Item No.:
03
|
|
Site:
Potable Water-Bunkering Records
|
|
Violation:
The bunker chart for 01/14/2013 showed the free chlorine residual to be between 0.5 and 1.25 PPM during the water bunkering operation from 0945 and 1320. The initial free chlorine residual in the log book for this date indicated 2.5 PPM.
|
|
Recommendation:
Continuously halogenate potable water to at least 2.0 mg/L (ppm) free residual halogen at the time of bunkering or production with an automatic halogenation device that is controlled by a flow meter and adjust the pH so it does not exceed 7.8. Ensure the amount of halogen injected during bunkering or production is controlled by a flow meter or a free halogen analyzer.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Microbiologic Monitoring
|
|
Violation:
The monthly microbiologic monitoring records showed that the samples were taken from the Bridge Pantry on October 28, November 7 and December 7.
|
|
Recommendation:
Collect samples from the forward, aft, upper, and lower decks of the vessel. Change the sample sites each month so that all of the potable water distribution system is effectively monitored.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Bunkering
|
|
Violation:
The bunkering records for 08/24 and 08/27 did not include microbiologic sample results. There was also no microbiologic report from the port.
|
|
Recommendation:
Either provide results for microbiologic samples analyzed on board the vessel or provide a microbiologic report from the port.
|
|
|
Item No.:
06
|
|
Site:
Potable Water-Bunkering / Production Records
|
|
Violation:
The calibration was not recorded on the production halogenation charts for 08/21-23/2013. The bunkering record did not include calibration for 8/24/2013.
|
|
Recommendation:
Calibrate at the beginning of bunkering or production. Ensure the calibration is recorded on the chart.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Bunkering Records
|
|
Violation:
The date was not recorded on the bunker chart for 01/09/2014.
|
|
Recommendation:
Maintain accurate records of bunkering.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Medical Center
|
|
Violation:
The sluice machine hot and cold water supply lines in the deckhead had backflow preventers that were leaking from the air relief holes indicating a possible failure.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
08
|
|
Site:
Galley-Port Side Italian Pantry
|
|
Violation:
The relief valve for reduced pressure backflow assembly for the hood cleaning system was leaking indicating a possible failure in the assembly.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Safety Equipment
|
|
Violation:
The shepherd's hook was not mounted in the Aquarius Pool area. The pool was out of service for maintenance at the time of this inspection.
|
|
Recommendation:
Provide a rescue or shepherd's hook at a prominent location (visible from the full perimeter of the pool). Mount these devices in a manner that allows for easy access during an emergency. Ensure the pole of the rescue or shepherd's hook is long enough to reach the center of the deepest portion of the pool from the side plus 2 feet. Ensure it is a light, strong, nontelescoping material with rounded, nonsharp ends.
|
|
|
Item No.:
11
|
|
Site:
Medical-Crew Acute Gastroenteritis Reporting
|
|
Violation:
A food worker had an acute gastrointestinal illness symptom onset on 12/21/2013 at 0800 and did not report to the medical staff until 1210. The work records showed this person was on duty between the illness onset and when the illness was reported to the medical staff. Another food worker on 11/13/2013 had an onset of 10 vomiting episodes at 0900. The illness was not reported until 1645. The work records showed the employee on duty from 1000 to 1100 on this day.
|
|
Recommendation:
Ensure food employees who have conditions or symptoms of diarrhea and vomiting report these conditions or symptoms to the vessel's medical staff and are restricted from working with exposed food, warewashing, clean equipment, utensils, and linens, and unwrapped single-service and single-use articles.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Cold Buffet Port Side
|
|
Violation:
The two tureens of hot milk and oatmeal were listed on the time control plan but were not labeled 'time control' on the physical units.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
16
|
|
Site:
Galley-East
|
|
Violation:
The milk compartment for the coffee machine was listed on the time control plan but the physical unit was not labeled for time control.
|
|
Recommendation:
Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
|
|
|
Item No.:
16
|
|
Site:
Dining Room-East
|
|
Violation:
The new menu had two different steak entrees that could be cooked-to-order for passengers. The general consumer advisory was on the bottom of the menu but the steak entrees were not noted with asterisks.
|
|
Recommendation:
If an animal food such as beef, eggs, fish, lamb, milk, pork, poultry, or shellfish that is raw, undercooked, or not otherwise processed to eliminate pathogens is offered in a ready-to-eat form or as a raw ingredient in another ready-to-eat food, ensure the consumer is informed by way of disclosure using menu advisories, placards, or other easily visible written means of the significantly increased risk to certain especially vulnerable consumers eating such foods in raw or undercooked form. Locate the advisory at the outlets where these types of food are served. Ensure that raw shell egg preparations are not used in uncooked products as described in section 7.3.3.2.3. Ensure that disclosure is made by one of the two following methods: (1) On a sign describing the animal-derived foods (e.g., "oysters on the half-shell," "hamburgers," "steaks," or "eggs"); AND that they can be cooked to order and may be served raw or undercooked; AND a statement indicating that consuming raw or undercooked meats, seafood, shellfish, eggs, milk, poultry may increase your risk for foodborne illness, especially if you have certain medical conditions. Ensure the advisory is posted at the specific station where the food is served raw, undercooked, or cooked to order OR (2) On a menu using an asterisk at the animal-derived foods requiring disclosure and a footnote with a statement indicating that consuming raw or undercooked meats, seafood, shellfish, eggs, milk, or poultry may increase your risk for foodborne illness, especially if you have certain medical conditions.
|
|
|
Item No.:
17
|
|
Site:
Galley-Deck 2 Garde Manger
|
|
Violation:
The cooling logs for melons cooled on 1 February did not have a final temperature recorded. The melons were still in the walk-in refrigerator and the inspector verified their internal temperature was less than 41°F.
|
|
Recommendation:
Ensure logs documenting cooked potentially hazardous food cooling temperatures and times from the starting points designated in 7.3.5.2.1 thru the control points at 2 and 6 hours are maintained onboard the vessel for a period of 30 days from the date the food was placed in the cooling process.
Ensure logs documenting cooling of potentially hazardous foods prepared from ingredients at ambient temperatures, with the start time to the time when 5°C (41 °F) is reached are also maintained for a period of 30 days, beginning with the day of preparation.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 2 Moble Refrigerator B2
|
|
Violation:
The digital temperature gauge for this unit was displaying a temperature of 6°C. The internal thermometer was reading about 48°F. The milk containers in this refrigerator were checked and had an internal temperatures between 41°F-43°F and were immediately placed into a different refrigeration unit.
|
|
Recommendation:
Food contact equipment must be maintained in good repair and proper adjustment: (1) Equipment must be maintained in a state of repair and condition that meets the materials, design, construction, and operating specifications of these guidelines; and (2) Cutting or piercing parts of can openers must be kept sharp to minimize the creation of metal fragments that can contaminate food when the container is opened.
|
|
|
Item No.:
20
|
|
Site:
Preparation Room-Deck A Bakery
|
|
Violation:
The dough sheeter belt was ripped and torn in several areas making it no longer easily cleanable.
|
|
Recommendation:
Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; (3) Free of sharp internal angles, corners, and crevices; (4) Finished to have smooth welds and joints; and (5) Accessible for cleaning and inspection by one of the following methods without being disassembled, by disassembling without the use of tools, or by easy disassembling with the use of handheld tools commonly available to maintenance and cleaning personnel. Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
22
|
|
Site:
Galley-Deck 2 Warewashing
|
|
Violation:
The temperature gauge for the final rinse was reading about 220°F. A 200°F maximum registering tape was placed on the final rinse manifold during use and it did not change color, indicating the water in the manifold was less than 200°F.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
|
|
|
Item No.:
22
|
|
Site:
Galley-Belvedere
|
|
Violation:
The final rinse spray for the flight-type dishwasher was not continually activated during use. It appeared the sensor in the machine that activates the final rinse spray was malfunctioning. Several racks of plates were observed moving through the machine without the final rinse spray.
|
|
Recommendation:
Ensure a warewashing machine and its auxiliary components are operated in accordance with the machine's data plate and other manufacturer's instructions. Ensure a warewashing machine's conveyor speed or automatic cycle times is maintained accurately timed in accordance with manufacturer's specifications.
|
|
|
Item No.:
26
|
|
Site:
Galley-Deck 2 Garde Manger
|
|
Violation:
Dried food residue was on the recessed ledge of the backplate on the previously cleaned deli slicer.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Bar-Rising Sun - Ice Machine
|
|
Violation:
The top of the ice cubers by the water dispensing nozzles had a significant amount of mold accumulated, especially in the back, difficult to reach and clean areas.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
26
|
|
Site:
Bar-Neptune Bar - Ice Machine
|
|
Violation:
The top of the ice cubers by the water dispensing nozzles had a significant amount of mold accumulated, especially in the back, difficult to reach and clean areas.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
29
|
|
Site:
Galley-Deck 3 Toilet Room
|
|
Violation:
The toilet room was out-of-order. Staff was waiting for new toilets to arrive to install.
|
|
Recommendation:
Ensure toilet rooms are provided and conveniently located.
|
|
|
Item No.:
29
|
|
Site:
Galley-Warewash
|
|
Violation:
The water temperature of both handwash sinks could not reach 100°F.
|
|
Recommendation:
Ensure handwashing sinks are equipped to provide water at a temperature of at least 38°C (100°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, and other types of handwash sinks where the user cannot make temperature adjustments, ensure the temperature provided to the user after the mixing valve does not exceed 49°C (120°F).
|
|
|
Item No.:
29
|
|
Site:
Preparation Room-Bakery
|
|
Violation:
The water temperature of the handwash sink by the walk-in refrigerator could not reach 100°F.
|
|
Recommendation:
Ensure handwashing sinks are equipped to provide water at a temperature of at least 38°C (100°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, and other types of handwash sinks where the user cannot make temperature adjustments, ensure the temperature provided to the user after the mixing valve does not exceed 49°C (120°F).
|
|
|
Item No.:
29
|
|
Site:
Galley-Deck 2 Toilet Room
|
|
Violation:
The toilet room was locked during operation. Upon further investigation it was determined the toilet room was out of order since December 2013.
|
|
Recommendation:
Ensure toilet rooms are provided and conveniently located.
|
|
|
Item No.:
29
|
|
Site:
Galley-Deck 3 Forward Griddles
|
|
Violation:
A spoon was found in the handwash sink to the left of the forward griddles.
|
|
Recommendation:
Ensure handwashing facilities are used for no other purpose and are accessible at all times.
|
|
|
Item No.:
29
|
|
Site:
Galley-Belvedere Warewashing
|
|
Violation:
The toilet room was locked during operation. Upon further investigation it was determined the toilet room was out of order.
|
|
Recommendation:
Ensure toilet rooms are provided and conveniently located.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Poultry Freezer #6
|
|
Violation:
A large accumulation of ice was on the bulkhead by the door around the emergency release button. Boxes of food were not in direct contact with the bulkhead but they were close enough to have small amounts of ice on them. These boxes were moved to a different area in the walk-in.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
33
|
|
Site:
Provisions-Fish Freezer
|
|
Violation:
Ice was on several boxes of frozen fish in the aft area of the freezer. Three light fixtures in this area had a significant amount of ice accumulated in the fixtures. One icicle was formed on the center light fixture. After examination the frozen fish boxes no ice had appeared to enter the boxes. The deck in this area under the pallets was covered in a layer of ice.
|
|
Recommendation:
Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
|
|
|
Item No.:
36
|
|
Site:
Bar-Neptune Bar
|
|
Violation:
The light intensity behind and around the ice machine was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-Hot Galley
|
|
Violation:
The light intensity behind and around the oven was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Housekeeping-Deck Pantries
|
|
Violation:
The lighting behind the deck mounted ice machines was less than 110 lux of illumination.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-Port Side Italian Pantry
|
|
Violation:
The light intensity behind and around the reach-in refrigerator was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-Midship Starboard Ice Machine
|
|
Violation:
The light intensity behind and around the ice machine was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-Midship Starboard Toaster Station
|
|
Violation:
The light intensity behind reach-in refrigerator BE4 was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-Midship Port SideToaster Station
|
|
Violation:
The light intensity behind reach-in refrigerator B10 was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Buffet-Aft Beverage Station
|
|
Violation:
Several of the small deckhead lights were not shielded. These light bulbs were not shatter-resistant.
|
|
Recommendation:
Ensure light bulbs are shielded, coated, or otherwise shatter-resistant in areas where there is exposed food, clean equipment, utensils, and linens, or unwrapped single-service and single-use articles.
|
|
|
Item No.:
36
|
|
Site:
Galley-Deck 3 Ovens
|
|
Violation:
The light intensity behind and around the ovens was less than 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 2 Dry Storage Area
|
|
Violation:
Two fruit flies were observed in this area.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 2 Warewashing
|
|
Violation:
One fruit fly was observed by the clean storage rack.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 2 Pastry
|
|
Violation:
Two small fruit flies were observed behind the ovens.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|