Cruise Ship: National Geographic Sea Lion Cruise Line: Lindblad Expeditions Inspection Date: 09/18/2016 Inspection Score: 97
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 01
Site: Medical-24-Hour Report
Violation: The voyage between 4 September and 18 September had one reportable passenger acute gastroenteritis (AGE) case, but the 24-hour report submitted prior to the arrival in Seattle, WA on 18 September listed zero reportable passenger cases.
Recommendation: Ensure the AGE report contains the following: (6) total numbers of reportable cases of AGE among passengers, including those who have disembarked because of illness-even if the number is 0 (zero reporting).
Item No.: 06
Site: Potable Water-Far Point Alarm
Violation: Staff stated the far point analyzer was not equipped with an audible alarm for high and low chlorine residual values.
Recommendation: Provide an audible alarm in a continuously occupied watch station to indicate low and high free halogen readings at the distant point analyzer.
Item No.: 08
Site: Potable Water-Fire Station 4
Violation: The atmospheric vent on the backflow prevention device installed on the first responder hose under fire station 4 was pointed up.
Recommendation: Maintain backflow prevention devices in good repair.
Item No.: 08
Site: Potable Water-Cross Connection Control Log
Violation: The Watts 9D backflow prevention device installed by the hot water tank and reverse osmosis system in the engine room was not listed on the cross connection control log.
Recommendation: Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections.
Item No.: 08
Site: Potable Water-Hot Water Tank
Violation: The hose connected to the hot water tank was under continuous pressure because it had a spray nozzle attached, but the backflow prevention device install at the hot water tank was for non-continuous pressure.
Recommendation: Install a continuous pressure-type backflow preventer when a valve is located downstream from the backflow preventer.
Item No.: 08
Site: Potable Water-Tank Paint
Violation: The paperwork for the paint used in the potable water tank was not available during the inspection. The independent third party documentation verifying the paint used to coat the potable water tank was approved for potable water use was also not available during the inspection.
Recommendation: Ensure the interior coatings on potable water tanks are approved for potable water contact by a certification organization. Follow all manufacturers' recommendations for application, drying, and curing. For the tank coatings used, maintain the following onboard: (1) written documentation of approval from the certification organization (independent of the coating manufacturer); (2) manufacturers' recommendations for application, drying, and curing; and (3) written documentation that the manufacturers' recommendations have been followed for application, drying, and curing.
Item No.: 08
Site: Potable Water-Tank Maintenance
Violation: The potable water tank was cleaned during the October 2015 drydock, but the ship did not document the disinfection procedure or the free halogen residual level prior to the tank being put back into service.
Recommendation: Maintain documentation of all inspections, maintenance, cleaning, and disinfection for 12 months and ensure it is available for review during inspections. Ensure records include a method of disinfection, concentration and contact time of the disinfectant, and a halogen value of less than or equal to 5 ppm before the tank is put back into service.
Item No.: 19
Site: Galley-Pulper Cabinet
Violation: Approximately five bottles of liquor and one bottle of beer were stored in the pulper cabinet. These bottles were immediately removed.
Recommendation: Protect food from contamination by storing the food: (1) Covered or otherwise protected; (2) In a clean, dry location; (3) Where it is not exposed to splash, dust, or other contamination; and (4) At least 15 centimeters (6 inches) above the deck.
Item No.: 28
Site: Bar-Undercounter Refrigerator
Violation: Water from the catch tray was dripping into a stainless steel coffee mug used to steam milk that was stored in the bottom of the refrigerator.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 28
Site: Other-Liquor Store Room
Violation: The far left tube that connected to the soda syrup bag was not in use and touching the deck.
Recommendation: Store cleaned equipment and utensils, laundered linens, and single-service and single-use articles: (1) in a clean, dry location; (2) in a location where they are not exposed to splash, dust, or other contamination; (3) at least 150 millimeters (6 inches) above the deck.
Item No.: 33
Site: Provisions-Dry Store
Violation: The deck around both reach-in refrigerators was not coved. A significant amount of dirt and debris was accumulated in the 90 degree crevice around the right reach-in refrigerator.
Recommendation: Cove all bulkhead/deck, equipment/deck, cabinet/deck, and deck sink coaming/deck junctures (including galleys, pantries, buffets, bars, waiter stations, dining room work counters, provisions, food storage rooms, equipment/utensil storage rooms, and toilet rooms intended for use by galley personnel). Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 34
Site: Bar-Undercounter Refrigerator
Violation: The drain line under the condenser unit in the back of the refrigerator was clogged, which caused water to accumulate in the catch tray and overflow.
Recommendation: Ensure a plumbing system in a food area is maintained in good repair.
*Inspections scores of 85 or lower are NOT satisfactory