|
|
|
Item No.:
06
|
|
Site:
Potable Water-Bunkered Water Microbiological Monitoring
|
|
Violation:
The ship bunkered potable water in Manaus, Brazil on 4 and 5 December. On 4 December, the ship bunkered from the pier and from a barge. Records documented two samples taken from Manaus on 4 December, but it was unclear if both samples came from the pier or one of the samples was from the barge. Both samples tested negative for coliforms and E.coli.
|
|
Recommendation:
Where available, ensure the vessel has a copy of the most recent microbiologic report from each port before bunkering potable water to verify that the water meets potable standards. Ensure the date of the analysis report is 30 days or less from the date of potable water bunkering, and include an analysis for Escherichia coli at a minimum.
|
|
|
Item No.:
07
|
|
Site:
Potable Water-System Maintenance Log
|
|
Violation:
Staff was disinfecting pipe replacements since September 2014 with 50 ppm of chlorine for 1 minute. No flushing or chlorine concentration after flushing was documented. There were more than 30 disinfection jobs documented with this procedure. Cruise line procedure SMS/PH/PO43 instructed to disinfect with 50 ppm of chlorine for at least 4 hours, flush, and document the end chlorine concentration after flushing.
|
|
Recommendation:
Disinfect after potential contamination by increasing the free residual halogen to at least 50 mg/L (ppm) throughout the affected area and maintain this concentration for 4 hours or by way of another procedure submitted to and accepted by VSP.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-System Maintenance Log
|
|
Violation:
Staff was disinfecting pipe replacements since September 2014 with 50 ppm of chlorine for 1 minute. No flushing or chlorine concentration after flushing was documented. There were more than 30 disinfection jobs documented with this procedure. Cruise line procedure SMS/PH/PO43 instructed to disinfect with 50 ppm of chlorine for at least 4 hours, flush, and document the end chlorine concentration after flushing.
|
|
Recommendation:
Flush the disinfected parts of the system with potable water or otherwise dechlorinate until the free residual halogen is less than or equal to 5.00 mg/L (ppm). Document the free halogen test result.
|
|
|
Item No.:
08
|
|
Site:
Potable Water-Annual Test
|
|
Violation:
Staff was using a procedure meant to test double-check backflow preventers to test the reduced pressure zone (RPz) assemblies, thus making the testing procedure incomplete. Records documented pressure differentials for check valve #1 and #2, but there were no pressure differentials at the point the relief vents opened and started leaking. The procedure for testing RPz was also in the backflow preventer tester storage case.
|
|
Recommendation:
Inspect and test backflow prevention devices requiring testing with a test kit after installation and at least annually. Maintain the test results showing the pressure differences on both sides of the valves for each device.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Whirlpool Shock Halogenation
|
|
Violation:
For a period of over one year, records documented only the start and end times for the shock halogenation of both whirlpools. No halogen concentration at the start and end times were documented. Cruise line procedure SMS/PH/P050 required these halogen concentrations to be recorded.
|
|
Recommendation:
Increase the free residual halogen to at least 10.0 mg/L (ppm) and circulate for at least 1 hour every 24 hours. Test the free residual halogen both at the start and completion of shock halogenation. Superhalogenate the water in the entire RWF system to 10 ppm to include the whirlpool spa/spa pool tub, compensation tank, filter housing, and all associated piping before starting the 1-hour timing.
|
|
|
Item No.:
10
|
|
Site:
Recreational Water Facilities-Turnover Rate
|
|
Violation:
The turnover rate for the pool was not calculated.
|
|
Recommendation:
For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters. Design recirculation systems and equipment, including chemical control equipment, UV disinfection systems, filter, and pumps to maintain adequate water chemistry control while operating at the following minimum turnover rates: (1) swimming pool (VSP 2005 Construction Guidelines or earlier): 6 hours; (2) swimming pool (VSP 2011 Construction Guidelines or later): 4 hours.
|
|
|
Item No.:
13
|
|
Site:
Buffet-La Veranda - Egg Station
|
|
Violation:
The crew member working in this area was equipped with a thermometer, but no alcohol wipes.
|
|
Recommendation:
Equip employees using thermometers with a sufficient supply of alcohol wipes.
|
|
|
Item No.:
19
|
|
Site:
Buffet-La Veranda - Outside Buffet
|
|
Violation:
Bowls of cut pineapple and cut grapefruits out for passenger self service did not have a serving utensil.
|
|
Recommendation:
Provide food-dispensing utensils for each container displayed at a consumer self-service unit such as a buffet or salad bar.
|
|
|
Item No.:
19
|
|
Site:
Galley-Cold Galley
|
|
Violation:
On the preparation counter, a fly was around the container of cut fruits. At one time the fly landed on the fruits. The container of fruits was immediately discarded.
|
|
Recommendation:
Protect food from contamination by storing the food: (3) Where it is not exposed to splash, dust, or other contamination.
|
|
|
Item No.:
19
|
|
Site:
Buffet-La Veranda
|
|
Violation:
A bowl of dried banana chips out for passenger self service did not have a serving utensil.
|
|
Recommendation:
Provide food-dispensing utensils for each container displayed at a consumer self-service unit such as a buffet or salad bar.
|
|
|
Item No.:
22
|
|
Site:
Galley-Dishwash Area
|
|
Violation:
The second to left upper final rinse sanitizing nozzle appeared clogged on the left side, resulting in a narrow spray pattern. Crew members attempted twice to clean out the nozzle with a sharp device.
|
|
Recommendation:
Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines.
|
|
|
Item No.:
27
|
|
Site:
Galley-La Veranda - Dishwash Area
|
|
Violation:
Below the clean landing, the wheels on the two trolleys were soiled with a brown and pink material.
|
|
Recommendation:
Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
|
|
|
Item No.:
30
|
|
Site:
Pantry-Bridge Pantry
|
|
Violation:
The handwashing station had no waste receptacle.
|
|
Recommendation:
Ensure a handwashing facility includes a sink, soap dispenser, single-use towels dispenser, and waste receptacle.
|
|
|
Item No.:
35
|
|
Site:
Pantry-Deck 5
|
|
Violation:
Water pooled on the deck in front of the undercounter warewasher while the machine was in operation and discharging water to the drain.
|
|
Recommendation:
Ensure black and gray water is discharged to the vessel's wastewater disposal system and does not pool on the deck.
|
|
|
Item No.:
36
|
|
Site:
Bar-Stars Lounge
|
|
Violation:
The light intensity was less than 220 lux along the front area of the service counter.
|
|
Recommendation:
In bars and dining room waiter stations, provide 220 lux (20 foot candles) light intensity during cleaning operations.
|
|
|
Item No.:
37
|
|
Site:
Galley-Dishwash Area
|
|
Violation:
Excess condensation was on the bulkhead and deckhead at the soiled end of the machine. Condensation dripped onto the machine from the center exhaust vent.
|
|
Recommendation:
Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads. Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles.
|
|
|
Item No.:
39
|
|
Site:
Galley-Cold Galley
|
|
Violation:
On the preparation counter, a fly was around the container of cut fruits.
|
|
Recommendation:
Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
|
|
|
Item No.:
44
|
|
Site:
Potable Water-Potable Water System Maintenance Log
|
|
Violation:
Staff was disinfecting pipe replacements since September 2014 with 50 ppm of chlorine for 1 minute. No flushing or chlorine concentration after flushing was documented. There were more than 30 disinfection jobs documented with this procedure. Cruise line procedure SMS/PH/PO43 instructed to disinfect with 50 ppm of chlorine for at least 4 hours, flush, and document the end chlorine concentration after flushing.
|
|
Recommendation:
Ensure the supervisor or person in charge of potable water operations on the vessel demonstrates to VSP?during inspections and on request-knowledge of potable water operations, is able to demonstrate this knowledge by compliance with Section 5 of the VSP 2011 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 5 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
44
|
|
Site:
Recreational Water Facilities-Whirlpool Shock Halogenation
|
|
Violation:
For a period of over one year, records documented only the start and end times for the shock halogenation of both whirlpools. No halogen concentration at the start and end times were documented. Cruise line procedure SMS/PH/P050 required these halogen concentrations to be recorded.
|
|
Recommendation:
Ensure the supervisor or person in charge of recreational water operations on the vessel demonstrates to VSP?during inspections and on request ? knowledge of recreational water operations, is able to demonstrate this knowledge by compliance with Section 6 of the VSP 2011 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 6 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|
|
Item No.:
44
|
|
Site:
Potable Water-Annual Test
|
|
Violation:
Staff was using a procedure meant to test double-check backflow perverter's to test the reduced pressure zone (RPz) assemblies, thus making the testing procedure incomplete. Records documented pressure differentials for check valve #1 and #2, but there were no pressure differentials at the point the relief vents opened and started leaking. The procedure for testing RPz was also in the backflow preventer tester storage case.
|
|
Recommendation:
Ensure the supervisor or person in charge of potable water operations on the vessel demonstrates to VSP?during inspections and on request-knowledge of potable water operations, is able to demonstrate this knowledge by compliance with Section 5 of the VSP 2011 Operations Manual or by responding correctly to the inspector?s questions as they relate to the specific operation, and properly trains employees to comply with Section 5 of the VSP 2011 Operations Manual as it relates to their assigned duties.
|
|