|
|
|
Item No.:
33
|
|
Site:
Provisions-Dry Storage
|
|
Violation:
The deck under the pallets was soiled with an accumulation of dust and debris.
|
|
Recommendation:
Ensure that decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas, are cleaned as often as necessary.
|
|
|
Item No.:
21
|
|
Site:
Food Service General-Stove Tops and Grills
|
|
Violation:
There were unsealed openings or peeling/missing sealant by the grease chutes of the stove tops, flat grills, and grooved grills.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
15
|
|
Site:
Galley-Hot Galley
|
|
Violation:
There was a hotel pan with a 2-inch long hair mixed with the seafood crock pot. The hair was in direct contact with the food. This item was discarded.
|
|
Recommendation:
Ensure that food is safe and unadulterated.
|
|
|
Item No.:
20
|
|
Site:
Room Service-Deck 5
|
|
Violation:
There were slotted fasteners in the food splash zone of the espresso coffee machine.
|
|
Recommendation:
Remove the slotted fasteners and replace with smooth, low-profile, non-slotted fasteners.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Port Bunker Station
|
|
Violation:
There was no intermediate vent on the double check valve for the international shore connection. The vent was installed on the similar connection in the starboard bunker station.
|
|
Recommendation:
Ensure that backflow preventers are installed when air gaps are impractical or when water under pressure is required. Ensure that the double check valve located at the international shore connection is equipped with an intermediate vent.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Program
|
|
Violation:
The backflow prevention devices for the showers and toilets for passenger cabins were combined by deck on the list of backflow prevention devices. However, the total number of devices was not included.
|
|
Recommendation:
Ensure that the cross-connection control program includes at minimum: a complete listing of cross-connections and the backflow prevention method/device for each, so that there is a match to the plumbing system component and location, and an inspection frequency. Ensure that air-gaps are included in the listing. Ensure that the total number of backflow prevention devices is included in the listing of backflow prevention devices when these are combined by deck in the cross-connection control program.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Medical
|
|
Violation:
There was no air gap below the vent on the backflow prevention device for the sluice. This was corrected by creating an air gap below this vent.
|
|
Recommendation:
Ensure that air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 3 cm (1 inch).
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-Connection Control Program
|
|
Violation:
The list of backflow prevention devices included only two devices for each passenger cabin. There were several suites that had an additional backflow prevention device for the hose at the whirlpool tub, but this device was not included.
|
|
Recommendation:
Update the listing of backflow prevention devices in the cross-connection control program.
|
|
|
Item No.:
11
|
|
Site:
Medical-
|
|
Violation:
On 17 December 2010, there was a bar steward with gastrointestinal illness who waited 24 hours between his first symptom and reporting to medical.
|
|
Recommendation:
Ensure that food employees who have conditions or symptoms of boils, open sores, infected wounds, diarrhea, jaundice, fever, vomiting, sore throat with fever, or discharges from the nose or mouth report these conditions or symptoms to the vessel's medical staff and are restricted from working with exposed food, warewashing, clean equipment, utensils, and linens, and unwrapped single-service and single-use articles.
|
|
|
Item No.:
30
|
|
Site:
Bar-Club Bar
|
|
Violation:
The handwash station had handwashing directions, but did not have a "wash hands often" sign.
|
|
Recommendation:
Ensure that a sign stating "WASH HANDS OFTEN" in a language that the food employees understand is posted over handwashing sinks.
|
|
|
Item No.:
29
|
|
Site:
Pantry-Club Bar
|
|
Violation:
The water at the handwash station was measured at greater than 127°F. The temperature could not be adjusted by the user.
|
|
Recommendation:
Ensure that handwashing sinks are equipped to provide water at a temperature of at least 43°C (110°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, where the user cannot make temperature adjustments, ensure that the temperature provided to the user does not exceed 52°C (125°F).
|
|
|
Item No.:
21
|
|
Site:
Bar-Casino Bar
|
|
Violation:
There were unsealed bulkhead penetrations in the undercounter multi-flow cabinet.
|
|
Recommendation:
Ensure that nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
|
|
|
Item No.:
33
|
|
Site:
Bar-Casino Bar
|
|
Violation:
The locking pin insert was missing and there were several holes in the door frame of the door between the bar and the pantry.
|
|
Recommendation:
Ensure that decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas, are maintained in good repair.
|
|