Item No.:
40
|
|
Site:
Integrated Pest Management-
|
|
Violation:
The time of active monitoring for pests was not recorded. Also, there was no record of follow-up inspections when pests were identified.
|
|
Recommendation:
Record the time of the active monitoring inspections in the log. When pests are noted during an inspection, ensure the log includes action taken and follow-up inspection results.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Antientrapment
|
|
Violation:
The drain covers in the pool and whirlpool were not stamped with all of the information required by ASME A112.19.8 and the 2011 VSP Operations Manual. New covers had been ordered.
|
|
Recommendation:
For RWFs with gravity drainage and a single blockable drain or multiple drains less than 3 feet apart, provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover and a gravity drainage system. Ensure the testing of manufactured drain covers is by a nationally or internationally recognized testing laboratory. Ensure the following information is stamped on each manufactured antientrapment drain cover: (1) certification standard and year; (2) type of drain use (single or multiple); (3) maximum flow rate (in gallons or liters per minute); (4) type of fitting (suction outlet); (5) life expectancy of cover; (6) mounting orientation (wall, floor, or both); (7) manufacturer's name or trademark; and (8) model designation.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Outbreak Prevention and Response Plan (OPRP)
|
|
Violation:
The OPRP did not include procedures for returning the vessel to normal operating conditions following an outbreak.
|
|
Recommendation:
Ensure each vessel has a written OPRP that details standard procedures and policies to specifically address AGE onboard. Include the following in the written OPRP: (5) Procedures for returning the vessel to normal operating conditions after an outbreak.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Production pH Analyzer
|
|
Violation:
There was no record of the calibration of the pH analyzer for the chart-recorder.
|
|
Recommendation:
Calibrate at the beginning of bunkering or production when halogen and pH analyzer-chart recorders are used in lieu of manual tests and logs. Ensure the calibration is recorded on the chart.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Bunker Shore-side Water Halogen Test
|
|
Violation:
The record of the halogen level of the shore-side water supply was from onboard the vessel and not from the shore-side water prior to treatment.
|
|
Recommendation:
Conduct a free halogen residual and pH test on the shore-side water supply before starting the potable water bunkering process to establish the correct halogen dosage. Record the results of the pretest and ensure they are available for review during inspections.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Bunker pH
|
|
Violation:
There was no hourly monitoring of the pH during bunkering of potable water.
|
|
Recommendation:
After the free residual halogen level of at least 2.0 mg/L (ppm) and pH level not exceeding 7.8 have been reached, monitor the free residual halogen and pH at least hourly during the bunkering of potable water.
|
|
|
Item No.:
33
|
|
Site:
Galley-Cold Galley
|
|
Violation:
There was a hole leading to a void space in the support column behind the toaster.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
33
|
|
Site:
Galley-Hot Galley
|
|
Violation:
In the walk-in refrigerator, the deckhead-mounted smoke detector cover was loose, exposing gaps.
|
|
Recommendation:
Secure the smoke detector to the deckhead.
|
|
|
Item No.:
27
|
|
Site:
Galley-Hot Galley
|
|
Violation:
The technical compartment below the utility sink was heavily soiled.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
36
|
|
Site:
Food Service General-Lighting
|
|
Violation:
The light intensity was below 110 lux behind and around many pieces of deck- and counter-mounted equipment. This was observed in areas such as behind ice machines, behind the flight-type warewash machine, and to the right of the deck oven in the pastry/bakery.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
21
|
|
Site:
Pantry-Top Side
|
|
Violation:
Potable water delivery lines and electrical cords from the coffee machines were draped across the counter top, making cleaning difficult.
|
|
Recommendation:
Remove the delivery lines and electrical cords from the counter tops.
|
|
|
Item No.:
40
|
|
Site:
Pantry-Pantry 5
|
|
Violation:
The door leading to the pantry where clean utensils were stored was fully open upon inspection. This area was on an open deck, but was not in operation. The door was immediately closed.
|
|
Recommendation:
Protect entry points where pests may enter the food areas.
|
|
|
Item No.:
33
|
|
Site:
Bar-Piano Bar
|
|
Violation:
There was a gap leading to a void space where the right support hook for the shutter doors penetrated the deckhead.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning.
|
|
|
Item No.:
36
|
|
Site:
Dining Room-Main Dining Room
|
|
Violation:
The maximum light intensity was less than 220 lux at the waiter stations.
|
|
Recommendation:
In bars and dining room waiter stations, provide 220 lux (20 foot candles) light intensity during cleaning operations.
|
|