Cruise Ship: Seven Seas Mariner Cruise Line: Regent Seven Seas Inspection Date: 01/11/2011 Inspection Score: 99
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 06
Site: Potable Water-Production and Bunkering Chart Recorders
Violation: There was no documentation that the halogen analyzer-chart recorder was calibrated at the start of bunkering or production of potable water. According to the staff, calibration or a calibration check was performed at the start.
Recommendation: Ensure that halogen analyzer-chart recorders used in lieu of manual tests and logs are calibrated at the beginning of bunkering or production, and the calibration is recorded on the chart or in a log book.
Item No.: 08
Site: Potable Water-Black Water Room
Violation: The pipe to the black water tank rinsing hose was striped blue for potable water. According to the staff, this was technical water.
Recommendation: Ensure that non-potable freshwater flows through a completely different piping system and is identified with a different color.
Item No.: 08
Site: Potable Water-Beauty Salon
Violation: There was no air gap at the intermediate atmospheric vent on the backflow prevention device for the men's sauna. There was duct tape around the space between the vent and the drain pipe below.
Recommendation: Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
Item No.: 08
Site: Potable Water-
Violation: The backflow prevention devices in the engine changing room and laboratory sinks were listed on the cross-connection control program as located in the beauty salon. The staff explained these devices were misplaced on the list. This was corrected.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 08
Site: Potable Water-Engine Room
Violation: There was no air gap at the left side backwash mineralizer. The distance between the pipe and the funnel was less than two times the diameter of the pipe.
Recommendation: Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
Item No.: 08
Site: Potable Water-Engine Room
Violation: The piping after a couple of the reduced pressure backflow prevention devices were striped blue for potable water. These backflow prevention devices were located at the right mineralizer and the supply expansion tank filling line for the swimming pool.
Recommendation: Ensure that non-potable freshwater flows through a completely different piping system and is identified with a different color.
Item No.: 08
Site: Potable Water-Beauty Salon
Violation: There were Watts N9 backflow prevention devices installed on the spray hoses at the hair washing stations. However, they were listed on the cross-connection control program as CA9C. The staff explained the CA9C backflow prevention devices were removed last month. The list was corrected.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 08
Site: Potable Water-Beauty Salon
Violation: There was a Watts N9 backflow prevention device installed at the port side hair washing station. However, it was listed on the cross-connection control program as A25-F. The list was corrected.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 08
Site: Potable Water-Beauty Salon
Violation: The backflow prevention devices installed in the technical area of the steam generator for the men's and women's sauna were not listed on the cross-connection control program. The list was corrected.
Recommendation: Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing.
Item No.: 21
Site: Buffet-La Veranda
Violation: The sneeze guard at the bread station was chipped along the bottom edge. This sneeze guard was scheduled to be replaced on the day of the inspection.
Recommendation: Ensure the sneeze guard is repaired and maintained in good condition.
Item No.: 21
Site: Buffet-Crew Mess Beverage Station
Violation: A water delivery line from the coffee machine was draped along the counter, making cleaning difficult. This was corrected.
Recommendation: Ensure the water delivery line is maintained off of the counter top.
Item No.: 27
Site: Galley-Beverage Station
Violation: The counter top below the coffee machine was soiled towards the back.
Recommendation: Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 28
Site: Dining Room-Compass Rose Waiter Station #16
Violation: Clean utensils were stored in a soiled drawer compartment. This was corrected.
Recommendation: Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
Item No.: 39
Site: Galley-Beverage Station
Violation: There were a few flies observed in the area.
Recommendation: Ensure that the presence of insects, rodents, and other pests is effectively controlled to minimize their presence in the food storage, preparation, service areas, warewashing, and utensil storage areas aboard a vessel.