaning and sanitizing of equipment such as meat saws.
Item No.: 21
Site: Buffet-Crew Mess
Violation: The sneeze guards adjacent to the plate dispensers on both serving lines were chipped along the side edges.
Recommendation:
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program