Cruise Ship: Costa Deliziosa Cruise Line: Costa Crociere S.P.A. Inspection Date: 12/21/2016 Inspection Score: 90
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 06
Site: Potable Water-Bunkering/Production Data Logger
Violation: No certified data security features could be verified for the data logger that was used to monitor the chlorine and pH during bunkering and production.
Recommendation: Ensure electronic data loggers with certified data security features used in lieu of chart recorders produce records that conform to the principles of operation and data display required of the analog charts, including printing the records.
Item No.: 08
Site: Potable Water-Engine Changing Room
Violation: No backflow prevention device was installed on the flexible shower hose in the shower room.
Recommendation: Provide a comprehensive cross-connection control program. Protect the following connections to the potable water system against backflow with air gaps or mechanical backflow prevention devices: (17) public toilets, urinals, and shower hoses.
Item No.: 08
Site: Potable Water-Deck 9 Technical Locker 9.6.09
Violation: The relief vent on the backflow prevention device was blocked with a white cap. Also, the water line up to the reduced pressure assembly was not striped blue or blue/green/blue to indicate potable water.
Recommendation: Maintain backflow prevention devices in good repair. Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers. Do not stripe or paint potable water lines after reduced pressure assemblies as potable water.
Item No.: 08
Site: Pantry-Aft Pool Bar
Violation: The chilled water line of the ice machine was not labeled.
Recommendation: Uniquely identify all refrigerant brine lines in all galleys, pantries, and cold rooms to prevent cross-connections.
Item No.: 08
Site: Potable Water-Bunkering Records
Violation: The manual bunkering records for 2 December indicated bunkering began at 9:19, but the halogen value at 30 minutes was not documented.
Recommendation: Adjust the free halogen residual level to at least 2.0 mg/L (ppm) within 30 minutes of the start of the bunkering and production processes.
Item No.: 10
Site: Recreational Water Facilities-Center and Aft Pools
Violation: The water level in both pools was filled approximately ten inches above the skim gutters in the main part of the pool and did not reach the skim gutters located on the beach access portion of the pools.
Recommendation: For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters.
Item No.: 10
Site: Recreational Water Facilities-Center Pool
Violation: The starboard anti-entrapment drain cover was missing one of the nine screws. The pool was immediately closed.
Recommendation: For RWFs with gravity drainage and multiple drains (2 or more drains greater than 3 feet apart), provide either a standard design (not compliant with ASME A112.19.8) drain cover and an alarm, or an ASME A112.19.8 compliant antientrapment/antientanglement drain cover. Ensure the alarm is audible and sounds in both a continuously manned space and at the RWF. Ensure this alarm is for all draining: accidental, routine, and emergency. Ensure anti-entrapment drains are installed according to manufacturer recommendations. For RWFs with gravity drainage and multiple drains (2 or more drains greater than 3 feet apart), provide either a standard design (not compliant with ASME A112.19.8) drain cover and an alarm, or an ASME A112.19.8 compliant antientrapment/antientanglement drain cover.
Item No.: 13
Site: Provisions-Bottle Store
Violation: Black plastic bags labeled 'ENGINE MATERIAL' were stored in the corner of the walk-in refrigerator. Inside the plastic bags were layers of other plastics bags containing soiled rags and boxes with dry cement material. On top of the bags there were four boxes containing coffee, coffee cups, and saucers.
Recommendation: Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control pints in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
Item No.: 13
Site: Galley-Club Restaurant
Violation: A counter-mounted vacuum packaging unit was on a counter in the galley. Staff stated they had not used this equipment in the past 2 months. Reduced oxygen packaging is not allowed by VSP due to the risk of toxin-producing bacteria, such as Clostridium botulinum or perfringens.
Recommendation: Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control pints in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
Item No.: 13
Site: Food Service General-Cooling Logs
Violation: In multiple areas, staff were not cooling cooked potentially hazardous foods properly. Specifically, staff were not checking the food temperatures after 2 hours of cooling to ensure the food was 70°F or less.
Recommendation: Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control pints in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
Item No.: 13
Site: Galley-Time Control
Violation: The service period for lunch embarkation day was over 4 hours, and potentially hazardous foods on the service lines in time control units (i.e. undercounter warmers/refrigerators, bains Marie, cold tops) and in galley time control units (i.e. upright refrigerator, trolleys) did not have 4-hour discard labels.
Recommendation: Because of the risks for foodborne illness inherent to the food operation, ensure the supervisor or person in charge of food operations on the vessel demonstrates to VSP - during inspections and on request - knowledge of foodborne disease prevention, application of the Hazard Analysis Critical Point principles, and the food-safety guidelines in this manual. Ensure that the person in charge demonstrates this knowledge: (1) By compliance with these guidelines; (2) By being a domestically or foreign certified food protection manager who has shown proficiency of required information through passing a test that is part of an accredited program; or (3) By responding correctly to the inspector's questions as they relate to the specific food operation. Ensure that the areas of knowledge include: (1) Describing the relation between prevention of foodborne disease and personal hygiene of a food employee; (2) Explaining the responsibility of the person in charge to prevent transmission of foodborne disease by a food employee who has a disease or medical condition that may cause foodborne disease; (3) Describing the symptoms associated with diseases that are transmissible through food; (4) Explaining the significance of the relation between maintaining the time and temperature of potentially hazardous food and the prevention of foodborne illness; (5) Explaining the hazards involved in the consumption of raw or undercooked meat, poultry, eggs, and fish; (6) Stating the required food temperatures and times for safe cooking of potentially hazardous food, including meat, poultry, eggs, and fish; (7) Stating the required temperatures and times for the safe refrigerated storage, hot holding, cooling, and reheating of potentially hazardous food; (8) Describing the relation between prevention of foodborne illness and management and control of the following: cross-contamination, hand contact with ready-to-eat foods, handwashing, and maintaining food operations in a clean condition and in good repair; (9) Explaining the relation between food safety and providing equipment that is sufficient in number and capacity as well as properly designed, constructed, located, installed, operated, maintained, and cleaned; (10) Explaining correct procedures for cleaning and sanitizing utensils and food-contact surfaces of equipment; (11) Identifying poisonous or toxic materials on the vessel and the procedures necessary to ensure they are safely stored, dispensed, used, and disposed of according to law; (12) Identifying critical-control pints in the operation from purchasing through service that when not controlled may contribute to the transmission of foodborne illness and explaining steps taken to ensure the points are controlled in accordance with the guidelines in this manual.
Item No.: 16
Site: Galley-Time Control
Violation: The time control plan for the crew mess galley and service line stated the set-up time was 1030 and closing/discard time was 1500, a service period of over 4 hours. The potentially hazardous foods located in the time control units in galley and service lines did not have 4-hour discard labels. This was corrected.
Recommendation: If time only-rather than time in conjunction with temperature-is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked or otherwise identified to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours. and (4) Is discarded within 4 hours of placement on time control.
Item No.: 16
Site: Buffet-Muscardine Port Line
Violation: The soup kettle, with a lid, was on time control but not listed on the time control plan or labeled as a time control unit. The service period was over 4 hours, and a 4-hour discard label was not attached.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
Item No.: 16
Site: Provisions-Smoked Salmon Parasite Destruction
Violation: The parasite destruction letter provided by the new cold smoked salmon provider as of October 2016 stated the smoked salmon was frozen to -20°C for 24 hours.
Recommendation: Before service in ready-to-eat form, ensure raw, raw-marinated, partially cooked, or marinated-partially cooked fish and fishery products other than molluscan shellfish are frozen throughout to a temperature of -20°C (-4°F) or below for 168 hours (7 days) in a freezer or to -35°C (-31°F) or below for 15 hours in a blast chiller.
Item No.: 17
Site: Galley-Pastry Cooling Logs
Violation: On December 19th, the triple chocolate cake, mocha chino parfait, and crepe mixture had starting temperatures of 64-68°F for cooling, and less than 2 hours later temperatures of 66-68°F were recorded. No additional notes or corrective actions were indicated on the log. On December 18th, a cooling entry of rice pudding had a temperature of 64°F recorded after 2.15 hours of cooling, and temperatures were not checked at the 2-hour mark.
Recommendation: Cool potentially hazardous food within 4 hours to 5°C (41°F) or less if prepared from ingredients at ambient temperature. Ensure logs documenting cooked potentially hazardous food cooling temperatures and times from the starting points designated in 7.3.5.2.1 thru the control points at 2 and 6 hours are maintained onboard the vessel for a period of 30 days from the date the food was placed in the cooling process. Ensure logs documenting cooling of potentially hazardous foods prepared from ingredients at ambient temperatures, with the start time to the time when 5°C (41 °F) is reached are also maintained for a period of 30 days, beginning with the day of preparation.
Item No.: 17
Site: Galley-Garde Manger Cooling Logs
Violation: On December 8th, a cooling entry of lamb had an initial temperature of 155°F at 1025 and the ending temperature of 36°F at 1025. On December 10th and 12th, cooling entries of bolognese and tomato sauce had initial temperatures of 160-162°F and after temperatures were taken over 2 hours after cooling (2 hours and 10 minutes-2 hours and 20 minutes); these temperatures were below 41°F.
Recommendation: Ensure cooked potentially hazardous food is cooled from 57°C (135°F) to 21°C (70°F) within 2 hours and from 21°C (70°F) to 5°C (41°F) or less within 4 hours. Ensure logs documenting cooked potentially hazardous food cooling temperatures and times from the starting points designated in 7.3.5.2.1 thru the control points at 2 and 6 hours are maintained onboard the vessel for a period of 30 days from the date the food was placed in the cooling process. Ensure logs documenting cooling of potentially hazardous foods prepared from ingredients at ambient temperatures, with the start time to the time when 5°C (41 °F) is reached are also maintained for a period of 30 days, beginning with the day of preparation.
Item No.: 17
Site: Galley-Club Restaurant
Violation: On December 19th, a cooling log entry of demi-glaze was checked after 2 hours and 3 minutes with a temperature of 68°F and a cooling entry of grilled mixed vegetables was checked after 2 hours and 6 minutes with a temperature of 70°F.
Recommendation: Ensure logs documenting cooked potentially hazardous food cooling temperatures and times from the starting points designated in 7.3.5.2.1 thru the control points at 2 and 6 hours are maintained onboard the vessel for a period of 30 days from the date the food was placed in the cooling process. Ensure logs documenting cooling of potentially hazardous foods prepared from ingredients at ambient temperatures, with the start time to the time when 5°C (41 °F) is reached are also maintained for a period of 30 days, beginning with the day of preparation.
Item No.: 19
Site: Other-Engine Changing Room
Violation: Food was stored and food equipment was installed in the engine changing room. The beverage counter had an espresso machine and a croissant warmer installed. Three boxes of tea bags were on the overshelf above the beverage station, and three cases of water were stored on the deck. The undercounter refrigerator had about 10 individual yogurt cups. Paper cups and individual sugar packets were stored in the undercounter neutral cabinet and shelves. A box of sugar packets and wooden spoons were stored in the shower room that was in the changing room, along with other items such two boxes of used oil. The upright refrigerator installed in the room had cartons of milk and water bottles.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck. Do not store foods: (1) In locker rooms; (3) In dressing rooms.
Item No.: 19
Site: Provisions-Bottle Store B. 1. 04
Violation: Black plastic bags labeled 'ENGINE MATERIAL' were stored in the corner of the walk-in refrigerator. Inside the plastic bags were layers of other plastics bags containing soiled rags and boxes with dry cement material. On top of the bags there were four boxes containing coffee, coffee cups, and saucers.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Provisions-Frozen Fish B6
Violation: The foot of a pallet was leaning against boxes of cod fillets.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Provisions-Corridor
Violation: Beer kegs were stored under the electric fly light trap in the corridor across from the fruit store.
Recommendation: Do not locate insect control devices, such as insect light traps, over food storage, food preparation areas, food service stations, or clean equipment. Prevent dead insects and insect fragments from falling on exposed food.
Item No.: 19
Site: Provisions-Fruit Store B.2.16
Violation: The feet of a pallet were leaning against boxes of palmaria palmata.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 19
Site: Provisions-Bottle Store B.1.04
Violation: The foot of a pallet was leaning against boxes of peanuts and alcohol. This was immediately corrected.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 20
Site: Galley-Potwash Clean Area
Violation: At least 10 mixing whisks, stored on the clean racks, had a plastic piece on the surface between the handle and where the whisk wires meet and this plastic was peeling, making cleaning difficult.
Recommendation: Materials used in the construction of multiuse utensils and food contact surfaces of equipment must be: (1) durable, corrosion resistant, and nonabsorbent; (2) sufficient in weight and thickness to withstand repeated warewashing; (3) finished to have a smooth, easily cleanable surface; and (4) resistant to pitting, chipping, crazing, scratching, scoring, distortion and decomposition.
Item No.: 20
Site: Galley-Starboard Ice Machine
Violation: Three slotted fasteners were on the ice thickness probe, which is considered a food-contact surface.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 20
Site: Pantry-Aft Pool Bar
Violation: Three slotted fasteners were in the ice thickness probe of the ice machine.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 21
Site: Other-Engine Changing Room
Violation: The cords under the espresso machine were draped on the counter, which made cleaning difficult.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 22
Site: Galley-Muscardine Potwash
Violation: The potwash machine had been out of order since December 13th. A work order was in place.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 22
Site: Galley-Muscardine Port Dishwash
Violation: The far left nozzle on the upper sanitizing rinse arm of the conveyor dishwasher was partially clogged.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 25
Site: Galley-Muscardine
Violation: An empty sanitizing bucket had a wet rag stored in it.
Recommendation: Restrict wiping cloths to the following: (1) Cloths used for wiping food spills are used for no other purpose; (2) Cloths used for wiping food spills are dry and used for wiping food spills from tableware and single service articles or wet and cleaned, stored in a chemical sanitizer, and used for wiping spills from food-contact and nonfood-contact surfaces of equipment; (3) Dry or wet cloths used with raw animal foods are kept separate from cloths used for other purposes. Wet cloths used with raw animal foods must be kept in a separate sanitizing solution; (4) Wet wiping cloths used with a freshly made sanitizing solution and dry wiping cloths are free of food debris and visible soil.
Item No.: 26
Site: Room Service-Deck 7
Violation: The previously cleaned hot milk dispensers 1 and 2 had food soil in the nozzles.
Recommendation: Ensure food only contacts surfaces of equipment and utensils that are cleaned and sanitized. Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 27
Site: Bar-Grand Bar
Violation: Dust, beyond a day's accumulation, was observed on the counter and equipment wires behind the espresso machine.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Preparation Room-Potwash
Violation: The previously cleaned mixing bowl and other mixing bowl equipment was soiled on the nonfood-contact side and was stored in the clean area.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 27
Site: Other-Engine Changing Room
Violation: The counter under the espresso machine was soiled with coffee debris.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 28
Site: Room Service-Deck 7
Violation: Two trolleys transporting empty champagne flutes to guest cabins were not protected. This was corrected.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 28
Site: Other-Engine Changing Room
Violation: Food was stored and food equipment was installed in the engine changing room. The beverage counter and an espresso machine and a croissant warmer installed. The undercounter refrigerator had about 10 individual yogurt cups. Paper cups and individual sugar packets were stored in the undercounter neutral cabinet and shelves. A box of sugar packets and wooden spoons were stored in the shower room that was in the changing room, along with other items such two boxes of used oil. The upright refrigerator installed in the room had cartons of milk and water bottles.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 29
Site: Galley-Muscardine
Violation: The temperatures of three handwashing sinks in the galley measured 95°F. Staff reported this was due to the coast guard drill, which began at 1015, and was the result of a blackout which impacted the thermostat of the potable water system. The inspection team was in the area from 1225-1235. The water temperature of the handwashing sinks reached 100°F around 1240.
Recommendation: Ensure handwashing sinks are equipped to provide water at a temperature of at least 38°C (100°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, and other types of handwash sinks where the user cannot make temperature adjustments, ensure the temperature provided to the user after the mixing valve does not exceed 49°C (120°F).
Item No.: 29
Site: Galley-Dishwash Area
Violation: The temperature of the handwashing sink next to the conveyor dishwasher was 95°F.
Recommendation: Ensure handwashing sinks are equipped to provide water at a temperature of at least 38°C (100°F) through a mixing valve or combination faucet. For handwash sinks with electronic sensors, and other types of handwash sinks where the user cannot make temperature adjustments, ensure the temperature provided to the user after the mixing valve does not exceed 49°C (120°F).
Item No.: 33
Site: Dining Room-Deck 2
Violation: A temporary buffet was set up for breakfast in the middle of the dining room and the deck was carpeted. Staff stated during the 24 day cruise the buffet was only set up for breakfast.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Do not use carpet in these areas.
Item No.: 33
Site: Bar-Grand Bar
Violation: Dust was noted on the air vents above the espresso machine.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 33
Site: Other-Engine Changing Room
Violation: The deck under the beverage counter was soiled with food and coffee debris.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 34
Site: Provisions-Corridor
Violation: The utility sink next to the hand wash station near the stairs and frozen food store in the provisions hall was leaking.
Recommendation: Ensure a plumbing system in a food area is maintained in good repair.
Item No.: 35
Site: Pantry-Aft Pool Bar
Violation: Water was pooled on the deck below the ice machine.
Recommendation: Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
Item No.: 35
Site: Preparation Room-Potwash
Violation: There was standing water on the deck of the bakery pot wash that was not draining into the drain or scupper.
Recommendation: Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
Item No.: 37
Site: Galley-Soup Station
Violation: Condensation had accumulated on the deckhead above the soup kettles and tilting pans and dripping was observed. No food was impacted.
Recommendation: Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles. Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 37
Site: Galley-Muscardine Port Side
Violation: Condensation was accumulated on the deckhead above the combination oven.
Recommendation: Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles. Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 38
Site: Room Service-Deck 7
Violation: A ladder was stored next to the counter with the counter-mounted milk dispensers.
Recommendation: Ensure maintenance tools such as mops, brooms, and similar items are stored in a designated locker so they do not contaminate food, food-contact surfaces of utensils, and equipment, linens, and single-service and single-use articles.
Item No.: 39
Site: Bar-Center Pool Bar
Violation: Three live fruit flies were observed.
Recommendation: Effectively control the presence of insects to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 39
Site: Pantry-Aft Pool Bar
Violation: One live fruit fly was observed.
Recommendation: Effectively control the presence of insects to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 43
Site: Ventilation-AC Room 4.4
Violation: The condensation collection pan and water droplet eliminator in AP 04.4.01 was soiled with dirt and debris. The condensation collection pan and right bulkhead in AP 04.4.02 was also soiled with dirt and debris.
Recommendation: Inspect evaporative condensers at least annually and clean as necessary to remove scale and sediment. Clean cooling coils and condensate pans as necessary to remove dirt and organic material.
Item No.: 43
Site: Ventilation-Engine Changing Room
Violation: The disinfection of the shower head was not documented.
Recommendation: Clean and disinfect shower heads every 6 months. Disinfect with an appropriate halogen-based disinfectant at 10 ppm for 60 minutes, or an equivalent CT value.
*Inspections scores of 85 or lower are NOT satisfactory