Cruise Ship: Asuka II Cruise Line: NYK Cruises Co., LTD Inspection Date: 06/08/2015 Inspection Score: 91
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 09
Site: Recreational Water Facilities-Whirlpool
Violation: The free chlorine level in the outdoor whirlpool was measured at 2.31, 2.34, and 2.27 ppm by the inspector, and 2.1, 2.4, and 2.1 by the vessel staff. The pH level was measured at 8.12 and 8.01 by the inspector and 7.8 by the vessel staff. The vessel staff was using a Hach test kit with LaMotte reagents. The whirlpool was open at the time of the inspection and staff closed it immediately. The free chlorine analyzer in the machinery room indicated a free chlorine level of 2.7 to 2.8 and the low level alarm was not activated. The pH analyzer in the machinery room indicated a pH of 6.5 and the low level alarm was indicated. Staff stated that a problem with the pH analyzer had been noted the previous day and the company was notified.
Recommendation: Maintain a free residual halogen in recirculated RWFs in the following ranges: (1) swimming pools, between 1.0 and 5.0 mg/L (ppm); (2) children's pools, between1.0 and 5.0 mg/L (ppm); (3) wading pools, between 1.0 and 5.0 mg/L (ppm); (4) interactive RWFs (activity pools), between 2.0 and 5.0 mg/L (ppm); (5) baby-only water facilities, between 3.0 and 10.0 mg/L (ppm) free chlorine or between 4.0 and 10.0 mg/L (ppm) bromine; and (6) whirlpool spas and spa pools, between 3.0 and 10.0 mg/L (ppm) free chlorine or between 4.0 and 10.0 mg/L (ppm) bromine. Maintain the pH level in all RWFs between 7.0 and 7.8. Immediately close facilities if these halogen and pH ranges are not maintained.
Item No.: 10
Site: Recreational Water Facilities-Seahorse Pool
Violation: The safety sign for the swimming pool did not state to not use the pool if experiencing vomiting.
Recommendation: Provide safety signs for all RWFs, except for baby-only water facilities. Ensure the signs, at a minimum, include the following words: (1) do not use these facilities if you are experiencing diarrhea, vomiting, or fever; (2) no children in diapers or who are not toilet trained; (3) shower before entering the facility; and (4) bather load #. For children's RWF signs, include the exact wording "TAKE CHILDREN ON FREQUENT BATHROOM BREAKS" or "TAKE CHILDREN ON FREQUENT TOILET BREAKS."
Item No.: 10
Site: Recreational Water Facilities-Whirlpool
Violation: The safety sign for the outdoor whirlpool did not state the following: (1) do not use these facilities if you are experiencing diarrhea, vomiting, or fever; (2) no children in diapers or who are not toilet trained; and (3) shower before entering the facility.
Recommendation: Provide safety signs for all RWFs, except for baby-only water facilities. Ensure the signs, at a minimum, include the following words: (1) do not use these facilities if you are experiencing diarrhea, vomiting, or fever; (2) no children in diapers or who are not toilet trained; (3) shower before entering the facility; and (4) bather load #. For children's RWF signs, include the exact wording "TAKE CHILDREN ON FREQUENT BATHROOM BREAKS" or "TAKE CHILDREN ON FREQUENT TOILET BREAKS."
Item No.: 10
Site: Recreational Water Facilities-pH Meter
Violation: The vessel had two ways to measure pH, but neither met the USPH standards. One was with a colorimetric test that did not have an error of accuracy of 0.2. The other was with a test kit manufactured by Hach, but the reagents shown to the inspector were pH tablets from the company LaMotte.
Recommendation: Ensure a test kit is available for testing water quality parameters, including free and total halogen levels (chlorine and bromine, where applicable), pH, and total alkalinity. Ensure that test kits are accurate to within 0.2 mg/L (ppm) for halogen and have a testing range of free residual halogen normally maintained in the RWF. Ensure test kits for pH are accurate to within 0.2. Ensure all reagents are not past their expiration dates. Ensure all reagents used are the correct reagents for the test kit.
Item No.: 10
Site: Recreational Water Facilities-Total Chlorine Reagents
Violation: There were no reagents on board for measuring total chlorine in order to monitor combined chlorine.
Recommendation: Monitor and adjust the RWF's flow rates, free and combined halogen levels, pH, total alkalinity, and clarity as recommended by the manufacturer and to maintain optimum public health protection and water chemistry.
Item No.: 10
Site: Recreational Water Facilities-Antientrapment Drain Cover - Whirlpool
Violation: The drain cover for the whirlpool did not meet antientrapment requirements and was not a certified cover.
Recommendation: For RWFs with gravity drainage and a single blockable drain or multiple drains less than 3 feet apart, provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover and a gravity drainage system.
Item No.: 10
Site: Recreational Water Facilities-Whirlpool Hair and Lint Strainer and Housing Disinfection
Violation: Results for disinfection of the hair and lint strainer and housing had not been recorded since 24 May 2015. Staff stated that the strainer and housing were cleaned and disinfected daily.
Recommendation: Clean, rinse, and disinfect the hair and lint strainer and hair and lint strainer housing on all RWFs weekly. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant. At a minimum, use a 50-ppm solution for 1 minute, or equivalent CT value. Maintain records on all inspection and cleaning procedures.
Item No.: 13
Site: Food Service General-Time Control Plans
Violation: Management in charge of the time control plans were not aware the plans needed to be posted in each outlet where time control was used, and that the plans needed to include and identify what units were used as time control units.
Recommendation: Ensure the supervisor or person in charge of food operations on the vessel monitors that: (1) Food operations are not conducted in a room used as living or sleeping quarters; (2) Persons unnecessary to the food operation are not allowed in the food preparation, food storage, or warewashing areas. (3) Employees and other persons such as delivery and maintenance persons and pesticide applicators entering the food preparation, food storage, or warewashing areas comply with the guidelines in this manual; (4) Food employees are effectively cleaning their hands; (5) Employees are observing foods as they are received to determine that they are from approved sources, delivered at the required temperatures, protected from contamination, unadulterated, and accurately presented; (6) Employees are properly cooking potentially hazardous food, being particularly careful in cooking foods known to cause severe foodborne illness and death, such as eggs and comminuted meats; (7) Employees are using proper methods to rapidly cool potentially hazardous foods that are not held hot or are not for consumption within 4 hours; (8) Consumers who order raw or partially cooked ready-to-eat foods of animal origin are informed that the food is not cooked sufficiently to ensure its safety; (9) Employees are properly sanitizing cleaned multiuse equipment and utensils before they are reused; (10) Consumers are notified that clean tableware is to be used when they return to self-service areas such as salad bars and buffets; (11) Employees are preventing cross-contamination of ready-to-eat food with bare hands by properly using suitable utensils such as deli tissue, spatulas, tongs, single-use gloves, or dispensing equipment; (12) Employees are properly trained in food safety, including food allergy awareness, as it relates to their assigned duties; (13) Food employees are informed of their responsibility to report to the supervisor or person in charge information about their health and activities as they relate to diseases that are transmissible through food.
Item No.: 16
Site: Food Service General-Time Control Plans
Violation: The time control plans for all the food outlets were incomplete. Most areas had one chart that diagrammed the flow of food from preparation to when it went on time control and another chart that listed the set-up and discard times of the area. The units on time control, which were primarily the bain maries and cold tops on the service lines but also included equipment such as a rice warmer and an espresso machine milk compartment in some areas, were not identified on the plan. Areas that did not have any posted time control plan, just a chart identifying the set-up and discard times, were the lido cafe omelet station, the lido garden center coffee and pastry station, port/starboard lido garden buffet, and the officer and crew mess.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
Item No.: 16
Site: Bar-Bistro
Violation: The time control plan did not indicate that the portable closed trolley and the espresso machine milk compartment were on time control. In addition, these units were not labeled as time control.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
Item No.: 19
Site: Buffet-Lido Garden
Violation: One tray of breakfast pastries was not protected by a sneeze shield at the center coffee and pastry station.
Recommendation: Protect food on display from contamination by the use of packaging; counter, service line, or salad bar food guards; display cases; self-closing hinged lids; or other effective means. Install side protection for sneeze guards if the distance between exposed food and where consumers are expected to stand is less than 1 meter (40 inches).
Item No.: 19
Site: Galley-Officer's Mess
Violation: The food-contact portion of the dispensing utensils for the hot food items were not protected under the sneeze shields.
Recommendation: During pauses in food preparation or dispensing, ensure food preparation and dispensing utensils are stored: (1) In the food with their handles above the top of the food and the container; (2) In food that is not potentially hazardous with their handles above the top of the food within containers or equipment that can be closed, such as bins of sugar, flour, or cinnamon; (3) On a clean portion of the food preparation table or cooking equipment only if the in-use utensil and the food-contact surface of the food preparation table or cooking equipment are cleaned and sanitized at least every 4 hours; (4) In running water of sufficient velocity to flush particulates to the drain (if used with moist food such as ice cream or mashed potatoes); (5) In a clean, protected location (if the utensils, such as ice scoops, are used only with a food that is not potentially hazardous); or (6) In a container of water (if the water is maintained at a temperature of at least 57°C [135°F] and the container is frequently cleaned and sanitized).
Item No.: 21
Site: Food Service General-Neutral Food Transport Cart
Violation: The wheels and wheel caps on several neutral food transport carts observed in the lido, main galley, and butcher shop were severely corroded.
Recommendation: Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 21
Site: Galley-Hot Galley
Violation: The opening around the grease trap housing under the forward grooved grill and the aft flat grill was not sealed.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 22
Site: Galley-Lido Garden-Scullery
Violation: The final rinse temperature gauge displayed a temperature of 230°F. A 200°F thermolabel was placed on the final rinse manifold and it did not change color, indicating the temperature was less than 200°F.
Recommendation: Ensure water temperature-measuring devices are scaled: (1) in Celsius or dually scaled in Celsius and Fahrenheit are designed to be accurate to within 1.5°C (within 3°F) in the intended range of use; (2) only in Fahrenheit are designed to be accurate to within 3°F in the intended range of use.
Item No.: 22
Site: Galley-Lido Garden-Scullery
Violation: The bottom left final rinse spray nozzle was partially blocked creating an ineffective spray pattern.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 29
Site: Pantry-Vista
Violation: The door to the pantry was pinned open, which blocked access to the handwashing station.
Recommendation: Ensure handwashing facilities are used for no other purpose and are accessible at all times.
Item No.: 33
Site: Galley-Dry Store
Violation: The grouting at the base of the deck/bulkhead juncture coving was missing in large sections around this room. The bulkhead behind the front storage shelf was soiled with an accumulation of flour and other food debris.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair. Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 36
Site: Buffet-Sushi Bar
Violation: The light intensity at the handwash station and in front of the reach-in refrigerator SB-5 was less than 220 lux.
Recommendation: Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
Item No.: 36
Site: Buffet-Lido Garden-Starboard
Violation: The light intensity at the handwash station by the crew corridor was less than 220 lux.
Recommendation: Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
Item No.: 36
Site: Preparation Room-Deck Ovens
Violation: The light intensity behind and around the two deck ovens was less than 110 lux.
Recommendation: Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
Item No.: 36
Site: Provisions-Freezer 405
Violation: The light in the far corner of the walk-in freezer was burnt out resulting in a light intensity of less than 110 lux.
Recommendation: Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
Item No.: 37
Site: Provisions-Freezer 415
Violation: A heavy amount of frozen condensation had accumulated on the deckhead and bulkhead in the separate cold box inside the walk-in freezer. Staff stated this cold room was maintained at -45°C and was defrosted and cleaned three times a year. No food boxes stored in the cold box appeared to be affected by the frozen condensation.
Recommendation: Ensure frozen condensation does not accumulate in the cold box.
Item No.: 38
Site: Preparation Room-Deck Ovens
Violation: Two large pizza paddles were stored on top on the right deck oven. The paddles looked like they have been stored in that location for some time, and staff stated they have never used them before.
Recommendation: Ensure only articles necessary for the food service operation are stored in food preparation, food storage, and warewashing areas.
Item No.: 39
Site: Provisions-Dry Store 412
Violation: One large house fly was observed in the dry store room.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 40
Site: Integrated Pest Management-Active Inspections and Follow-up Inspections
Violation: The ship's IPM plan only accounted for passive monitoring, which consisted of checking the glue traps twice a month (one during the day and one at night). No active inspections were performed by crew members, and no pest sighting log was kept to detail what pesticide was applied and the follow-up inspection results. The monthly summary results of the passive monitoring did list the number of pests that were found and what pesticide was applied, but no follow-up inspection was documented. The weekly active inspection of the garbage handling areas of the ship was not documented.
Recommendation: Ensure the IPM Plan sets a schedule for periodic active monitoring inspections, including some at night or during periods of no or minimal activity. Ensure the IPM Plan includes provisions for logs for active monitoring of pest sightings in operational areas of the vessel. Ensure the IPM plan includes provisions for training of crew members in charge of log completion. Record the time of the active monitoring inspections in the log. When pests are noted during an inspection, ensure the log includes action taken and follow-up inspection results. Inspect the garbage handling areas of the vessel at least weekly for the presence of insects, rodents, and other pests. Maintain the results of these inspections in a log.