Cruise Ship: Seven Seas Navigator Cruise Line: Regent Seven Seas Inspection Date: 08/04/2012 Inspection Score: 92
This cruise ship inspection report lists deficiencies found during the inspection. Additional information corresponding to each item number is available in the latest edition of the VSP Environmental Public Health Standards.

View/Print Summary Report  |  View/Print Corrective Action Statement
Item No.: 08
Site: Potable Water-Water Production
Violation: The water production records did not identify the beginning of the production process, therefore, there was no way to ensure that the free halogen level reached 2.0 ppm within 30 minutes.
Recommendation: Adjust the free halogen residual level to at least 2.0 mg/L (ppm) within 30 minutes of the start of the bunkering and production processes.
Item No.: 08
Site: Potable Water-Cross Connection Control Program
Violation: The cross connection control program included a list of air gaps, but there were no records to indicate that they were being inspected periodically.
Recommendation: Ensure the cross-connection control program includes at a minimum: a complete listing of cross-connections and the backflow prevention method or device for each, so there is a match to the plumbing system component and location. Include air gaps on the listing. Ensure a schedule for inspection frequency is set. Maintain a log documenting the inspection and maintenance in written or electronic form, and ensure it is available for review during inspections. Inspect backflow prevention devices periodically and replace any failed units.
Item No.: 08
Site: Potable Water-Starboard Bunker Station
Violation: At one of the bunker lines, a small rope was being used to keep the filling cap from touching the deck when unscrewed. This was replaced with a non-corroding keeper chain during the inspection.
Recommendation: Ensure the potable water filling line has a screw cap fastened by a noncorroding cable or chain to an adjacent bulkhead or surface in such a manner that the cap cannot touch the deck when hanging free. Ensure the hose connections are unique and fit only the potable water hoses.
Item No.: 08
Site: Potable Water-Permeate Water Lines
Violation: The permeate water lines directed to the potable water system were not painted or striped in accordance with ISO 14726 (blue/gray/blue).
Recommendation: Stripe or paint potable water lines either in accordance with ISO 14726 (blue/green/blue) or blue only. Stripe or paint distillate and permeate lines directed to the potable water system in accordance with ISO 14726 (blue/gray/blue). Ensure no other lines have the above color designations. Stripe or paint these lines at 5 meters (15 feet) intervals and on each side of partitions, decks, and bulkheads, except where decor would be marred by such markings, including potable water supply lines in technical lockers.
Item No.: 08
Site: Potable Water-High Saline Discharge
Violation: The air gap for the air relief valve on the reduced pressure backflow device was obstructed by plastic bottles used to funnel discharged water. The plastic bottles were removed.
Recommendation: Ensure air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 25 millimeters (1 inch).
Item No.: 08
Site: Potable Water-Technical Water Filling
Violation: The air gap on the technical water filling line was not at least twice the diameter of the supply line. This was corrected during the inspection.
Recommendation: Ensure air gaps are at least twice the diameter of the delivery fixture opening and a minimum of 25 millimeters (1 inch).
Item No.: 10
Site: Recreational Water Facilities-Hair and Lint Strainer
Violation: Documentation for the cleaning, rinsing, and disinfection of the hair and lint strainer and housing for the swimming pool was not available.
Recommendation: Clean, rinse, and disinfect the hair and lint strainer and hair and lint strainer housing on all RWFs weekly. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant. At a minimum, use a 50-ppm solution for 1 minute, or equivalent CT value. Maintain records on all inspection and cleaning procedures.
Item No.: 10
Site: Recreational Water Facilities-Filter Housing Cleaning and Disinfection
Violation: Documentation for the cleaning, rinsing, and disinfection of the filter housings for the RWFs was not available.
Recommendation: Clean, rinse, and disinfect the filter housing before the new filter media is placed in it. Ensure disinfection is accomplished with an appropriate halogen-based disinfectant. At a minimum, use a 50-ppm solution for 1 minute, or equivalent CT value. Maintain records on all inspection and cleaning procedures.
Item No.: 10
Site: Recreational Water Facilities-Turnover Rates / Bather Loads
Violation: Flow meters were not installed on the RWFs and thus, the ship staff could not accurately calculate the turnover rates and bather loads.
Recommendation: For RWFs with skim gutters, ensure that the fill level of the RWF is to the level of the skim gutters. Design recirculation systems and equipment, including chemical control equipment, UV disinfection systems, filter, and pumps to maintain adequate water chemistry control while operating at the following minimum turnover rates: (1) swimming pool (VSP 2005 Construction Guidelines or earlier): 6 hours; (2) swimming pool (VSP 2011 Construction Guidelines or later): 4 hours; (3) children's pool: 0.5 hours; (4) wading pool: 1 hour; (5) whirlpool spa: 0.5 hours; (6) spa pool: 2 hours; (7) interactive RWF or activity pool less than 610 millimeters (24 inches) deep: 1 hour; (8) interactive RWF or activity pool greater than 610 millimeters (24 inches) deep: 2 hours; and (9) baby-only water facility: 0.5 hours. Ensure an RWF slide that is combined with a pool has a turnover rate that matches the rate for the pool. Maintain documentation on the maximum bather load for each RWF. Ensure the maximum bather load is based on the following factor: one person per five gallons (19 liters) per minute of recirculation flow.
Item No.: 10
Site: Recreational Water Facilities-Test Kit
Violation: There was no test kit available that could test for total chlorine and total alkalinity.
Recommendation: Ensure a test kit is available for testing water quality parameters, including free and total halogen levels (chlorine and bromine, where applicable), pH, and total alkalinity. Ensure that test kits are accurate to within 0.2 mg/L (ppm) for halogen and have a testing range of free residual halogen normally maintained in the RWF. Ensure test kits for pH are accurate to within 0.2. Ensure all reagents are not past their expiration dates.
Item No.: 10
Site: Recreational Water Facilities-Water Chemistry
Violation: The RWF's flow rates, free and combined chlorine levels, and total alkalinity were not being monitored,
Recommendation: Monitor and adjust the RWF?s flow rates, free and combined halogen levels, pH, total alkalinity, and clarity as recommended by the manufacturer and to maintain optimum public health protection and water chemistry.
Item No.: 10
Site: Recreational Water Facilities-Automated pH Testing
Violation: There were no working chart recorders or electronic data loggers with security features that record pH for each individual recreational water facility.
Recommendation: Install chart recorders or electronic data loggers with security features that record pH measurements for each individual RWF. Ensure the sample line for the analyzer probe (monitoring) is either directly from the RWF or on the return line from each RWF and before the compensation tank. Install appropriate sample taps for analyzer calibration. Provide an audible alarm in a continuously occupied watch station to indicate low and high free halogen and pH readings in each RWF.
Item No.: 10
Site: Recreational Water Facilities-Antientrapment Drain Covers
Violation: The drain covers for the swimming pool and the 2 whirlpools do not conform with ASME A112.19.8 standards. The drains in the pool were gravity, multiple, and greater than 3 feet apart with no alarm. The drains in the whirlpool were gravity, multiple, and less than 3 feet apart.
Recommendation: For RWFs with gravity drainage and multiple drains (2 or more drains greater than 3 feet apart), provide either a standard design (not compliant with ASME A112.19.8) drain cover and an alarm, or an ASME A112.19.8 compliant antientrapment/antientanglement drain cover. Ensure the alarm is audible and sounds in both a continuously manned space and at the RWF. Ensure this alarm is for all draining: accidental, routine, and emergency. For RWFs with gravity drainage and a single blockable drain or multiple drains less than 3 feet apart, provide an ASME A112.19.8 compliant antientrapment/antientanglement drain cover and a gravity drainage system.
Item No.: 43
Site: Ventilation-AC Station 5.113 - Unit104
Violation: There was a large amount of dust and debris inside the supply fan compartment of this unit. Also, there was a large amount of dust buildup on the air filters for this unit.
Recommendation: Keep air handling units clean.
Item No.: 41
Site: Housekeeping-Outbreak Prevention and Response Plan (OPRP)
Violation: The OPRP did not include health and safety procedures to minimize respiratory and dermal exposures to both passengers and crew when sanitizing public and common areas.
Recommendation: Ensure each vessel has a written OPRP that details standard procedures and policies to specifically address AGE onboard. Include the following in the written OPRP: (c) Health and safety procedures to minimize respiratory and dermal exposures to both passengers and crew.
Item No.: 28
Site: Galley-Dishwash
Violation: On the clean equipment and utensil storage stands, there were a number of plates, bowls, and carafes that were not covered or inverted. This was corrected.
Recommendation: Store clean equipment and utensils in a self-draining position that allows air drying, and covered or inverted.
Item No.: 22
Site: Galley-Dishwash
Violation: The fresh hot water sanitizing rinse was measured at 10 psi by the pressure gauge of the in-use, single-rack, hood-type dishwash machine. The data plate indicated a required pressure of 15 to 25 psi.
Recommendation: Ensure pressure measuring devices that display pressures in the water supply line for the fresh hot water sanitizing rinse have increments of 7 kilopascals (1 pound per square inch or 0.07 bar) or smaller and are accurate to within 14 kilopascals (within 2 pounds per square inch or within 0.14 bar) in the 100-170 kilopascals (15-25 pounds per square inch or 1.03-1.72 bars) range.
Item No.: 16
Site: Buffet-La Veranda
Violation: The #7 undercounter refrigerator at the port side desert counter, was labeled as being on time control but was not described on the time control plan.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
Item No.: 16
Site: Buffet-La Veranda - Coffee Station
Violation: The milk inside the coffee machine refrigerator was on time control but was not labeled with set up and discard times. The milk is replaced every four hours, 24 hours a day according to the staff. This information was not specified in the time control plan.
Recommendation: If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (3) Is marked or otherwise identified to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours. and (4) Is discarded within 4 hours of placement on time control.
Item No.: 20
Site: Food Service General-Ice Machines
Violation: The upper technical compartments of the ice machines in pantries and galleys had several food-contact surfaces that were corroded. There were also slotted fasteners on the water tray.
Recommendation: Ensure multiuse food-contact surfaces are: (1) Smooth; (2) Free of breaks, open seams greater than 0.8 mm (1/32 inch), cracks, chips, inclusions, pits, and similar imperfections; Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 36
Site: Galley-Room Service Pantry
Violation: The light intensity above the food preparation counter at the back of the pantry was less than 220 lux.
Recommendation: Ensure the light intensity is at least 220 lux (20 foot candles) on food preparation surfaces, and at a distance of 75 centimeters (30 inches) above the deck in food preparation areas, handwashing facilities, warewashing areas, equipment, and utensil storage, pantries, toilet rooms, and consumer self-service areas.
Item No.: 21
Site: Food Service General-Technical Compartments
Violation: The technical compartments of multiple upright and undercounter refrigerators showed many signs of heavy corrosion on mechanical parts, insulation, and panels. This was observed in buffets, galleys, pantries, and food preparation areas.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 27
Site: Food Service General-Technical Compartments
Violation: The technical compartments of most upright and undercounter refrigerators were heavily soiled with debris and colored materials that appeared to be mold. This was observed in buffets, galleys, pantries, and food preparation areas.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 33
Site: Food Service General-Technical Compartments
Violation: The technical compartments of most upright refrigerators showed many openings to void spaces where mostly pipes or power cables penetrated bulkheads and deckheads. This was observed in buffets, galleys, pantries, and food preparation areas.
Recommendation: Ensure decks, bulkheads, and deckheads in food preparation, warewashing, pantries, and storage areas are maintained in good repair.
Item No.: 20
Site: Galley-Room Service Coffee Station
Violation: There were at least 8 slotted fasteners on the food splash zone of the espresso machine.
Recommendation: Ensure multiuse food-contact surfaces are:Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 16
Site: Room Service-Consumer Advisory
Violation: The 24-hour room service in-suite menu did not have a consumer advisory. There were animal-derived products on the menu that could be ordered by the consumer in an undercooked form.
Recommendation: If an animal food such as beef, eggs, fish, lamb, milk, pork, poultry, or shellfish that is raw, undercooked, or not otherwise processed to eliminate pathogens is offered in a ready-to-eat form or as a raw ingredient in another ready-to-eat food, ensure the consumer is informed by way of disclosure using menu advisories, placards, or other easily visible written means of the significantly increased risk to certain especially vulnerable consumers eating such foods in raw or undercooked form. Locate the advisory at the outlets where these types of food are served. Ensure that raw shell egg preparations are not used in uncooked products as described in section 7.3.3.2.3. Ensure that disclosure is made by the following method: (2) On a menu using an asterisk at the animal-derived foods requiring disclosure and a footnote with a statement indicating that consuming raw or undercooked meats, seafood, shellfish, eggs, milk, or poultry may increase your risk for foodborne illness, especially if you have certain medical conditions.
Item No.: 16
Site: Galley-Cold Galley
Violation: There were several potentially hazardous foods labeled with different set up and discard times then those indicated on the time control plan.
Recommendation: Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet.
Item No.: 21
Site: Galley-Soup Station
Violation: There were difficult to clean seams on the back of the turning handles of the tilting pans and kettles.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 20
Site: Galley-Hot Galley
Violation: The right deep fat fryer had 1 slotted fastener in direct contact with the oil.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 22
Site: Galley-Lift
Violation: There was a cutting board and hotel pan laying on the deck and against the bulkhead. Staff stated that those utensils were transported to be washed and sanitized.
Recommendation: Store soiled items off the deck and at soiled staging areas.
Item No.: 21
Site: Galley-
Violation: There were difficult to clean seams on the back of the turning handles of the tilting pan and kettle.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 20
Site: Galley-Hot Galley
Violation: The deep fat fryer had 2 slotted fasteners in the food splash zone.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 20
Site: Buffet-Officers Mess
Violation: There were at least 5 slotted fasteners in the food splash zone of the espresso machine.
Recommendation: Use only low profile, nonslotted, noncorroding, and easy-to-clean fasteners on food-contact surfaces and in splash zones. Prohibit the use of exposed slotted screws, Phillips head screws, or pop rivets in these areas.
Item No.: 39
Site: Provisions-Dry Store #13
Violation: During the evaluation of the area, there were at least 5 sightings of small cockroaches and ants under the pallets aligned against the aft bulkhead. There was a seam along the deck/bulkhead juncture where the pests were observed going in and out. One cockroach was sighted on top of a pallet. The staff engaged in corrective actions during the inspection.
Recommendation: Effectively control the presence of insects, rodents, and other pests to minimize their presence in the food storage, preparation, and service areas and warewashing and utensil storage areas aboard a vessel.
Item No.: 33
Site: Provisions-Decks
Violation: The decks under the pallets in most store rooms were heavily soiled with old liquid food spills, food remnants, and dust accumulations.
Recommendation: Ensure decks, bulkheads, deckheads, and attached equipment in food preparation, warewashing, pantries, and storage areas are cleaned as often as necessary.
Item No.: 27
Site: Preparation Room-Fish
Violation: The door gasket of the upright refrigerator was soiled with a dark and moist material.
Recommendation: Ensure nonfood-contact surfaces of equipment are kept free of an accumulation of dust, dirt, food residue, and other debris.
Item No.: 21
Site: Preparation Room-
Violation: The gasket of the preparation room front door was held by many pieces of clear tape making cleaning difficult.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.
Item No.: 16
Site: Bar-Navigator Lounge
Violation: The milk was labeled with a different set up and discard time then what was indicated on the time control plan.
Recommendation: If time only?rather than time in conjunction with temperature?is used as the public health control for a working supply of potentially hazardous food before cooking, or for ready-to-eat potentially hazardous food that is displayed or held for service for immediate consumption, ensure the food (1) Has an initial temperature of 5°C (41°F) or less or 57°C (135°F) or greater before placement on time control. (2) Is not be placed on temperature control again. (3) Is marked or otherwise identified to indicate the time 4 hours past the point in time when the food is removed from temperature control (if the time between service set-up and closing is greater than 4 hours. and (4) Is discarded within 4 hours of placement on time control. Maintain a written time control plan(s) that ensures compliance with these guidelines on the vessel and make it available for review during inspections. Post a time control plan at each outlet where time control is used. Ensure plan(s): (1) Includes set-up and discard times for each outlet. (2) List refrigeration and hot holding units (compartments and cabinets) on time control (the physical units must also be labeled as such). (3) Describe or show the flow of potentially hazardous food from when last in temperature control to placement in time control and discard.
Item No.: 21
Site: Food Service General-Trolley Wheels
Violation: There were several trolleys throughout the food areas with heavily corroded wheel casters and/or damaged wheels which made cleaning difficult.
Recommendation: Ensure nonfood-contact surfaces are free of unnecessary ledges, projections, and crevices, and designed and constructed to allow easy cleaning and to facilitate maintenance.