|
|
|
Item No.:
06
|
|
Site:
Potable Water-Microbiological Sampling Procedures
|
|
Violation:
The ship was using an 18-hour E.coli test kit. When asked about the procedures crew stated that after the water sample was taken the reagent was mixed in and then immediately placed into the incubator. The result was then read after 18 hours. However, the 18-hour test the ship was using required the sample to be warmed in a water bath for 20 minutes before being placed in the incubator. Staff was not aware of this step and did not have a water bath.
|
|
Recommendation:
If water samples are collected and analyzed by the vessel for the presence of E. coli, analyze the samples using a method accepted in Standard Methods for the Examination of Water and Wastewater. Ensure test kits, incubators, and associated equipment are operated and maintained in accordance with the manufacturers? specifications.
|
|
|
Item No.:
02
|
|
Site:
Medical-Reportable Case Definition
|
|
Violation:
A passenger reported to the medical center on 27 November with 1 episode of diarrhea and no other symptoms. Antidiarrheal medication was dispensed and the passenger was listed as nonreportable. A crew member reported to the medical center on 26 November with 1 episode of diarrhea and no other symptoms. Antidiarrheal medication was dispensed and the crew member was listed as nonreportable. In discussion with the doctor it was determined this amount of diarrhea was above normal for each individual but they were deemed nonreportable cases because each individual had less than 3 episodes each within a 24 hour period.
|
|
Recommendation:
Ensure a reportable case of AGE is a case reported to the master of the vessel, the medical staff, or other designated staff by a passenger or a crew member and meets the case definition based on the following symptoms: (1) Diarrhea (three or more episodes of loose stools in a 24 hour period or what is above normal for the individual. See section 4.1.2.1.3, illness symptoms); or (2) vomiting and one additional symptom including one or more episodes of loose stools in a 24-hour period, or abdominal cramps, or headache, or muscle aches, or fever (temperature of greater than or equal to 38°C [100.4°F]).
|
|
|
Item No.:
44
|
|
Site:
Medical-Reportable Case Definition
|
|
Violation:
The doctor was not aware the updated definition of a reportable case included 3 or more episodes of loose stools in a 24 hour period or what is above normal for the individual. The old definition from the 2005 VSP Operations Manual that did not include 'or what is above normal for the individual' was posted by the doctor's computer.
|
|
Recommendation:
Ensure the supervisor or person in charge of medical operations related to AGE on the vessel demonstrates to VSP-during inspections and on request-knowledge of medical operations related to AGE, is able to demonstrate this knowledge by compliance with Section 4 of the VSP 2011 Operations Manual or by responding correctly to the inspector's questions as they relate to the specific operation, and properly trains employees to comply with Section 4 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
41
|
|
Site:
Medical-Public Toilet
|
|
Violation:
The public toilet room did not have a sign advising users to wash hands and a sign advising users to use a paper towel to open the door when exiting.
|
|
Recommendation:
Provide the passenger and crew public toilets with a handwashing station that includes: (4) A sign advising users to wash hands. Post a sign advising users of toilet facilities to use hand towel, paper towel, or tissue to open the door unless the exit is hands free.
|
|
|
Item No.:
44
|
|
Site:
Potable Water-Microbiological Sampling Procedures
|
|
Violation:
The ship was using an 18-hour E.coli test kit. When asked about the procedures crew stated that after the water sample was taken the reagent was mixed in and then immediately placed into the incubator. The result was then read after 18 hours. However, the 18-hour test the ship was using required the sample to be warmed in a water bath for 20 minutes before being placed in the incubator. Staff was not aware of this step and did not have a water bath.
|
|
Recommendation:
Ensure staff follows the manufacturer's instructions for completing an E. coli test.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Production Pipe Striping
|
|
Violation:
The distillate water line from the evaporators to the mineralizer and the permeate water line from the reverse osmosis to the mineralizer were not striped blue/gray/blue.
|
|
Recommendation:
Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers. Do not stripe or paint potable water lines after reduced pressure assemblies as potable water. Uniquely identify all refrigerant brine lines in all galleys, pantries, and cold rooms to prevent cross-connections.
|
|
|
Item No.:
41
|
|
Site:
Other-Engine Control Room
|
|
Violation:
The crew toilet room did not have a sign advising users to wash hands and a sign advising users to use a paper towel to open the door when exiting.
|
|
Recommendation:
Provide the passenger and crew public toilets with a handwashing station that includes: (4) A sign advising users to wash hands. Post a sign advising users of toilet facilities to use hand towel, paper towel, or tissue to open the door unless the exit is hands free.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Data Logger
|
|
Violation:
The chlorine and pH values for all 6 RWFs were displayed in real time on a computer in the engine control room. However, the values were only recorded in the computer every hour. After the computer compiled a week's worth of data the data was exported to an excel spreadsheet on a different computer. The excel spreadsheet could be edited by the user. Moreover, the chlorine values exported to the excel spreadsheet were recorded at 1 hour intervals and the pH values were recorded at every 4 hours. The original data on the first computer was only stored for a maximum of 21 days.
|
|
Recommendation:
Install chart recorders or electronic data loggers with security features that record pH and halogen measurements for each individual RWF. Ensure the sample line for the analyzer probe (monitoring) is either directly from the RWF or on the return line from each RWF and before the compensation tank. Install appropriate sample taps for analyzer calibration. In the event of equipment failure, measure free residual halogen and pH by a manual test kit at the RWF or return line at least hourly for whirlpool spas, spa pools, children?s pools, and wading pools and every 4 hours for all other RWFs. Record manual readings on a chart or log, retain for at least 12 months, and ensure that they are available for review during inspections. Complete repairs on malfunctioning halogen analyzer-chart recorders within 30 days of equipment failure. Provide an audible alarm in a continuously occupied watch station to indicate low and high free halogen and pH readings in each RWF. If an electronic data logger is used in lieu of a chart recorder, ensure it has certified data security features. Retain logs and charts for 12 months and ensure that they are available for review during inspections.
|
|
|
Item No.:
09
|
|
Site:
Recreational Water Facilities-Main Pool
|
|
Violation:
The pool had a waterfall feature that classified it as an interactive water facility. The chlorine levels measured by the inspector were 1.19 ppm and 1.19 ppm. The levels measured by the crew were 1.26 ppm and 1.22 ppm. The pool was open during the inspection and was immediately closed.
|
|
Recommendation:
Maintain a free residual halogen in recirculated RWFs in the following ranges: ; (4) interactive RWFs (activity pools), between 2.0 and 5.0 mg/L (ppm).
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Turnover Rates
|
|
Violation:
No calculated turnover rates for each individual RWF were provided to the inspector.
|
|
Recommendation:
For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters. Design recirculation systems and equipment, including chemical control equipment, UV disinfection systems, filter, and pumps to maintain adequate water chemistry control while operating at the following minimum turnover rates: (1) swimming pool (VSP 2005 Construction Guidelines or earlier): 6 hours; (2) swimming pool (VSP 2011 Construction Guidelines or later): 4 hours; (3) children's pool: 0.5 hours; (4) wading pool: 1 hour; (5) whirlpool spa: 0.5 hours; (6) spa pool: 2 hours; (7) interactive RWF or activity pool less than 610 millimeters (24 inches) deep: 1 hour; (8) interactive RWF or activity pool greater than 610 millimeters (24 inches) deep: 2 hours; and (9) baby-only water facility: 0.5 hours. Ensure an RWF slide that is combined with a pool has a turnover rate that matches the rate for the pool.
|
|
|
Item No.:
44
|
|
Site:
Recreational Water Facilities-Pool Classification and Turnover Rate
|
|
Violation:
The main pool was operated as a normal swimming pool (CL range 1 ppm- 5 ppm) and not as an interactive water facility (2 ppm- 5 ppm) which it was determined to be upon inspection. No turnover rates were calculated to be reviewed to determine if the turnover rate met the interactive water facility limit (2 hours).
|
|
Recommendation:
Ensure the supervisor or person in charge of recreational water operations on the vessel demonstrates to VSP?during inspections and on request ? knowledge of recreational water operations, is able to demonstrate this knowledge by compliance with Section 6 of the VSP 2011 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 6 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Lower Far Point Records
|
|
Violation:
The chlorine residual level was below 0.2 ppm from 11AM on 19 November until 5AM on 20 November. According to staff an alarm was installed on the system and was set to activate once the chlorine residual level fell below 0.2 ppm, but it could not be determined if the alarm sounded during this interval.
|
|
Recommendation:
Ensure records from the halogen analyzer-chart recorder verifies the free residual halogen of between 0.2 mg/L (ppm) and 5.0 mg/L (ppm) in the water distribution system for at least 16 hours in each 24 hour period since the last inspection of the vessel.
|
|
|
Item No.:
31
|
|
Site:
Pantry-Housekeeping Pantries
|
|
Violation:
All four deck pantries had chemical dispensers installed on the bulkhead and a biological drain cleaning dispensing station under the handwash station. The bulkhead mounted chemical dispenser included a nano surface maintenance cleaner, an acid bathroom cleaner, an all-purpose cleaner, and an order spray. All these chemicals were used by the hotel stewards to clean the cabins. According to staff none of the chemical were used to clean surfaces in the pantries. No food production occured in the pantries but bottled water, champaigne, and clean wine glasses were stored in the pantries. In addition, a yellow container of used sharps collected from the cabins was stored soiled side of the counter next to soiled dishes and glasses.
|
|
Recommendation:
Ensure only poisonous or toxic materials that are required for the operation and maintenance of a food area of the vessel, such as for the cleaning and sanitizing of equipment and utensils and the control of insects and rodents, are allowed in the food areas of the vessel.
|
|
|
Item No.:
42
|
|
Site:
Children Area-Diaper Changing
|
|
Violation:
The diaper changing table pad had splash marks on it and dust in the folds of the plastic that showed incomplete cleaning. The soiled diaper unit had old soil in the disposal chute.
|
|
Recommendation:
Clean and disinfect diaper changing facilities daily and when soiled during use.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Deck 9 - Calypso Show Galley
|
|
Violation:
A slight layer of dust was noted on the decorative pieces on the buffet display above where open food was being served.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Deck 9 - Calypso Aft Beverage Station
|
|
Violation:
Milk in the bulk milk dispenser that was listed on the time control plan and labeled as a 'Time Control' unit had a time label on the milk showing 0700 - 1100 but the time control plan listed the discard time for all food as 1000.
|
|
Recommendation:
Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Deck 9 - Calypso Fruit Station
|
|
Violation:
A green cutting board being used at the fresh fruit station was severely scored with knife marks making it difficult to clean.
|
|
Recommendation:
Ensure surfaces such as cutting boards that are subject to scratching and scoring are resurfaced if they no longer can be effectively cleaned and sanitized, or discarded if they are not capable of being resurfaced.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 10 - Pool Grill
|
|
Violation:
Coated metal serving pans with cast iron-base material were found to be chipping along the edge. Spots of rust were showing along the edges of several pans examined.
|
|
Recommendation:
Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition. Ensure cast iron is not used for utensils or food contact surfaces of equipment.
|
|
|
Item No.:
33
|
|
Site:
Bar-Deck 8 - Aida Bar
|
|
Violation:
The flanges around the water supply lines to the ice machines were incomplete leaving holes to the interior of the bulkhead.
|
|
Recommendation:
Ensure bulkheads in food preparation areas are maintained in good repair.
|
|
|
Item No.:
16
|
|
Site:
Bar-Deck 8 - Aida Bar / Deck 7 Ocean Bar
|
|
Violation:
The time control plan for dairy items was not posted in either bar. The laminated plan was stored in a folder in the cleaning lockers. The plans were posted while the inspector was in the areas. In addition, the milk holding unit on the coffee machine in the Ocean Bar was not labeled as a 'Time Control' unit.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such).
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 8 - Rossini Galley / Main Galley - Potwash
|
|
Violation:
A large blue cutting board in clean storage was severely scored from knife marks.
|
|
Recommendation:
Ensure surfaces such as cutting blocks and boards that are subject to scratching and scoring are resurfaced if they no longer can be effectively cleaned and sanitized, or discarded if they are not capable of being resurfaced.
|
|
|
Item No.:
08
|
|
Site:
Galley-Deck 8 - Main Galley - Hot Galley
|
|
Violation:
The backflow preventer on the water supply line to the combination steamer oven #MB-450-2-Q8 was continuously leaking from the air relief holes indicating a malfunction of the valve. The plumber was replacing the backflow preventer before the team left the area.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
22
|
|
Site:
Buffet-Deck 8 - Market Restaurant
|
|
Violation:
The wiping cloth solution being used outside the Show Galley station was severely soiled with food debris and grease. This was immediately changed.
|
|
Recommendation:
Ensure the sanitize solutions are maintained clean.
|
|
|
Item No.:
39
|
|
Site:
Buffet-Deck 2 - Crew Mess - Beverage Station
|
|
Violation:
Four fruit flies were found on a milk dispenser adjacent to an out of order juice machine. The mess was closed at the time of the inspection. The juice machine and the overflow drain were being cleaned as the inspection team left the area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food service areas.
|
|