Cruise Ship: Crystal Symphony Cruise Line: Crystal Cruises LTD Inspection Date: 05/09/2015 Inspection Score: 96
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 07
Site: Potable Water-Engine Room - Production
Violation: A hose was connected from the potable water line to the chlorine drum adjacent to the production chlorine injection point, and no backflow prevention device was installed. The hose was immediately removed.
Recommendation: Ensure the potable water distribution system is maintained free of cross-connections.
Item No.: 08
Site: Potable Water-Engine Room - Production
Violation: The reduced pressure backflow preventer, adjacent to the reverse osmosis unit, was continuously dripping water from the atmospheric vent, indicating the device may be failed.
Recommendation: Maintain backflow prevention devices in good repair.
Item No.: 08
Site: Potable Water-Tank Maintenance Records
Violation: The disinfectant contact time was not recorded for two potable water tank (FWD 2 & 9) maintenance records. The disinfectant concentration was not recorded for one potable water tank (FWD 1) maintenance record. The halogen residual value was not recorded for seven potable water tank (FWD 1, 2, 6, 7, 8, 9, & 10) maintenance records. Staff indicated all the potable water tanks were disinfected according to the procedure outlined in the VSP Operations Manual, but this was only documented properly for three potable water tanks.
Recommendation: Maintain documentation of all inspections, maintenance, cleaning, and disinfection for 12 months and ensure it is available for review during inspections. Ensure records include a method of disinfection, concentration and contact time of the disinfectant, and a halogen value of less than or equal to 5 ppm before the tank is put back into service.
Item No.: *
Site: Recreational Water Facilities-Chart Records
Violation: The whirlpool chart records were scaled 0-5 ppm, and staff indicated they were using the 0-14 pH scale to record the bromine residual levels and it was appropriately calibrated.
Recommendation: Dual-scale halogen analyzer-chart recorder charts used in recreational water facilities must be able to measure the full range of halogen/pH of the facility type to which the chart is installed.
Item No.: 10
Site: Recreational Water Facilities-Whirlpool Safety Sign
Violation: The whirlpool safety sign did not advise caution against use by children.
Recommendation: In addition to the safety sign requirements in section 6.7.1.1.1, install a sign at each whirlpool spa and spa pool entrance listing precautions and risks associated with the use of these facilities. Include, at a minimum, cautions against use by the following: (3) pregnant women, elderly persons, and children.
Item No.: 20
Site: Pantry-Deck 10 -Midship
Violation: Slotted fasteners were observed in the food contact area of the espresso machine.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 16
Site: Pantry-Deck 10 -Midship
Violation: Three individual containers of yogurt, stored inside the upright refrigerator, had internal food temperatures between 44° and 46°F. The yogurts were discarded and staff were advised to lower the temperature of the unit and evaluate the remaining potentially hazardous food items in the refrigerator.
Recommendation: Maintain potentially hazardous foods at 5°C (41°F) or less.
Item No.: 36
Site: Pantry-Deck 10 -Midship
Violation: The light intensity was less than 110 lux behind the ice machines in the pantry. This was noted on the last inspection, and staff reported the lighting issue was for all deck pantries, and there was a work order in place to address the lighting.
Recommendation: Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
Item No.: 24
Site: Galley-Main Galley - Dishwash Starboard
Violation: The in-use flight-type conveyor dishwashing machine had a final rinse manifold temperature below the minimum 180 °F and a plate level final rinse temperature of 157 °F after several tests. Staff repaired the machine and it was re-tested to show both manifold and plate level temperatures in the proper range.
Recommendation: In a mechanical operation, ensure the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F) or less than: (1) 74°C (165°F) for a stationary rack, single-temperature machine; (2) 82°C (180°F) for all other machines. Ensure the utensil surface temperature is not less than 71°C (160°F) as measured by an irreversible registering temperature indicator.
Item No.: 24
Site: Galley-Main Galley - Dishwash Starboard
Violation: The in-use conveyor glass washing machine had a final sanitizing rinse manifold temperature of 148 °F according to the mounted temperature gauge, and a dish level final sanitizing rinse temperature of only 145 °F. Staff repaired the machine immediately and the re-tests were above the minimum 160 °F required at the plate surface.
Recommendation: In a mechanical operation, ensure the temperature of the fresh hot water sanitizing rinse as it enters the manifold is not more than 90°C (194°F) or less than: (1) 74°C (165°F) for a stationary rack, single-temperature machine; (2) 82°C (180°F) for all other machines. Ensure the utensil surface temperature is not less than 71°C (160°F) as measured by an irreversible registering temperature indicator.
Item No.: 08
Site: Galley-Main Galley - Dishwash Starboard
Violation: During activation of the final rinse cycle for the in-use conveyor glass washing machine the atmospheric vacuum breaker installed on the supply pipe leaked heavily and water was pooling on the top exterior of the machine.
Recommendation: Maintain backflow prevention devices in good repair.
Item No.: *
Site: Galley-Main Galley - Water Station
Violation: The bottle water treatment system installed in the galley for orders in the dining room utilized a tall bottle with a narrow opening which made it difficult to ensure the entire contents would receive a full spray in each of the standard conveyor dishwash machine compartments for wash, rinse and final rinse. A container such as a carafe should be considered with a wider opening for pouring.
Recommendation:
Item No.: 26
Site: Galley-Main Galley - Hot Galley
Violation: An small electric handheld blender with food residue around and on the blade was stored as clean in a cabinet with other clean items.
Recommendation: Ensure food only contacts surfaces of equipment and utensils that are cleaned and sanitized. Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 20
Site: Galley-Main Galley - Pot Wash
Violation: Two long-handled strainers found among the clean pots and pans had heavy damage to the metal strainer and multiple broken welds from previous repairs. The split metal where the strainer center attached to the outer ring was very sharp and difficult to clean. Both strainers should be replaced.
Recommendation: Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 33
Site: Dining Room-Crystal Dining Room - Waiter Stations
Violation: Most of the deckhead surfaces directly above the waiter stations had a raised painted surface that was rough and very difficult to clean. Some of the triangle shaped island stations had old dark brown food residue stained into the paint.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary. Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Ensure bulkheads and deckheads have smooth, hard finishes and light colored surfaces.
Item No.: 40
Site: Integrated Pest Management-IPM - Incoming Shipments
Violation: The incoming shipments for the engine supplies were inspected, according to staff, but there was nothing recorded in the provisions loading log regarding this inspection or the results.
Recommendation: Routinely inspect incoming shipments of food and all other supplies for evidence of insects, rodents, and other pests. Maintain a record of these inspections onboard the vessel and make the record available for review during inspections.
Item No.: 21
Site: Buffet-Lido Cafe
Violation: The port and starboard side carving stations had a gap present along the underside of the grease pan housing where the grease drain pipe penetrated. The same condition was found at the aft grill station on the underside of the flat grill grease pan housing, where the drain pipe penetrated.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 36
Site: Other-Ice Cream Bar
Violation: The artificial light level over the back bar ice cream cone making and topping area was not fitted with deckhead light fixtures and relied only on sunlight. The light level was not able to be adjusted to a minimum 220 lux for cleaning.
Recommendation: Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
Item No.: 33
Site: Other-Trident Grill
Violation: A layer of dust had accumulated on the deckhead directly over the front preparation counter and surrounding the deckhead vent supply cover. Staff stated this is a daily event and that they clean this heavy dust build-up from the deckhead weekly, so some review of the duct work in this area should take place.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.