Skip directly to site content Skip directly to page options

Inspection Detail Report

  Advanced Search |  Ship Scored 100 |  Green Sheet  |  CDC Home |  VSP Home
 
Cruise Ship: Oceania Marina Cruise Line: Oceania Cruises Inspection Date: 05/10/2016 Inspection Score: 96
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 33
Site: Provisions-Deck 3 FWD Consumables and Equipmenment Locker
Violation: Some bulkheads were made of a soft insulation material or a cage-like structure with many openings, making cleaning difficult. Many areas of the deckhead had exposed pipes and cables, and some of these pipes had dust on top of them. All food equipment was wrapped in plastic wrapping, stored in plastic boxes, or stored in its original packaging. Staff reported they planned to repair and build this area during their dry dock.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, bars, and food and equipment storage areas are constructed and maintained for easy cleaning. Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 37
Site: Preparation Room-Potwash Machine
Violation: Condensate was noted on the deckhead above the potwash machine.
Recommendation: Ensure exhaust ventilation hood systems in food preparation and warewashing areas--including components such as hoods, fans, guards, and ducting--are designed to prevent grease or condensation from draining or dripping onto food, equipment, utensils, linens, and single-service and single-use articles. Ensure ventilation hood systems and devices are sufficient in number and capacity to prevent grease or condensation from collecting on bulkheads and deckheads.
Item No.: 16
Site: Buffet-Terrace Cafe
Violation: Two soup kettles with lids were used as time control units and not labeled as time control units or listed on the time control plan. This was immediately corrected.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such).
Item No.: 26
Site: Galley-Terrace Cafe Potwash
Violation: Two previously cleaned black pans were soiled with food debris. They were immediately sent to be re-cleaned.
Recommendation: Ensure food only contacts surfaces of equipment and utensils that are cleaned and sanitized. Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 16
Site: Galley-Red Ginger
Violation: The chaffing dish was used as a time control unit in the galley and was not labeled as such or listed on the time control plan.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such).
Item No.: 22
Site: Galley-Dishwash- Conveyor Dishwasher
Violation: The leftmost upper nozzle of the final rinse arm was partially clogged and did not produce an effective spray pattern. This was corrected.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 22
Site: Galley-Dishwash
Violation: Water was spraying from the doors of the rack-type glasswasher, causing water to pool on the deck. This was due to one of the lower wash arms missing a plug. This was corrected.
Recommendation: Maintain warewashing equipment in good repair and proper adjustment, including: (1) warewashing equipment is maintained in a state of repair and condition that meets the standards of the materials, design, and construction of these guidelines; (2) water pressure and water temperature-measuring devices are maintained in good repair and accurate within the intended range of use.
Item No.: 33
Site: Galley-Dishwash
Violation: Water was pooled on the deck underneath and to the side of the glasswasher.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 21
Site: Galley-Dishwash Soiled Area
Violation: A table was stored alongside the bulkhead in the soiled area, and Velcro was attached around the side of the tables, making cleaning difficult. This was noted on the last inspection.
Recommendation: Ensure nonfood-contact surfaces of equipment that are exposed to splash, spillage, or other food soiling or that require frequent cleaning are constructed of a corrosion-resistant, nonabsorbent, and smooth material.
Item No.: 39
Site: Galley-Cold Pantry
Violation: One live house fly was observed.
Recommendation: Effectively control the presence of insects to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 33
Site: Galley-Walk-in Refrigerator #5.5.04
Violation: Condensate had pooled inside one of the deckhead light covers. This was corrected.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 27
Site: Buffet-Beverage Station
Violation: Water was leaking and pooling on the counter from the counter-mounted ice and water dispenser.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 34
Site: Buffet-Beverage Station
Violation: Water was leaking and pooling on the counter from the counter-mounted ice and water dispenser. This was corrected.
Recommendation: Ensure a plumbing system in a food area is maintained in good repair.
Item No.: 26
Site: Pantry-Waves Bar
Violation: Grayish debris was noted in the recirculating ice water bath of the ice machine.
Recommendation: Ensure food only contacts surfaces of equipment and utensils that are cleaned and sanitized. Ensure food contact surfaces of equipment and utensils are clean to sight and touch.
Item No.: 02
Site: Medical-Acute Gastroenteritis (AGE) Log
Violation: Medical staff reported asking the reportable crew members if they had additional immediate contacts (i.e. boyfriend, girlfriend, spouse, etc.) besides cabin mates, but it was not documented if they did not.
Recommendation: Maintain the following records on board for 12 months and make them available for review by VSP during inspections and outbreak investigations: (4) interviews with cabin mates and immediate contacts of crew members with AGE [initial, 24-, and 48-hour].
Item No.: 06
Site: Potable Water-Microbiological Sampling
Violation: The test reagents used to analyze water for the presence of E. coli expired on 6 May 2016. Medical staff stated new test reagents had been ordered and were due to arrive the day of the inspection.
Recommendation: If water samples are collected and analyzed by the vessel for the presence of E. coli, analyze the samples using a method accepted in Standard Methods for the Examination of Water and Wastewater. Ensure test kits, incubators, and associated equipment are operated and maintained in accordance with the manufacturers? specifications.
Item No.: 08
Site: Potable Water-Bunker/Production Halogen Injection
Violation: The analyzer probe on the combined bunkering and production line was located about 5 feet (1.5 meters) away from the chlorine and pH injection point.
Recommendation: Obtain water samples for halogen and pH testing from a sample cock and/or a halogen analyzer probe located on the bunker or production water line at least 3 meters (10 feet) after the halogen injection point and before the storage tank.
Item No.: 08
Site: Potable Water-Mineralizer Air Gaps
Violation: The two air gaps on the backwash lines for the mineralizers were not listed on the cross-connection control log.
Recommendation: Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
Item No.: 41
Site: Housekeeping-Outbreak Prevention and Reponse Plan (OPRP)
Violation: The OPRP did not state that a letter informing embarking passengers, following an outbreak on the previous voyage, about the outbreak would be distributed.to passengers prior to embarking. However, a letter template for this scenario was found on the ship's database.
Recommendation: Ensure each vessel has a written OPRP that details standard procedures and policies to specifically address AGE onboard. Include the following in the written OPRP: (4) Procedures for informing passengers and crew members of the outbreak. Ensure this section also includes procedures for notification of passengers embarking the vessel following an outbreak voyage or segment of a voyage.
Item No.: 19
Site: Other-Engine Changing Room
Violation: A coffee station was located in the engine changing room, which included a coffee machine, styrofoam cups, tea bags, artificial sweeteners, and a refrigerator that was not working.
Recommendation: Do not store foods: (1) In locker rooms.
Item No.: 27
Site: Other-Engine Changing Room
Violation: The counter underneath and around the coffee machine noted above was heavily soiled with dust, dirt, and coffee debris.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Other-Engine Changing Room
Violation: Coffee debris was noted on the deck under the counter, and the deck/bulkhead juncture at the coffee station noted above.
Recommendation: Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel). Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 10
Site: Recreational Water Facilities-Main Pool
Violation: The water level in the pool was filled above the skim gutters in the main part of the pool but did not reach the skim gutters on the beach access level. More than half of the beach access around the pool was dry. Staff stated the skim gutters in the main pool were closed and the water level was supposed to be filled to the skim gutters on the beach access. Multiple tests had to be taken around the interactive pool by the inspector and crew to ensure the average free residual chlorine level was above 2.0 ppm.
Recommendation: For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters.
Item No.: 31
Site: Food Service General-Crew and Passenger Beverage Stations
Violation: A container of Clorox bleach wipes was stored adjacent to the coffee and juice machines. Staff reported since they were in an elevated gastrointestinal illness (GI) code they provided these wipes for guests and crew to sanitize the machines prior to use to prevent GI transmission.
Recommendation: Store poisonous or toxic materials used in the cleaning and maintenance of food areas in a cleaning materials locker so they cannot contaminate food, equipment, utensils, linens, and single-service and single-use articles.
*Inspections scores of 85 or lower are NOT satisfactory
Vessel Sanitation Program