Item No.:
08
|
|
Site:
Potable Water-All Air Conditioning Fan Room
|
|
Violation:
Each of the fan rooms have a single sink basin inside and the staff stated that they connect hoses to the sink faucet when cleaning the interior of the fan units and condensate pans. There were no backflow prevention devices installed on either the hot or cold potable water supply pipes connected to these sinks.
|
|
Recommendation:
Provide a comprehensive cross-connection control program. Protect the following connections to the potable water system against backflow with air gaps or mechanical backflow prevention devices: (4) photographic laboratory developing machines and utility sinks; (5) beauty and barber shop spray-rinse hoses; (6) spa steam generators where essential oils can be added; (7) hose-bib connections; (26) other connections between the potable water system and a nonpotable water system, such as the gray water system, laundry system, or technical water system (install an air gap or a reduced pressure assembly); (27) black water or combined gray water/black water systems (install an air gap); (28) any other connection to the potable water system where contamination or backflow can occur.
|
|
|
Item No.:
11
|
|
Site:
Medical-Crew Gastrointestinal (GI) Illness Reporting
|
|
Violation:
A galley utility worker with GI illness onset at 1100 on 29 March did not report to the medical center until 2 pm that day. The worker reported in his self-administered questionnaire that he ate lunch in the crew mess the same day at 11:30.
|
|
Recommendation:
|
|
|
Item No.:
16
|
|
Site:
Galley-Silk Road
|
|
Violation:
The dinner menu had a consumer advisory, but was not fully visible. The advisory was tucked into the corner of the menu cover.
|
|
Recommendation:
Rearrange the dinner menu so the cover does not block the consumer advisory.
|
|
|
Item No.:
16
|
|
Site:
Buffet-Crew Mess
|
|
Violation:
The posted time control plan indicated cooling units #3 and #4 were being used, however these units were in the Officer's Mess. Cooling units #1 and #2 were used in the crew mess.
|
|
Recommendation:
Update the time control plan in the Crew Mess.
|
|
|
Item No.:
19
|
|
Site:
Galley-Pastry
|
|
Violation:
Unused flour was in the open center compartment of the dough sheeter. The area was not in operation during the inspection.
|
|
Recommendation:
Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
|
|
|
Item No.:
19
|
|
Site:
Other-Deck 4 Elevator Lobby at Garbage Room
|
|
Violation:
One food employee was observed wheeling a trolley filled with food trays of ready-to-eat foods from the garbage only elevator to move into the crew area. The elevator had numerous signs both inside and out specifying it was for transport of garbage only. It appeared that staff do not follow the signs posted on the two elevators and simply take the most convenient one to transport foods.
|
|
Recommendation:
|
|
|
Item No.:
20
|
|
Site:
Galley-Pastry
|
|
Violation:
There were slotted fasteners near the door inside each deck oven shelf.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Preparation Room-/Vegetable
|
|
Violation:
One slotted fastener was in the food contact area of the left potato peeler.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Other-Trident Grill
|
|
Violation:
The crew members responsible for cooking hamburgers were not equipped with tip-sensitive thermometers.
|
|
Recommendation:
Ensure food temperature-measuring devices are provided and readily accessible for use in ensuring attainment and maintenance of food temperatures. Use tip-sensitive temperature-measuring devices, such as a thermocouple or thermistor, for measuring thin food products.
|
|
|
Item No.:
20
|
|
Site:
Bar-Cove Bar
|
|
Violation:
One slotted fastener was in the food contact area where the coffee handles fit into the upper portion of the coffee machine.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Lido Cafe - Egg Stations
|
|
Violation:
The crew members responsible for preparing eggs cooked to order were not equipped with tip-sensitive thermometers.
|
|
Recommendation:
Ensure food temperature-measuring devices are provided and readily accessible for use in ensuring attainment and maintenance of food temperatures. Use tip-sensitive temperature-measuring devices, such as a thermocouple or thermistor, for measuring thin food products.
|
|
|
Item No.:
20
|
|
Site:
Bar-The Bistro
|
|
Violation:
One slotted fastener was in the food contact area where the coffee handles fit into the upper portion of the coffee machine.
|
|
Recommendation:
Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Lido Cafe
|
|
Violation:
The lamp shades were made of thin paper-like wood material that were easy to tear. Some areas of the lamp shades were soiled with dust of more than one day's accumulation. Clean plates for passenger service were stored below.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
27
|
|
Site:
Buffet-Lido Cafe
|
|
Violation:
The outside upper areas of the heat lamps were soiled with dust of more than one day's accumulation.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
28
|
|
Site:
Galley-Starboard Dishwash Machine
|
|
Violation:
Condensation was observed dripping onto clean dishes as they exited the machine and onto clean dishes stored below the exhaust vents.
|
|
Recommendation:
Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
|
|
|
Item No.:
28
|
|
Site:
Galley-Pastry
|
|
Violation:
Numerous previously cleaned brown soufflé bowls were stored wet inside the clean items locker across from the ice machines.
|
|
Recommendation:
Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
|
|
|
Item No.:
28
|
|
Site:
Other-Trident Grill
|
|
Violation:
Two stacks of plates for crew member use were stored on the front counter near where passengers were waiting. The plates were not protected by a sneeze shield or inverted.
|
|
Recommendation:
Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
|
|
|
Item No.:
28
|
|
Site:
Galley-Pastry
|
|
Violation:
About five plates not in use were stored upright on an open plate rack.
|
|
Recommendation:
Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
|
|
|
Item No.:
28
|
|
Site:
Bar-The Bistro
|
|
Violation:
Plates for crew members to provide passengers were stored on the front counter in an area where passengers could get one if they choose. The plates were not inverted or covered. All plates were moved to the back bar counter.
|
|
Recommendation:
Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
|
|
|
Item No.:
33
|
|
Site:
Bar-Officer Bar
|
|
Violation:
There was no coving at the deck/vertical column juncture.
|
|
Recommendation:
Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel).
|
|
|
Item No.:
33
|
|
Site:
Galley-Lido Cafe - Corridor
|
|
Violation:
The locking mechanisms were missing in the two entry doors, exposing a hole in each door. These doors were located at the warewash area and the corridor and at the corridor and the hot galley.
|
|
Recommendation:
|
|
|
Item No.:
34
|
|
Site:
Galley-Pastry
|
|
Violation:
The faucet of the ice cream dipper well was continuously leaking.
|
|
Recommendation:
Ensure a plumbing system in a food area is maintained in good repair.
|
|
|
Item No.:
36
|
|
Site:
Galley-Starboard Ice Machine
|
|
Violation:
The light intensity was less than 110 lux behind and beside the ice machine.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-Silk Road
|
|
Violation:
The light intensity was less than 110 lux behind and to the left of the ice machine.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Buffet-Lido Cafe - Beverage Stations
|
|
Violation:
The light intensity was less than 110 lux between the coffee machines and the bulkhead.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Pantry-Cabin Deck Pantries
|
|
Violation:
The artificial light level behind and around the ice machines in the pantry were below the minimum 110 lux.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Galley-
|
|
Violation:
The light intensity was less than 110 lux behind the left combination oven.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
36
|
|
Site:
Dining Room-
|
|
Violation:
The light intensity could not be raised to 220 lux at the waiter stations.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at handwashing stations in bars. In bars and dining room waiter stations, provide 220 lux (20 foot candles) light intensity during cleaning operations.
|
|
|
Item No.:
36
|
|
Site:
Galley-Cold Pantry
|
|
Violation:
The light intensity was less than 220 lux at the handwash station near the walk-in refrigerator.
|
|
Recommendation:
Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
|
|
|
Item No.:
36
|
|
Site:
Galley-Potwash
|
|
Violation:
The light intensity was less than 110 lux behind the hood-type potwash machine.
|
|
Recommendation:
Ensure the light intensity is at least 110 lux (10 foot candles) at a distance of 75 centimeters (30 inches) above the deck when in use, in walk-in refrigerator units and dry storage areas, and in other areas and rooms during periods of cleaning. Ensure the light intensity is at least 110 lux (10 foot candles) behind and around mounted equipment, including counter-mounted equipment.
|
|
|
Item No.:
37
|
|
Site:
Galley-Starboard Dishwash Machine
|
|
Violation:
There was excess condensation on the inside final exhaust compartment of the in-use conveyor dishwash machine. Also, excess condensation was on the exhaust vent in front of the machine at the clean end, above the clean landing, and on the exhaust vent near the cleaning locker. Condensation was observed dripping onto clean dishes as they exited the machine and onto clean dishes stored below the exhaust vents.
|
|
Recommendation:
Ensure heating, ventilating, and air conditioning systems are designed and installed so that make-up air intake and exhaust vents do not cause contamination of food, food-contact surfaces, equipment, or utensils.
|
|
|
Item No.:
38
|
|
Site:
Galley-Potwash
|
|
Violation:
An unused squeegee was stored behind the soiled storage racks.
|
|
Recommendation:
Ensure maintenance tools such as mops, brooms, and similar items are stored in a designated locker so they do not contaminate food, food-contact surfaces of utensils, and equipment, linens, and single-service and single-use articles.
|
|
|
Item No.:
38
|
|
Site:
Pantry-The Bistro
|
|
Violation:
An electrical vacuum was stored in the pantry as it was charging.
|
|
Recommendation:
Ensure maintenance tools such as mops, brooms, and similar items are stored in a designated locker so they do not contaminate food, food-contact surfaces of utensils, and equipment, linens, and single-service and single-use articles.
|
|
|
Item No.:
39
|
|
Site:
Galley-Prego / Silk Road
|
|
Violation:
One live fly was at the light above hot holding unit #1. The area was not in operation during the inspection.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Active Monitoring Records
|
|
Violation:
The printed log for the pro-active inspections for live pests included date of inspection but no times, so it was unclear which were conducted at night.
|
|
Recommendation:
Ensure the IPM Plan sets a schedule for periodic active monitoring inspections, including some at night or during periods of no or minimal activity. Include the time of inspection so it is clear that some were conducted at night.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Rat Guards
|
|
Violation:
At least one of the rat guards on the mooring lines was a inverted U design which covered two lines and had no closure on the bottom. This design did very little to prevent access at the lower side of the ship to pests because the underside of both ropes were not covered at all.
|
|
Recommendation:
Provide effective rat guards for mooring line protection.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Outbreak Prevention and Response Plan (OPRP)
|
|
Violation:
The written OPRP is contained in the medical management disease prevention manual, With appendix 18, under the cleaning and sanitation level practices there are statements that when cleaning and disinfecting hard, non porous food-contact surfaces that a 1% solution of the RelyOn cleaner/disinfectant can be used or 100 ppm chlorine. This statement appears under routine level practices, under level 1 conditions where gastrointestinal illness is elevated but below 2%, and for level 2 and level 3, where GI illness outbreaks are detected. This product requires a wipe down after the required contact time according to the company literature when used on food-contact surfaces, and does not meet VSP requirements for use on food-contact surfaces.
|
|
Recommendation:
Remove the statements where a disinfectant level product is used for food-contact surfaces. Such surfaces require sanitizing at levels prescribed in the VSP Manual and not higher, unless there is a vomiting event which takes place on that food surface. In such cases the product would need to be rinsed off completely after use and the surface re-applied with standard sanitizing level concentrations.
|
|
|
Item No.:
41
|
|
Site:
Housekeeping-Outbreak Prevention and Response Plan (OPRP)
|
|
Violation:
In the written OPRP, appendix 18 there is a statement for galleys and bars that twice daily, following lunch and dinner, that for galleys and preparation rooms the tops of prep tables should be completely washed down, followed by either application of 1% RelyOn or 100 ppm chlorine. The same was written for bars, and this was for routine level sanitation and level 2 and 3 when GI illness exceeds 2 or 3%. The cleaner/disinfectant should not be used in this way to meet routine or even elevated GI conditions, as a wipe down is required wherever it is applied, following the 10 minute contact time.
|
|
Recommendation:
Remove statements about use of products on food preparation surfaces where a wipe off of that product following application is required. The only time a strong disinfectant can be used in galleys is when an actual vomiting incident has occurred. That requires a rinse step following disinfection and final application at a sanitizing strength of 50-200 ppm chlorine.
|
|
|
Item No.:
42
|
|
Site:
Children Area-Fantasia Children's Area
|
|
Violation:
The hot water at the handwash sink in the play room reached a temperature of 126 °F.
|
|
Recommendation:
|
|