|
|
|
Item No.:
07
|
|
Site:
Potable Water-Skin Tank Varaince
|
|
Violation:
The approved variance for skin tanks stated that routine maintenance checks were to be carried out every 6 months on the salinometer and alarm system. However, the last two checks occurred on 1 November 2015 and 15 September 2016, almost 11 months apart.
|
|
Recommendation:
12.13 Variances
12.13.1 Procedures
12.13.1.1 Variance Procedures
VSP may grant a Variance by modifying or waiving the requirements of this VSP 2011 Operations Manual if VSP determines that a health hazard or nuisance will not result from the Variance.
12.13.1.3 Vessel Records
If a Variance is granted, the vessel using the VARIANCE must retain the information in its records for ready reference.
12.13.3 Conformance
12.13.3.1 Conformance
If VSP grants a Variance, the vessel must
? Comply with the HACCP plans, standard operating procedures, training plan, and monitoring plan that are submitted and approved as a basis for the modification or waiver.
? Maintain and provide to VSP, on request, records to demonstrate that procedures monitoring critical-control points are effective, monitoring of the critical-control points are routinely used, necessary corrective actions are taken if there is failure at a critical-control point, and periodic verification of the effectiveness of the operation or process in protecting public health.
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
12.13.3.2 Rescinding Variance
Variance approval may be rescinded at any time for noncompliance with these conditions or if it is determined that public health could be compromised.
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
|
|
|
Item No.:
08
|
|
Site:
Buffet-Deck 5 - Topside Buffet
|
|
Violation:
The backflow preventer on the water supply line to the combi oven was leaking, indicating a possible failure. Water had pooled on the counter and the valve was discolored indicating a longstanding problem.
|
|
Recommendation:
Maintain backflow prevention devices in good repair.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Cross-connection Control Program
|
|
Violation:
Both reduced pressure zone (RPZ) backflow prevention devices for the international shore connections for fire were tested on 1 June 2016 using a test method for double check valves and not for RPZ. As a result, the tests did not measure pressure differentials at the time the intermediate relieve vent started to leak. This last step was an essential part of the RPZ test.
|
|
Recommendation:
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Tank Maintenance
|
|
Violation:
Records indicated that during the 25 October-8 November crossing from Europe to the Caribbean, 5 of the 6 potable water tanks were cleaned and painted. The 2011 VSP Operations Manual alternative disinfection method was chosen. The surfaces were sprayed with 200 ppm of chlorine solution to remain wet for 2 hours. Step 2 of the alternative method requires to clean all tank surfaces, including filling lines, etc., with an appropriate detergent; however, a detergent was not used. In addition, there was no indication that curing and drying times for the paint were followed before the tanks were filled.
|
|
Recommendation:
Maintain documentation of all inspections, maintenance, cleaning, and disinfection for 12 months and ensure it is available for review during inspections. Ensure records include a method of disinfection, concentration and contact time of the disinfectant, and a halogen value of less than or equal to 5 ppm before the tank is put back into service.
Document the free halogen residual level. Flush the disinfected parts of the system with potable water or otherwise dechlorinate until the free residual halogen is less than or equal to 5.00 mg/L (ppm). Document the free halogen test result. Ensure the interior coatings on potable water tanks are approved for potable water contact by a certification organization. Follow all manufacturers? recommendations for application, drying, and curing. For the tank coatings used, maintain the following onboard: (3) written documentation that the manufacturers? recommendations have been followed for application, drying, and curing.
If the alternative potable water tank cleaning and disinfection procedure described in this section is used, ensure it is only used for routine cleaning and disinfection and not for known or suspected contaminated tanks.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Housing Disinfection
|
|
Violation:
Records indicated that filters and hair/lint strainers for the pool and whirlpool were disinfected appropriately, but had no notes about cleaning and disinfection of the housings. The job description for this cleaning and disinfection stated that housings had to be cleaned and disinfected too.
|
|
Recommendation:
Clean, rinse, and disinfect the hair and lint strainer and hair and lint strainer housing on all RWFs weekly. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant. At a minimum, use a 50-ppm solution for 1 minute, or equivalent CT value. Maintain records on all inspection and cleaning procedures.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Shock Halogenation
|
|
Violation:
Records indicated that the whirlpool was shock halogenated every night around 2200 with a starting concentration of 10+ chlorine. No other notes as to the final chlorine concentration and the end time of the process.
|
|
Recommendation:
Test the free residual halogen both at the start and completion of shock halogenation.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Flow Meters
|
|
Violation:
The flow meter of the pool system was not working and as a result the turnover rate and bather load calculations could not be verified. The functionality of the flow meter for the whirlpool could not be verified because the system was under maintenance.
|
|
Recommendation:
Replace RWF flow meters when they are defective.
|
|
|
Item No.:
20
|
|
Site:
Buffet-Deck 5 - Topside Buffet
|
|
Violation:
The food warming unit below the overshelf was rusty, making it difficult to clean.
|
|
Recommendation:
Food contact equipment must be maintained in good repair and proper adjustment: (1) Equipment must be maintained in a state of repair and condition that meets the materials, design, construction, and operating specifications of these guidelines.
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 2 - Butcher Shop
|
|
Violation:
The small counter-mounted mixer had rust on the planetary mounting plate for the mixer impeller/blade that made this surface above food in the mixing bowl difficult to clean.
|
|
Recommendation:
|
|
|
Item No.:
20
|
|
Site:
Galley-Deck 2 - Cold Galley
|
|
Violation:
Condensate was pooling in the bottom of the left compartment of the double door reach-in cooler #17. Since the cooler was empty, no food was impacted by the condensate that was dripping from the evaporator housing at the top of the cooler. Staff said they add an empty top pan to catch the condensate when the unit is in service.
|
|
Recommendation:
Food contact equipment must be maintained in good repair and proper adjustment: (1) Equipment must be maintained in a state of repair and condition that meets the operating specifications of these guidelines.
|
|
|
Item No.:
22
|
|
Site:
Galley-Deck 2 - Beverage Pantry
|
|
Violation:
The coffee machine cleaning instructions were not available. The coffee machine sanitizer is a quaternary ammonium compound. Test strips were not available for this sanitizer.
|
|
Recommendation:
When clean in place or other alternative cleaning, rinsing and sanitizing procedures are used, follow the manufacturer?s instructions. Accurately determine the concentration of the sanitizing solution by using a test kit.
|
|
|
Item No.:
22
|
|
Site:
Bar-Deck 6 - Top of the Yacht
|
|
Violation:
The undercounter dishwasher was out of order and a replacement dishwasher has been ordered.
|
|
Recommendation:
Maintain warewashing equipment in good repair.
|
|
|
Item No.:
23
|
|
Site:
Galley-Deck 2 - Beverage Pantry
|
|
Violation:
The coffee machine milk tubing and milk foaming parts were found soaking in a cleaning solution that was heavily soiled with old milk particles.
|
|
Recommendation:
Ensure equipment is preflushed as a part of the cleaning process.
|
|
|
Item No.:
26
|
|
Site:
Galley-Deck 2 - Pastry
|
|
Violation:
The mix addition tube on the ice cream maker was soiled with what appeared to be small pieces of chocolate. Galley steward #1 cleaned the tube with a small brush, rinsed the tube and sanitized it while the team was in the area.
|
|
Recommendation:
Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
|
|
|
Item No.:
27
|
|
Site:
Galley-Deck 2 - Pastry
|
|
Violation:
Old chocolate residue was found on the plastic flange around the mix feed tube. This was cleaned at the same time that the tube was cleaned.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of food residue. Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of food residue.
|
|
|
Item No.:
29
|
|
Site:
Bar-Deck 2 - Pool Bar
|
|
Violation:
The bar's handwashing sink was partially blocked by a new draft beer dispenser system plastic 'keg' and a large red trash bin. This bar was not in use during this inspection.
|
|
Recommendation:
Ensure handwashing facilities are accessible at all times.
|
|
|
Item No.:
30
|
|
Site:
Bar-Deck 6 - Top of the Yacht
|
|
Violation:
The sink in the front bar did not have towels, soap, waste container or handwash reminder sign.
|
|
Recommendation:
Ensure a handwashing facility includes a sink, soap dispenser, single-use towels dispenser, and waste receptacle. Post a sign over handwashing sinks stating "WASH HANDS OFTEN" in a language that the food employees understand.
|
|
|
Item No.:
33
|
|
Site:
Galley-Deck 2 - Dry Stores
|
|
Violation:
The deck in the back right corner of the storeroom under the shelves and behind the movable pallet stands was soiled with a small amount of spilled dry food. The area was immediately cleaned by Galley Steward #1.
|
|
Recommendation:
Ensure decks in food areas are cleaned as often as necessary.
|
|
|
Item No.:
39
|
|
Site:
Galley-Deck 2 - Butcher Shop
|
|
Violation:
One live house fly was noted in the closed area.
|
|
Recommendation:
Effectively control insects in the food areas.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Incoming Shipments
|
|
Violation:
Staff stated that flowers were checked by a crew member. However, records were not clear as to the inspection of flowers.
|
|
Recommendation:
Routinely inspect incoming shipments of all other supplies for evidence of insects, rodents, and other pests. Maintain a record of these inspections onboard the vessel and make the record available for review during inspections.
|
|
|
Item No.:
40
|
|
Site:
Integrated Pest Management-Rat Guards
|
|
Violation:
One of the mooring lines did not have a rat guard. Staff instructed crew members to correct this immediately.
|
|
Recommendation:
Protect entry points where pests may enter.
|
|