Item No.:
16
|
|
Site:
Buffet-Deck 9 Starboard Cereal Counter
|
|
Violation:
There was a tray of individually wrapped butter out for lunch service. The internal temperatures ranged from 48°F to 53°F. These pieces of butter were taken from a tray containing butter inside undercounter refrigerator B15, located at the international counter/Deck 9. The internal temperature of the butter stored in this refrigerator measured between 48°F and 53°F. There was no assurance that the initial temperature of the butter was less than 41°F before being placed on time-control.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less. Ensure that cold potentially hazardous food is 41°F or less before being placed on time control.
|
|
|
Item No.:
08
|
|
Site:
Recreational Water Facilities-Mechanical Rooms
|
|
Violation:
There were several potable water supply lines in the mechanical rooms for the swimming pools and whirlpools that were striped blue after the reduced pressure zone (RPz) backflow prevention assemblies.
|
|
Recommendation:
Remove the blue striping after each Reduced Pressure zone (RPz) assembly.
|
|
|
Item No.:
20
|
|
Site:
Housekeeping-Deck 1 Pantry 1.4.05 Ice Machine
|
|
Violation:
The food contact surface of the ice cuber was rough and not easily cleanable.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
15
|
|
Site:
Housekeeping-Deck 1 Pantry 1.4.05 Ice Machine
|
|
Violation:
There was a light accumulation of a black powder in the water bath, along the removable white diffuser.
|
|
Recommendation:
Ensure that food is safe and unadulterated.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Deck 9 Main Whirlpool
|
|
Violation:
The anti-entrapment drain cover was cracked.
|
|
Recommendation:
Replace the anti-entrapment drain cover.
|
|
|
Item No.:
21
|
|
Site:
Bar-Deck 9 Multi-Flow Cabinet
|
|
Violation:
The carbonator/multi-flow unit was set on top of a stainless steel shelf above the syrup boxes. The carbonator/multi-flow unit could not be moved by one person, which prohibited proper cleaning around the unit. There was a small accumulation of water and a sticky substance on the shelf.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
27
|
|
Site:
Bar-Deck 9 Multi-Flow Cabinet
|
|
Violation:
The carbonator/multi-flow unit was set on top of a stainless steel shelf above the syrup boxes. The carbonator/multi-flow unit could not be moved by one person, which prohibited proper cleaning around the unit. There was a small accumulation of water and a sticky substance on the shelf.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
08
|
|
Site:
Bar-Multi-Flow/Carbonator Units
|
|
Violation:
There was no backflow prevention device protecting the non-carbonated potable water line that leads to the multi-flow hand-held spray nozzle.
|
|
Recommendation:
Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required.
|
|
|
Item No.:
33
|
|
Site:
Bar-Deck 9 Aquarius
|
|
Violation:
The deckhead on the worker side of the bar was constructed of sail cloth and ropes. This item was noted on the previous inspection.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are constructed and maintained for easy cleaning. Ensure that bulkheads and deckheads have smooth, hard finishes, and light colored surfaces.
|
|
|
Item No.:
36
|
|
Site:
Bar-Deck 9 Aquarius
|
|
Violation:
The light level at the counter and above the deck was not sufficient for cleaning.
|
|
Recommendation:
Ensure that the light intensity is at least 220 Lux (20 foot candles) in bars and at dining room waiter stations during periods of cleaning.
|
|
|
Item No.:
19
|
|
Site:
Buffet-Deck 9 Aft Storage Locker 9.2.17
|
|
Violation:
There were food and food related articles stored in locker 9.2.17, which had exposed lagging and pipes.
|
|
Recommendation:
Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 2 Coffee Station
|
|
Violation:
There were slotted fasteners and gaps in the food splash zone of the two coffee machines. The fasteners were soiled.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
29
|
|
Site:
Galley-Dishwash
|
|
Violation:
There were soiled plate covers placed directly on the handwash station, making the handwash station inaccessible.
|
|
Recommendation:
Ensure that handwashing facilities are used for no other purpose and are accessible at all times.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dishwash
|
|
Violation:
There were many broken and missing fingerlinks in the conveyor of the flight-type conveyor dishwashing machine. This machine was in use at the time of the inspection.
|
|
Recommendation:
Ensure that warewashing equipment is maintained in good repair and proper adjustment including: (1) Being maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; and (2) Maintaining water pressure, and water temperature measuring devices in good repair and ensuring their accuracy within the intended range of use.
|
|
|
Item No.:
28
|
|
Site:
Dining Room-Deck 2 Meridian Restaurant
|
|
Violation:
After the breakfast service, there were staff members placing soiled dishes, cups, and remnants of food in the clean areas of the waiter stations. There were clean items stored in this area.
|
|
Recommendation:
Ensure that cleaned equipment and utensils, laundered linens, and single-service and single-use articles are stored: (1) In a clean, dry location; (2) Where they are not exposed to splash, dust, or other contamination; and (3) At least 150 mm (6 inches) above the deck.
|
|
|
Item No.:
34
|
|
Site:
Galley-Deck 2 Pastry
|
|
Violation:
There was a leak at the spray nozzle located next to the stack ovens.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Food Service General-Undercounter Refrigerator Technical Compartments
|
|
Violation:
In the technical compartments of many of the undercounter refrigerators, there were gaps where the refrigeration piping penetrated the bulkheads.
|
|
Recommendation:
Seal the bulkhead/pipe penetrations.
|
|
|
Item No.:
34
|
|
Site:
Galley-Soup Station
|
|
Violation:
There was a leak at the faucet located over the soup kettles HG-BL2 and HG-BL5.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
37
|
|
Site:
Galley-Soup Station
|
|
Violation:
There was condensate dripping from the deckhead over the top cover of kettle HG-BL3. The staff was cooking ham stock in this kettle at the time of the inspection.
|
|
Recommendation:
Ensure that ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
|
|
|
Item No.:
34
|
|
Site:
Galley-Potwash
|
|
Violation:
There was a leak at the faucet of the three compartment sink.
|
|
Recommendation:
Ensure that a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
30
|
|
Site:
Galley-Deck 3 Aft-Starboard Coffee Pantry
|
|
Violation:
There was no waste receptacle at this handwash station.
|
|
Recommendation:
Provide a waste receptacle for the handwash station.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 3 Aft-Starboard Coffee Pantry
|
|
Violation:
There were slotted fasteners and gaps in the food splash zones of the coffee machines. There was a corroded slotted fastener and a gap suggesting a missing fastener. These conditions made cleaning difficult.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
38
|
|
Site:
Galley-Deck 3 Pastry
|
|
Violation:
There was a dough mixer that had been out of service since 22 September 2010.
|
|
Recommendation:
Repair, replace, or remove the dough mixer.
|
|
|
Item No.:
27
|
|
Site:
Galley-Deck 3 Pastry
|
|
Violation:
There was accumulated food residue by the top of the middle shaft of the dough mixer.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
21
|
|
Site:
Galley-Deck 3 Coffee Pantry
|
|
Violation:
The bread slicer was placed directly on the counter top and was not sealed to the counter or elevated on legs. This piece of equipment was heavy and not easily movable, making cleaning beneath difficult.
|
|
Recommendation:
Ensure that table-mounted equipment that is not easily movable is installed to allow cleaning of the equipment and areas underneath and around the equipment by being: (1) Sealed to the table; or (2) Elevated on legs.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 3 Coffee Pantry
|
|
Violation:
There were slotted fasteners in the food contact zone of the bread slicer, making it difficult to clean.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
26
|
|
Site:
Galley-Deck 3 Coffee Pantry
|
|
Violation:
A piece of lint was stuck in one of the blades of the previously cleaned bread slicer. It appeared that the lint was from a cleaning cloth.
|
|
Recommendation:
Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
24
|
|
Site:
Galley-Deck 3 Potwash
|
|
Violation:
The employee was not fully immersing the hotel pans and flat hotel sheets in the sanitizing hot water. The partial immersion also lasted for 16 to 20 seconds.
|
|
Recommendation:
In a manual operation, ensure that if immersion in hot water is used for sanitizing: (1) The temperature of the water is maintained at 77°C, (171°F) or above; and (2) The food-contact surface is immersed for at least 30 seconds.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Deck 9 Port Cereal Counter
|
|
Violation:
There was a tray with yogurt containers in undercounter refrigerator B2. The internal temperature of the yogurt was approximately 50°F. These items were discarded.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
29
|
|
Site:
Galley-Deck 9 Belvedere Hot Galley
|
|
Violation:
There was a waste bin placed in front of the handwash station, making it inaccessible. This item was corrected.
|
|
Recommendation:
Ensure that handwashing facilities are used for no other purpose and are accessible at all times.
|
|
|
Item No.:
24
|
|
Site:
Galley-Potwash
|
|
Violation:
The employee was not fully immersing the hotel pans in the sanitizing hot water.
|
|
Recommendation:
In a manual operation, ensure that if immersion in hot water is used for sanitizing: (1) The temperature of the water is maintained at 77°C, (171°F) or above; and (2) The food-contact surface is immersed for at least 30 seconds.
|
|
|
Item No.:
13
|
|
Site:
Other-Sanitizing Rinse Practices
|
|
Violation:
There were two different employees in two different potwash stations that were not fully immersing the washed utensils in the sanitizing rinse water, leaving parts of the utensils out of this sanitizing rinse. The staff stated that both employees were trained.
|
|
Recommendation:
Person in charge: Ensure that employees are properly sanitizing cleaned multiuse equipment and utensils before they are reused, through routine monitoring of solution temperature and exposure time for hot water sanitizing, and chemical concentration, pH, temperature, and exposure time for chemical sanitizing.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Liquor-Beverage Storage # 20
|
|
Violation:
The decks were soiled with a mixture of dust and remnants of old liquid under the pallets.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Beverage-Flour-Sugar Storage # 19
|
|
Violation:
The decks were soiled with a mixture of dust and remnants of old liquid under the pallets. Also, there were pieces of broken glass under the pallets.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Storage # 16
|
|
Violation:
The deck under a pallet holding cans of solid rhubarb (2.86 kg each) was soiled with what appeared to be syrup. The syrup appeared to have dripped from the top of some of the cans. These cans also had syrup on top. The staff explained that these cans had been provisioned that day and that they had an incoming inspection.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
16
|
|
Site:
Provisions-Cool Storage # 7
|
|
Violation:
There were three pallets holding 24 cases of eggs (30 dozen eggs per case) located outside of this cooler during provisioning. The temperatures of these eggs, taken from different boxes throughout the pallets, were measured between 48°F and 60°F. There were several other pallets of these same eggs placed inside the cooler and the temperatures of these eggs, taken from different boxes throughout the pallets, were measured between 48°F and 60°F as well. It was also unclear at what temperature these eggs were received and accepted for introduction into the ship.
|
|
Recommendation:
Ensure that receiving temperatures are as follows: (1) Refrigerated, potentially hazardous food shall be at a temperature of 7°C (45°F) or below when received. (3) Potentially hazardous food that is cooked and received hot shall be at a temperature of 60°C (140°F) or above. (4) A food that is labeled frozen and shipped frozen by a food-processing plant shall be received frozen. (5) Upon receipt, potentially hazardous food shall be free of evidence of previous temperature abuse. Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
20
|
|
Site:
Preparation Room-Deck B
|
|
Violation:
There was a slotted fastener in the food contact surface of the potato peeler unit located at the far right of the potato peeler station.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|
|
Item No.:
26
|
|
Site:
Preparation Room-Deck B
|
|
Violation:
There was food residue in the seams in the food contact areas of the previously cleaned potato peeler unit located at the far right of the potato peeler station.
|
|
Recommendation:
Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
16
|
|
Site:
Provisions-Fresh Food and Vegetable Cooler
|
|
Violation:
The cut spinach and lettuce had internal temperatures measured at 54°F. The ambient temperature of this cooler was measured at 63°F.
|
|
Recommendation:
Except during preparation, cooking, or cooling, or when time is used as the public health control, ensure that potentially hazardous food is maintained: (1) At 60°C (140°F) [roasts 54°C (130°F)] or above, or (2) At 5°C (41°F) or less.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Fresh Food and Vegetable Cooler
|
|
Violation:
The deck was soiled with a mixture of wet food residue.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
15
|
|
Site:
Provisions-Fresh Food and Vegetable Cooler
|
|
Violation:
There was water dripping from melting ice that was covering some vegetables, such as fresh broccoli. This ice comes as a cooling aide inside the fresh produce boxes. This water was wetting boxes containing food and soiling the deck.
|
|
Recommendation:
Ensure that food packages are in good condition and protect the integrity of the contents so that the food is not exposed to adulteration or potential contaminants. Ensure that canned goods with dents on end or side seams are not used.
|
|
|
Item No.:
21
|
|
Site:
Buffet-Deck 9 / Belvedere Countertops
|
|
Violation:
There were fractures and chipped pieces along the black countertops, which made cleaning difficult. In addition, where the countertop junctures met the bulkhead, there was loose and missing sealant.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment and utensils are designed and constructed to be durable and to retain their characteristic qualities under normal use conditions. Ensure that nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Deck 9 / Belvedere Countertops
|
|
Violation:
There was an accumulation of dirt and food residue along some of the fractures in the countertops.
|
|
Recommendation:
Ensure that nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
19
|
|
Site:
Galley-Soup Station
|
|
Violation:
There was condensate dripping from the deckhead over the top cover of kettle HG-BL3. The staff was cooking ham stock in this kettle at the time of the inspection.
|
|
Recommendation:
Ensure that food is protected from contamination by storing the food: (1) In a clean, dry location; (2) Where it is not exposed to splash, dust, or other contamination; and (3) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
26
|
|
Site:
Bar-Multi-Flow/Carbonator Units
|
|
Violation:
Several of the large multi-flow/carbonator units had copper tubing inside. It could not be determined if copper was used between the carbonator tanks and the backflow prevention devices.
|
|
Recommendation:
Ensure that copper and copper alloys such as brass are not used in contact with a food that has a pH below 6 such as vinegar, fruit juice, or wine or for a fitting or tubing installed between a backflow prevention device and a carbonator.
|
|
|
Item No.:
26
|
|
Site:
Galley-Deck 2 Coffee Station
|
|
Violation:
There were slotted fasteners and gaps in the food splash zone of the two coffee machines. The fasteners were soiled.
|
|
Recommendation:
Ensure that food-contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
20
|
|
Site:
Preparation Room-Deck B
|
|
Violation:
There were seams in the food contact areas of the potato peeler unit located at the far right of the potato peeler station.
|
|
Recommendation:
Ensure that materials used in the construction of multiuse utensils and food-contact surfaces of equipment are: (1) Durable, corrosion-resistant, and nonabsorbent; (2) Sufficient in weight and thickness to withstand repeated warewashing; (3) Finished to have a smooth, easily cleanable surface; and (4) Resistant to pitting, chipping, crazing, scratching, scoring, distortion, and decomposition.
|
|